background image

Control power

The control requires a 120 Vac (104-127 Vac) to operate the 

battery charger. An additional 120 Vac input with a flip-flop 

relay will be provided for preferred/alternate voltage sources 

(See Figures 2 and 3).

Figure 2 . AC supply and battery charger board

Description of control

Control operation

The DC motor operator control is designed for use 

with Eaton’s Cooper Power series Type RVAC and VFI 

pad-mounted switchgear. The motor operator control is 

applicable with both 600 amp vacuum loadbreak switch 

mechanisms and vacuum fault interrupter mechanisms.
The motor operator control is designed to monitor and 

direct the operation of DC motors when supplied with 

Type RVAC and VFI pad-mounted switchgear. The control 

will operate up to six motor actuators-one at a time-in a 

user-selected random order for 25 OPEN and 25 CLOSE 

operations without line voltage.

941195KM

The basic DC control can be operated in either the LOCAL 

or REMOTE modes by making the appropriate selection 

with the SCADA toggle switch. With the SCADA switch on 

LOCAL, STATUS and control functions are accessed via the 

control panel. With the SCADA switch on REMOTE, STATUS 

and control functions are accessed via the SCADA interface 

(See Figures 4 and 6).

Auxiliary contacts

One “a” and one “b” auxiliary switch contact from the “B” 

phase of each actuated mechanism are utilized for status 

indication. To read status in either LOCAL or REMOTE 

modes, a motor must first be selected.

Simultaneous indication for SCADA

For some SCADA applications, it may be necessary to 

monitor the status of each stage simultaneously. To 

provide this capability, an additional stage for each actuated 

mechanism is required. For these applications, an optional 

interface, separate from the control, can be additionally 

provided (consult factory for details).

Electrical interlocks

The DC motor operator control may be supplied with the 

capability for user-specified electrical interlocking. For these 

applications, an additional stage may be required (consult 

factory for details).

CLOSING indicator light

Power Switch

Motor Select Knob

CLOSE push button

CLOSED indicator light

OPEN indicator light

LAMP TEST push button

OPEN push button

OPENING indicator light

SCADA Toggle Switch

STOP push button

Figure 3 .  Operator panel of DC motor operator control

941194KM

2

OPERATION INSTRUCTIONS

   MN285018EN   May 2017

DC motor operator control installation and operation instructions

Summary of Contents for COOPER POWER SERIES

Page 1: ...DC motor operator control installation and operation instructions COOPER POWER SERIES Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 S285 80 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...iliary contacts 2 Simultaneous indication for SCADA 2 Electrical interlocks 2 Control operation LOCAL Mode 3 LOCAL Mode operation 3 LOCAL Mode features 3 Battery charger board 3 Wiring schematic 4 Ins...

Page 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Page 5: ...that the battery is disconnected during storage Quality standards ISO 9001 Certified Quality Management System Control battery storage and charging The 24 Vdc control battery is fully charged prior t...

Page 6: ...panel With the SCADA switch on REMOTE STATUS and control functions are accessed via the SCADA interface See Figures 4 and 6 Auxiliary contacts One a and one b auxiliary switch contact from the B phas...

Page 7: ...rupter mechanism via the motor operator STOP YELLOW PUSH BUTTON Stops the motor operated opening or closing action of the selected switch or interrupter mechanism Note N Mechanisms should not be left...

Page 8: ...Figure 4 Wiring schematic of DC motor operator control 4 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 9: ...agrams supplied with your control for specific information on accessories or special modifications that were supplied at the time of manufacture Dashed wires indicate customer made connections 5 OPERA...

Page 10: ...h SCADA terminals Select one of several motors Read status of selected motor Operate the selected motor Monitor opening or closing action REMOTE Mode Features All remote features are accessed through...

Page 11: ...set to the LOCAL position for extended local control operation CLOSE RED PUSH BUTTON Closes the selected switch or interrupter mechanism via the motor operator OPEN GREEN PUSH BUTTON Opens the select...

Page 12: ...Figure 7 Outline diagram of DC motor operator control 8 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 13: ...onnects the motor to the yellow handle See Figure 11 Translator Tube Figure 10 DC Motor actuator disconnected Note N The actuator and limit switches are adjusted for proper operation prior to shipment...

Page 14: ...ical operating characteristics of the DC Motor Operator Control Table 1 DC motor operator ratings Close max amps Open max amps Running load amperage RLA 12 12 Lock rotor amperage LRA 24 23 In rush 20...

Page 15: ...This page intentionally left blank 11 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN285018EN May 2017 KA2048 0406 REV01 Eaton is a registered trademark All trademarks are property of their...