X-Limiter™ Hinge-Mount for S&C SMD®-20 Fuse  

Mounting AsseMbly And instAllAtion instructions

   MN132018EN   November 2016

Product information

  CAUTION

Eaton’s Cooper Power series X-Limiter Hinge-Mount 

fuse is designed to be installed in accordance with 

normal safe operating procedures . These instructions are 

not intended to supersede or replace existing safety and 

operating procedures . READ ALL THE INSTRUCTIONS 

BEFORE INSTALLING THE X-Limiter Hinge-Mount fuse . 

The Hinge-Mount fuse should be installed and serviced 

only by personnel familiar with good safety practice and 

the handling of high-voltage electrical equipment .

Introduction

The X-Limiter Hinge-Mount, Full Range current-limiting fuse 

has been adapted to fit the S&C SMD

®

-20 cutout mounting. 

The use of the S&C standard end fittings allow for complete 

interchangeability with fuses mounted in S&C SMD-20 

cutouts.

  CAUTION

Do not install fuse units if the blown fuse indicator has 

been damaged or destroyed, as the fuse’s moisture seal 

will be damaged, which may cause fuse failure .

Retrofit installation of X-Limiter hinge-mount fuse

Initial retrofit installation includes removing the existing 

fuse from the S&C SMD-20 cutout and replacing it with the 

X-Limiter fuse in accordance with the following steps.
1.  Removal of fuse in the S&C SMD-20 cutout:

A. The fuse will be in an open position after it has 

operated. 

Remove it from the mounting using a 

standard insulated hotstick

.

B. 

Loosen the upper- and lower-end fitting-clamp 

screws . 

With a screwdriver, force the upper-end 

fitting clamp apart slightly, and slide both end fittings 

off the upper end of the fuse unit.

C. 

Save the end fittings for use with the X-Limiter 

fuse .

Figure 1 . 

Clamp Screw

Current 

Transfer 

Surface

Locating Pin

Upper Seal

Locating Slot

Inward Dimple

Notch

Locknut

Clamp Pad

Clamp Screw

Actuating Pin Through 

Upper Seal When Fuse 

Unit Is Blown

Upper End Fitting

Full-Range 

Current-Limiting 

Fuse

Lower End Fitting

 Line illustration of X-Limiter hinge mount for 

S&C SMD-20 fuse mounting .

2.  Assembly of X-Limiter hinge-mount current-limiting 

fuse: When shipped from the factory, the X-Limiter fuse 

will be readily equipped for installation.

3.  Attachment of end fittings on the X-Limiter fuse:

A. 

The lower end fitting must be attached first . 

The X-Limiter fuse has a notch in the bottom which 

receives the S&C end fitting wedge. Care must be 

taken to hand tighten the bolt such that the end 

fitting wedge is in the fuse notch. When properly 

installed, the bottom of the fitting is even with the 

bottom of the fuse, to about 1/8” above the bottom 

of the fuse, and the inward dimple is centered and 

visible on the opposite side of the fittings. (Location 

of notch and inward dimple are shown in Figure 1.) 

When the end fitting is properly located tighten the 

clamp screw and locking nut securely.

  CAUTION

If upper and lower contacts are not properly aligned DO 

NOT FORCE . Loosen clamp screws and realign .

B. Slide the upper end fitting over the X-Limiter fuse. 

Align the locating pin inside the end fitting with the 

locating slot of the fuse and slide it down. When the 

locating pin is placed in the slot, tighten the clamp 

screw securely. (Refer to Figure 1.)

Summary of Contents for COOPER POWER SERIES

Page 1: ...X Limiter Hinge Mount for S C SMD 20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 S240 84 1...

Page 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Page 3: ...18EN November 2016 Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY ii SAFETY FOR LIFE iv SAFETY INFORMATION iv Safety instructions iv PRODUCT INFORMATION 1 Introduction 1 Retrofit instal...

Page 4: ...ly hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUT...

Page 5: ...screws With a screwdriver force the upper end fitting clamp apart slightly and slide both end fittings off the upper end of the fuse unit C Save the end fittings for use with the X Limiter fuse Figure...

Page 6: ...Upper Seal on Fuse Gap Illustration of gap at top upper end fitting 4 Installation of X Limiter hinge mount fuse with end fittings into SMD 20 cutout Refer to manufacturer s operating procedure for i...

Page 7: ...3 X Limiter Hinge Mount for S C SMD 20 Fuse Mounting Assembly and Installation Instructions MN132018EN November 2016 This page is intentionally left blank T...

Page 8: ...States Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN132018EN Rev 0 November 2016 Eaton is a registered trademark All trademarks are property of their res...

Reviews: