background image

4

INM F890 Rev 1

MECHANICAL

4 .1  Mounting Orientation

The F890-CA carriers are designed for mounting on a vertically aligned DIN-rail on a 
vertical surface.  This method of mounting ensures optimum heat dissipation from the 
Power Modules.  

4 .2  Enclosure Requirements

4 .2 .1  General Requirements

The assembly may be mounted in hazardous (classified) areas – see Sections 8 & 9.  
The following conditions must also be satisfied to ensure safe and reliable operation.

a)  Prevent any form of pollution that could compromise the operation of the unit. 

For example, choose an unpolluted location or a suitable enclosure to protect the 
assembly.

b)  Provide an adequate level of mechanical protection. This can be achieved by 

selecting a protected location, a suitable enclosure, or a combination of both.

c)  Ensure that all cable entries and connections are secure by making provision for 

the careful routing and securing of all cables.

d)  Provide adequate security against unauthorized interference.
e)  Ensure that the permitted ambient temperature range of –40°C to +65°C (derate to 

+50°C for the F802 when loaded above 60% of its full load rating) is not exceeded. 
Allow for power dissipation within the enclosure and consider the use of shading 
against direct sunlight.

4 .2 .2  Outdoor Mounting

If the power system is mounted in an outdoor location, use a suitable enclosure with 
a minimum of IP54 ingress protection.  A higher level of ingress protection rating will 
be necessary if the working atmosphere is or can be corrosive or if the enclosure is 
subject to wet or dusty environments.

4 .3  DIN-rail Mounting

The carrier is designed for mounting on 35mm x 7.5mm T-section “top hat” DIN rail to 
EN50022 and uses six built-in DIN clamp tabs to hold it on the rail.  The F801 power 
modules must be removed from the carrier to obtain access to the DIN-rail clamp 
screws.

4 .3 .1  Mounting Procedure

Before starting to mount the carrier on the DIN rail, rotate all six of the DIN clamp 
screws counterclockwise (i.e. unscrew) until the clamping tabs reach the position 
shown in Figure 3a and none of the tabs extend into the channel for the DIN rail.

a)

b)

     Figure 3 - 

DIN rail clamp positions before mounting

 

Summary of Contents for Crouse-Hinds MTL F890

Page 1: ...MTL F890 8 Segment Redundant Fieldbus Power Supply for use with non proprietary cabled systems March 2022 INM F890 Rev 1 Instruction manual MTL fieldbus networks...

Page 2: ...ii INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 3: ...5 5 ELECTRICAL CONNECTIONS 5 5 1 DC Power Requirements 6 5 2 Power A and Power B 7 5 2 1 Redundancy 7 5 2 2 Terminator 7 5 3 Alarm Connection 7 5 4 FInal Segment Connections 8 5 5 Field Segment Conne...

Page 4: ...dule may be used where redundancy is not required 2 DESCRIPTION For maximum reliability the module carrier contains no components and only provides interconnections between the Power Modules and the e...

Page 5: ...xtinguished and the red Alarm LED is lit Redundant 24V DC nom input power is connected to the F890 CA carrier using two part pluggable connectors Field wiring connections are available with either plu...

Page 6: ...s www mtl fieldbus com Relcom Inspect Clamps Inspect Clamps Shield Ground Option Ground SG 51 52 53 Rev E 0 S S S S S S S S 20 21 22 17 18 19 14 15 16 11 12 13 23 24 25 26 27 28 29 30 31 32 33 34 Segm...

Page 7: ...ure that the permitted ambient temperature range of 40 C to 65 C derate to 50 C for the F802 when loaded above 60 of its full load rating is not exceeded Allow for power dissipation within the enclosu...

Page 8: ...carrier with four screw mountings There are four locating connectors two for each module on the module carrier along with mating connectors in the F801 or F802 module Align the module with the retaini...

Page 9: ...vided allowing the use of bulk power supplies with a supply range of 19 2 30VDC Input power cabling and over current protection devices must be chosen to match the current consumption An F890 system o...

Page 10: ...ion Power must be connected to Power B terminals if live replacement of Power Module A is necessary since Power B terminals feed the Power Module B connector 5 2 2 Terminator A single terminator is pr...

Page 11: ...28 Segment 6 17 Segment 3 29 Segment 7 18 Segment 3 S 30 Segment 7 S 19 Segment 3 31 Segment 7 20 Segment 4 32 Segment 8 21 Segment 4 S 33 Segment 8 S 22 Segment 4 34 Segment 8 The host cable length s...

Page 12: ...the connector for the indicated function When using the screen grounding facility on the F890 carrier the jumper must be installed correctly Figure 7a and an Instrumentation Ground must be routed to...

Page 13: ...ith nine LEDs eight to indicate segment status and one to signify an Alarm condition Fault Condition Segment LED Fault Alarm contact status No Fault Green Off Closed Segment shorted Off Red Open Outpu...

Page 14: ...11 INM F890 Rev 1 8 FM CONTROL DRAWINGS...

Page 15: ...ed in place of the missing F801 or F802 module 24VDC Power Supplies may be installed in the Non hazardous area Vmax 24VDC F801 30VDC F802 24VDC Power Supply A 24VDC Power Supply A This is a Chassis Gr...

Page 16: ...clause 4 2 of EN 60079 17 b This equipment has been designed to provide protection against all the relevant additional hazards referred to in Annex II of the directive such as those in clause 1 2 7 c...

Page 17: ...ified product 9 5 Marking Each device is marked in compliance with the Directive Regulation This information applies to products manufactured during or after the year 2007 Typical certification markin...

Page 18: ...15 INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 19: ...Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Milano...

Reviews: