INM MTL 130-0200 Rev 4
15
Table 1
- Common groups (continued)
Send
Function
Reply (verbose)
Reply (terse)
Limits (where applicable)
Notes
AxPy
Parameters.
P9 Terse=0
P9=1
0 or 1
1 to set instrument into terse
mode – 0 to set verbose
P8 A2 Mode=1
P8 =1
0 to 3
0, 1, 2, 3 in terse - Off, High,
Low, status in verbose
P7 A2 Hyst=1.0%
P7 =1.0
1 to 10 (1dp)
Alarm hysteresis
P6 A2 Level=5.0%
P6 =5.0
0 to 100
Alarm trip point
P5 A1 Mode=1
P5 =1
As alarm 2
As alarm 2
P4 A1 Hyst=1.0%
P4 =1.0
As alarm 2
As alarm 2
P3 A1 Level=5.0%
P3 =5.0
As alarm 2
As alarm 2
P2 4mA=0%
P2 =0
Will show 0V or 4mA
depending on variant.
P1 20mA=50%
P1 =50
0 to 100
Zero and FSD limits are
interactive.
AxRy
Reading
* see (8) below
R5 Comp2=N/A
R5 =0
R4 Temp=Normal
R4 =1
Heater state – see also heater
errors.
R3 Alarm2=Normal
R3 =0
0 to 2
Alarm state – Off, Normal,
ALARM or N/A (if not fitted)
R2 Alarm1=Normal
R2 =0
0 to 2
In terse mode alarm state is
1 in alarm and 0 for all other
states
R1 Conc=5.00%
R1 =5.00
Instrument range and resolution
Measure and Concentration
Notes on readings:- In over-range condition (110% of instrument span) xxxxx will be ‘+++++’ (e.g. ‘R1 Conc= +++++’). Similarly in under-range
condition (-5% of instrument span) xxxxx will be ‘-----’. In the case of a system error R1 will be replaced by the error code e.g. ? 72 In verbose
mode a brief fault description will be appended. ‘Conc’ & ‘%’ are determined by sensor type and unit – see ‘U’ below. Resolution is applica-
tion dependant. Where a fault is present in the secondary reading it will be indicated by a text description in verbose mode and by a code in
the case of Zr units (heater does not return a numeric value in R4) or by -999 or +999 to indicate downscale or upscale failures respectively.
AxUy
Unit
(read only)
U13 Test Flags=0
U13=0
U12 Factory Flags=0
U12=0
U11 Output=mA*
U11=1
Analogue output: 0=4/20mA,
1= 0/1V, 2 = 0/5V, 3=0/20mA
U10 Sens 2 Ch=1
U10=1
Sens 2 ADC chan (9)
U9 R2 unit=mV
U9=2
U8 R2 type=T/C
U8 =14
U7 R1 Ch=1
U7 =1
U6 R1 unit=%
U6 =1
U5 R1 type=Z
U5 =13
U4 F/w rev=0.24
U4 =0.24
U3 F/w p/n=290-6031
U3 =290-6031
U2 S/n = I-700123
U2=I-700123
U1 Addr=0
U1 =0
Sensor Card Address
Summary of Contents for Crouse-Hinds Z130
Page 4: ...iv INM MTL 130 0200 Rev 4 THIS PAGE IS LEFT INTENTIONALLY BLANK...
Page 12: ...8 INM MTL 130 0200 Rev 4 Figure 3 130 series menu...
Page 21: ...INM MTL 130 0200 Rev 4 17 THIS PAGE IS LEFT INTENTIONALLY BLANK...
Page 22: ...18 INM MTL 130 0200 Rev 4 THIS PAGE IS LEFT INTENTIONALLY BLANK...
Page 23: ...INM MTL 130 0200 Rev 4 19 THIS PAGE IS LEFT INTENTIONALLY BLANK...