November 2016
INS 801-726 Rev B

Instruction sheet 

MTL surge protection

MTL RackShield range

 

Communication Transient Voltage Surge Suppressor

Eaton Electric Limited, 

Great Marlings, Butterfield, Luton
Beds, LU2 8DL, UK.
Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283
E-mail: [email protected]
www.mtl-inst.com
© 2016 Eaton 
All Rights Reserved
Publication No. INS 801-726 Rev B
November 2016

1

INTRODUCTION

The RackShield is a modular data/telephone 

communications transient suppression 

system specifically designed to protect the 

communication I/O ports on sensitive equipment 

from the harmful effects of transient voltages and 

surges caused either externally by sources such 

as lightning and utility load switching or internally 

by electrostatic discharge (ESD) or even a user’s 

own equipment. The RackShield Series can 

incorporate up to 12 protection modules that can 

be individually configured to meet a wide variety 

of standard communications protocols including 

RS232, RS422, RS485, Lease Line Telephone 

Networks (LLTN) and Public Switched Telephone 

Networks (PSTN).

IMPORTANT SAFETY INSTRUCTIONS

WARNING

 

Never install external data 

communication wiring during a  

lightning storm.

WARNING

 

This product is intended for  

INDOOR USE ONLY.

INSTALLATION

1.   Read and understand all instructions.

2.   Slide modules into any open bay and press  

 

firmly to ensure that the module locks  

 

into place.

3.   To remove module apply pressure to the  

 

release mechanism under the unit and gently  

 

pull out.

4.   Mount the enclosure in a 19” rack or to the  

 

wall by removing and rotating the mounting  

 brackets.

5.   Route the data communication line(s) from  

 

the equipment and connect the line to the  

 

“OUT” connector(s) on the enclosure.

6.   Route the line side of the data communication  

 

line(s) and connect this line to the “IN”  

 

connector(s) on the enclosure.

7.   Be sure to keep the protected and  

 

unprotected lines separated.

8.   Connect the ground to the enclosure ground  

 

stud (see grounding section).

9.  

SAVE THESE INSTRUCTION

Modules easily slide-in to the RackShield and 

Summary of Contents for CROUSE-HINDS MTL RackShield Series

Page 1: ...e variety of standard communications protocols including RS232 RS422 RS485 Lease Line Telephone Networks LLTN and Public Switched Telephone Networks PSTN IMPORTANT SAFETY INSTRUCTIONS WARNING Never install external data communication wiring during a lightning storm WARNING This product is intended for INDOOR USE ONLY INSTALLATION 1 Read and understand all instructions 2 Slide modules into any open...

Page 2: ... range November 2016 2 INS 801 726 Rev B ground automatically provided that the rack housing ground wire is connected to the same reference used by the system being protected Please refer to the section on grounding ...

Page 3: ...must be at least No 14AWG wire with no bends of less that a two inch radius The RackShield ground stud must be connected to the same reference point used by the AC power line transient suppressor This is the power safety ground wire green wire such as in an AC receptacle NOTE The protected device should also have AC suppression or it will be vulnerable to transients from the incoming AC power This...

Page 4: ...India No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Milano Italy Tel 39 02 959501 Fax 39 02 95950759 E mail chmninfo eaton com JAPAN Cooper Crouse Hinds Japan KK MT Building 3F 2 7 5 Shiba Daimon Minato ku Tokyo Japan 105 0012 Tel...

Reviews: