7
Explosion-protected empty enclosure GBXE
GB
1
Technical data
1.1 Empty enclosure
2 Legende
Warning
This symbol warns of a serious hazard. Failure to observe this
warning may result in death or the destruction of property.
Attention:
This symbol indicates a possible failure. Ignoring this warning can
lead to the total failure of the device, system or operation to which it
is connected.
Note:
This symbol stresses important information.
2.1 Safety instructions
The operations shall be carried out
by qualified, instructed electricians or qualified personnel
according to IEC/EN 60079-14 and engineering/develop-
ment specialists according to IEC/EN 60079-0.
The requirements of the IEC/EN 60079-31 regarding excessive dust
deposits and temperature to be considered from the user.
These empty enclosures GBXE may not be used in hazardous areas
without full certification. Even if they are fully certified, they are not
suitable for use in Zone 0 and Zone 20.
After apparatus/terminals have been installed in the empty enclo-
sure, it shall be tested and fully certified by a testing authority or
authorized person.
They shall be used for their intended purpose and in perfect and
clean condition.
Once Installed do not dismantle except for occasional inspection.
The empty enclosures GBXE shall only be used where temperature
at the point of entry is between (- 50 °C to +100 °C).
EU type examination certificate:
TÜV 18 ATEX 8239U
Marking acc. to 2014/34/EU and standard:
EN 60079-0
II 2 G
Ex e IIC Gb
II 2 D
Ex tb IIIC Db
IEC Ex type examination certificate
IECEx TUR 18.0033U
Marking:
IEC60079-0
Ex e IIC Gb
Ex tb IIIC Db
Perm. service temperature:
-50 °C
...
+100 °C
Perm. storage temperature in original packing:
-50 °C
...
+100 °C
Impact resistance acc. to IEC/EN 60079-0:
7 J
Protection category acc. to IEC/EN 60529:
IP66 (catalogue version)
Insulation class acc. to IEC/EN 61140:
II
Enclosure material:
GRP (Glass fiber reinforced plastics)
Enclosure color:
Black ( Similar to RAL 9011)
Test torques:
Cover screws:
M4
1 - 2
Nm
M6
2- 4
Nm