background image

I.L. 32-693 A

Page 4

Effective September 1998

The output current is a function of the line voltage, which
must be sinusoidal and have good regulation.

If the Test Kit 

RESET lamp will not light, check to make

sure that no trip LED’s are lit on the Trip Unit.  If so, press
the “trip reset” pushbutton on the face of the Trip Unit.

2.2  CIRCUIT BREAKER INFORMATION

2.2.1  TRIP UNIT TOLERANCE BANDS

Long Delay Times of the Trip Unit are top of band,
therefore expect shorter times when testing.

Short Time, Instantaneous, and Ground Fault values
are mid-band, which have +/- 10% tolerance.

2.2.2  TRIP UNIT TEST GUIDELINES

Testing of the Trip Unit must be performed with the Trip
Unit properly installed in the breaker.

The long time function has a memory circuit with a reset
time of 36 times the long delay time setting; i.e., for a LDT
setting of 4 seconds the reset time is 144 seconds (36x4).
Therefore, for long delay time tests, there must be a time
delay greater than the calculated reset time or the ac
control power to the Trip Unit must be interrupted between
tests to clear the memory circuit. To do this, remove the ac
supply to the Auxiliary Power Module rather than discon-
necting the plug from the Test Kit Adapter. A thermal
memory jumper may need to be repositioned to the
“inactive” position to disable the thermal memory. This
jumper is shipped from the factory in the “active” position.

If a trip function LED on the Trip Unit is lit prior to a test,
press the “trip reset” pushbutton on the Trip Unit.

When bench testing a breaker wired for zone interlock
applications, shorting plug 8779C02G06 must be installed
per Figure 5.

SECTION 3:  CHECKING THE TEST KIT

3.1  GENERAL INFORMATION

This check should be performed when the Test Kit is first
received, or for a maintenance check.  A more rigorous
check would be to perform all Trip Unit tests on a standard
Trip Unit.

3.2  HARDWARE CONNECTIONS (REFER TO FIGURE 2)

1.

Connect the 11-pin banana plug on the Test Kit to the
corresponding port on the Test Kit Adapter.

2.

Connect the 14-pin plug from the Test Kit Adapter into
the corresponding test port on the Trip Unit.

3.3  SETTING THE TEST KIT

1.

TIMER ON/OFF switch to “OFF”.

2.

HI / LO AMPS  switch to “LO AMPS”.

3.

CURRENT ADJUSTMENT  to “ZERO”.

3.4  TESTING THE TEST KIT

1.

Plug the APM and the Test Kit into 120 volt, 60 Hz
source. (Test Kit can be used on 50 Hz but timer
readings must be multiplied by 6/5.)

2.

Turn the Test Kit 

POWER ON/OFF  switch “ON”.

2A.

POWER ON/OFF  pilot lamp (red) should light.

2B.

RESET  pilot lamp (amber) should light. If RESET  pilot
lamp is not lit, push 

RESET  button. RESET  pilot lamp

should then light.

3.

Turn 

TIMER ON/OFF  switch to “ON”. Timer should not

run.

4.

Push 

TEST   button.

4A. 

TEST  pilot lamp (red) should light.

4B.

RESET  pilot lamp (amber) should go out.

4C.

TIMER  should operate, counting seconds.

5.

Operate 

STOP  toggle switch (momentary) to “STOP”.

5A.

TIMER  should stop.

5B.

RESET  pilot lamp (amber) should light.

5C.

TEST  pilot lamp (red) should go out.

6.

Push manual 

RESET button on timer. TIMER  should

reset to zero.

7.

Hold 

CALIB toggle switch (momentary) in “CALIB”

position and turn 

CURRENT ADJUSTMENT knob from

zero to maximum. Ammeter should read from zero to
approximately 8 amperes.

Summary of Contents for Cutler-Hammer 140D481G02R

Page 1: ...OINSTALLORPERFORMMAINTE NANCEONEQUIPMENTWHILEITISENERGIZED DEATH ORSEVEREPERSONALINJURYCANRESULTFROM CONTACTWITHENERGIZEDEQUIPMENT ALWAYS VERIFYTHATNOVOLTAGEISPRESENTBEFOREPRO CEEDINGWITHTHETASKANDALW...

Page 2: ...CTION 4 TESTINGTHETRIPUNIT 4 1 Legend 5 4 2 General Setup 5 4 3 Checking theTrip Unit 5 4 4 CheckingLongDelayPickup 5 4 5 Checking Long Delay Time 6 4 6 Checking Instantaneous 6 4 7 Checking Short Del...

Page 3: ...ction GROUND TEST For testing the Ground Fault function EXT AM Allows for connection of an external ammeter to read current levels Jumper must be installed when not using external ammeter CIRCUIT SELE...

Page 4: ...on on the Trip Unit When bench testing a breaker wired for zone interlock applications shorting plug 8779C02G06 must be installed per Figure 5 SECTION 3 CHECKINGTHETEST KIT 3 1 GENERAL INFORMATION Thi...

Page 5: ...t timer readings must be multiplied by 6 5 The green Unit Status LED should flash indicating that theTrip Unit is operational 3 Turn theTest Kit POWER switch ON 4 It is recommended that a check of the...

Page 6: ...mentarily to read the trip current 4 5 CHECKING LONG DELAYTIME L D T SEE SECTION 2 2 2 REGARDING THETRIP UNIT S THERMAL MEMORY CIRCUIT 1 Set the Test Kit as follows 1A TIMER switch to OFF 1B HI LO AMP...

Page 7: ...exciting current 4 8 CHECKING SHORT DELAYTIME IF APPLICABLE Note Zone Selective Interlocking essentially disables Short Delay Time This function is provided as a standard feature on all Magnum Trip U...

Page 8: ...Zone Interlock wiring breaker is beyond the test position install the Zone Interlock Defeat adapter 4 While holding the GROUND TEST momentary switch and the CALIB switch in the down positions turn CU...

Page 9: ...t Current Pickup Settings Primary Amperes Installed RatingPlug Amperes I n 25 30 35 40 50 60 75 1 0 100 25 30 35 40 50 60 75 100 200 50 60 70 80 100 120 150 200 250 63 75 88 100 125 150 188 250 300 75...

Page 10: ...8 9 10 11 12 13 14 15 10 EXT AM Allows for connection of an external ammeter to read current levels Jumper must be installed when not using external ammeter 11 CIRCUIT SELECTOR Permits checking of all...

Page 11: ...ptember 1998 SECTION5 FIGURESANDTABLES Figure 2 Test Kit and Adapter Figure 3 Zone Interlock Shorting Plug Figure 4 Trip Unit Face Plate Showing Test Port Connec tion Figure 5 Zone Interlock Shorting...

Page 12: ...SOFFITNESSFORAPARTICULARPURPOSE ORMERCHANTABILITY ORWARRANTIESARISINGFROMCOURSEOFDEALINGORUSAGEOFTRADE AREMADE REGARDINGTHEINFORMATION RECOMMENDATIONSANDDESCRIPTIONSCONTAINEDHEREIN Innoeventwill Cutle...

Reviews: