background image

IM1465    Rev.2       2020/09                                                   Cooper Electric (Changzhou) Co., Ltd.                                                        Page2/7

6.2 Mounting luminaire

6.2.1 Mounting the bracket

Only use the accompanying mounting bracket! Securely fasten the mounting 

bracket to a suitable base with sufficient load-bearing capacity. The mounting 
should be secured with M6 bolts and relative lock washers, nuts should be 
used. 

The minimum distance between the luminaire and illuminated surface, directly 

in front of the luminaire, is 0.5 meter. The lamp must not be illuminated 
when at a distance of less than 0.5m from inflammable material

6.3 Cable entries/Plugs and Breathing valve

The “Increased safety (Exe)" properties must be preserved when select and 

mount cable entry/plug and breathing valve. Unused holes must be closed 
with certified plug to establish the Exe protection category. The cable 
glands/plugs and breathing valve should be Ex tb certified if the whole 
product is Ex tb certified also. 

Cable entries sealing washer(if required by 

manual of cable gland/plug) must be used to obtain IP66.

The authoritative mounting guidelines for the cable glands and breathing valve 

used must be observed. Mounting the selected cable entries acc. type and 
dimensions of the main connection cable following their manufacturer 
instructions. The cable temperatures are given as the rise over the max. rated 
ambient (Tamb). This allows the user to adjust the cable specification for 
actual maximum site ambient. Only heat resistant cable according to the data 
on the type label may be used! The max. conductor size is 6mm². The standard 
looping cable size is 4mm².

6.4 Opening/closing the luminaire
6.4.1 General

The opening of luminaire always shall be without voltage! All gasket seals 

must be clean and undamaged before closing the luminaire. Make sure the 
luminaires is well closed before operation! 

6.4.2 Exe chamber cover

Open the cover with PC cover. And carry out the steps in reverse order to close 

the luminaire. Check all screws to ensure a secure fit during operation .

6.5 Electrical connection

The electrical connection of the lamp must only be established by qualified 

electricians. 

Make sure the supply voltage is the same as the luminaire voltage! Use proper 

supply wiring as specified on the nameplate of the luminaire and in this 
instructions! Excessive tightening may affect or damage the connection.

6.5.1 Wire connection 

The conductors shall be connected with special care in order to maintain the 

explosion category.  

The conductor itself shall not be damaged. 
The connectible min. and max. conductor cross-sections shall be observed (see 

technical data).  All terminals, used and unused, shall be fully tightened to 
prevent incorrect selection between 1.2Nm for Exe T 6P and 1.5~1.8Nm for 
MBK. Main connection: See wiring diagram. See Fig.4 for details.

6.6 Emergency light attention:

In mains operation the light fitting is charged by means of constant current 

output from inverter. Charging takes place via the un-switched external phase 
L to prevent an interruption, even when the luminaire is switched off.

With regular operation of the light fitting, the charging time is requested to 

more than 12h. It is suitable for a continuous charge of the battery.

Standard emergency discharge time is 90min for EM2, 180min for EM3.
Regularly inspection on battery states. Check if the battery cell is leak is 

necessary.

6.7 LED indicator for HRL emergency:

• LED is green light when normal work and charging battery;
• LED is flash when discharging;
• LED will not work, when no supply power, or inverter & battery is bad, or 

battery is full discharged;

7. Putting into operation

Prior to putting the apparatus into operation, the tests specified in the 
relevant national regulations shall be carried out. Insulation measurements 
may only be carried out between PE and the external conductor L1 (L2, L3) 
as well as between PE and N.
- Measurement voltage: Max. 1.5 KV AC
- Measurement current: Max.5 mA

The luminaire may only be operated when closed.
It is generally recommended (see IEC/EN 60079-14) that you ensure the 

type of protection of the construction is not impaired during installation.

8. Maintenance/Servicing

8.1 General

The relevant national regulations which apply to the maintenance/servicing of 
electrical apparatus in explosive atmospheres, shall be observed (EN/IEC 60079-
17). The interval between maintenance depends upon the ambient conditions 
and the hours of operation. The recommendations given within EN/IEC 60079-
17 for recurring checks must be observed.

8.2 Checks

The equipment must be de-energised before opening 

Visual inspection should 

be carried out at a minimum of 12 monthly intervals and more frequently if 
conditions are severe, refer to EN/IEC 60079-17. The time between lamp 
changes could be very infrequent and this is too long a period without 
inspection. 

8.3 Routine Examination

During maintenance, the parts affecting the level of protection must be 
checked in particular:
- Ensure the lamp is lit when energised and examine the enclosure and glass 
for any signs of cracks and damage.
- When de-energised and left to cool, there should be no significant sign of 
internal moisture. If there are signs of water ingress, the luminaire should be 
opened up, dried out, and any likely ingress points eliminated by re-gasketing, 
re-greasing or other replacement.
- Check the gasket of pc cover and LED housing for any damage or permanent 
set and replace as required.
- Terminal, screw glands and blanking plugs for secure fitting.
- To maintain the light output, clean the protective pc cover periodically with a 
damp cloth or a mild cleaning fluid.
- If this product is used in the combustible dust area, outside of enclosure 
must be cleaned on a regular basis to prevent accumulation of dust.
- The cable connections should be checked for tightness. The gasket should be 
checked for cracks or lack of elasticity, and if necessary, replaced.
- Check that mountings are secure and the adjusting bolts are tight.
- If it has been suspected that the luminaire has mechanical damage, a 
stringent workshop overhaul will be required. Where spares are needed, 
these must be replaced with factory specified parts. 
No modifications should be made without the knowledge and approval of the 
manufacturer.

Cleaning the joint of housing assy. and pc cover use a damp cloth or a mild 
cleaning fluid.

9. Repair/Overhaul/Modifications

9.1 General

The national regulations EN/IEC60079-19 have to be observed! Repairs and 
overhaul may only be carried out with genuine Eaton Crouse-Hinds spare 
parts.
In the case of battery failure, the battery pack must be replaced as a 
complete unit  from the manufacture.
Before replacing or disassembling individual parts, observe the following:
Disconnect the power supply to the equipment before maintenance/repair. 
Make sure that there is no explosive atmosphere when opening the 
equipment. See section 8.4 for notes on opening and closing the lamp.
Only use original spare parts. If the luminaire was previously in operation 
then wait to cool enough before opening. Repairs that affect the explosion 
protection, may only be carried out by Eaton Crouse-Hinds or a qualified 
electrician in compliance with the applicable national rules. Modifications to 
the device or changes to its design are not permitted.
After carrying out repair or overhaul work, ensure that the “Exde" properties 
have not been affected.
Assistance may also be obtained through Cooper Electronic Technologies 
(Shanghai) Co., Ltd. Sales Service department, 
955 ShengLi Road, Pudong Shanghai 201201
Phone (86) 21-28993943

10. Disposal/Recycling

When the apparatus is disposed of, the respective national regulations on 
waste disposal will have to be observed.

Reviews: