GROUNDING

All transients are taken to the RackShield 

enclosure ground stud.

The RackShield ground must be connected to the 

same AC ground reference used by the system 

being protected. The RackShield must also be 

located as close as possible to the system being 

protected. (i.e. communication adapter, CRT, etc.) 

The ground lead should be as short as possible. It 

must be at least No. 14AWG wire with no bends 

of less that a two inch radius.

The RackShield ground stud must be connected 

to the same reference point used by the AC 

power line transient suppressor. This is the power 

safety ground wire (green wire) such as in an AC 

receptacle.

NOTE:

 The protected device should also have AC 

suppression or it will be vulnerable to transients 

from the incoming AC power. This can show up as 

failures on the communication interface.

If devices are received in a damaged condition, 

please notify the transportation company. Please 

retain all containers and packing materials for 

inspection.

Summary of Contents for CROUSE-HINDS MTL RackShield Series

Page 1: ...e variety of standard communications protocols including RS232 RS422 RS485 Lease Line Telephone Networks LLTN and Public Switched Telephone Networks PSTN IMPORTANT SAFETY INSTRUCTIONS WARNING Never install external data communication wiring during a lightning storm WARNING This product is intended for INDOOR USE ONLY INSTALLATION 1 Read and understand all instructions 2 Slide modules into any open...

Page 2: ... range November 2016 2 INS 801 726 Rev B ground automatically provided that the rack housing ground wire is connected to the same reference used by the system being protected Please refer to the section on grounding ...

Page 3: ...must be at least No 14AWG wire with no bends of less that a two inch radius The RackShield ground stud must be connected to the same reference point used by the AC power line transient suppressor This is the power safety ground wire green wire such as in an AC receptacle NOTE The protected device should also have AC suppression or it will be vulnerable to transients from the incoming AC power This...

Page 4: ...India No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Milano Italy Tel 39 02 959501 Fax 39 02 95950759 E mail chmninfo eaton com JAPAN Cooper Crouse Hinds Japan KK MT Building 3F 2 7 5 Shiba Daimon Minato ku Tokyo Japan 105 0012 Tel...

Reviews: