Instructions Publication
P51995
Effective July 2017
CurrentWatch™ EGFL Series Ground Fault Sensors
Large Aperture Ground Fault Sensors with
Auto Reset
NNrmally Entrgiztd MNdtls
Used for detecting ground faults and loss of control power.
Output
No Power
Control Power Applied
No Fault
Fault Detected
Output
Status
LED
Output
Status
LED
Output
Status LED
N.C.
Closed
Off
Open
Off
Closed
On
N.O.
Open
Off
Closed
Off
Open
On
NNrmally Dt-Entrgiztd MNdtls
Used for detecting ground faults only.
Output
No Power
Control Power Applied
No Fault
Fault Detected
Output
Status
LED
Output
Status
LED
Output
Status LED
N.C.
Closed
Off
Closed
Off
Open
On
N.O.
Open
Off
Open
Off
Closed
On
Power Supply Notes
All low-current ground-fault sensors are sensitive devices that
require reasonable care in system design to avoid false trips caused
by high electrical noise levels. Keep in mind that the best way to
reduce noise in a system is to suppress it at its source.
•
Keep the sensor power isolated from noisy circuits.
•
Do not power the sensor with the same circuit that switches con-
tactors or other high current inductive loads.
System Grounding
Good design practice and code require that all AC power systems
be grounded. The EGFL Series sensors are designed to work on
grounded AC power systems. They may not operate properly on
ungrounded systems.
Specifications
Specification
Value
Power Supply
120 VAC (Operates from 66-132 V, 50-400 27 Hz)
24 VAC/DC (Operates from 19.2-28.8 V)
Voltage Range
Up to 1,500 VAC (Monitored Circuit)
Power Consumption
2.5 W
Output
SPDT Form C Electromechanical Relay with Auto Reset upon
removal of fault condition
Output Rating
1.0 A @ 120 VAC
2.0 A @ 30 VDC
Response Time
15 ms: At 500% Over Setpoint
60 ms: At 50% Over Setpoint
200 ms: At 5% Over Setpoint
Setpoint Range
Adjustable Setpoints: 5, 10, 30 mA (by Jumper)
Frequency Range
50-400 Hz (Monitored Circuit)
Housing
UL94V-0 Flammability Rated
Dimensions
Case: 4.25 in. H x 3.0 in. W x 3.25 in. D (108 x 76 x 83 mm)
Aperture: 1.875 in. (47 mm) dia.
LED Indicators
Green = Power Supply Energized
Red = Relay Has Operated
Environmental
Operating Temperature: +5 to +158°F (-15 to +70°C)
Humidity: 0-95% RH, Non-Condensing
Approvals
UL Listed E117028
UL Tested to Canadian Safety Standards
CE
RoHs Compliant