Instructions for LOCAL mode operation

For DC Motor Operator Control wiring and outline 

information, refer to Figure 5 and 8.

1 .  POWER switch must remain ON for normal 

operation . Power OFF disables both control 

and motors .

The power switch is a 5-amp, DC breaker which will 

operate in 1 to 3 seconds for 20 amps. Placing the 

switch in the OFF position disables the DC, which 

powers both the control and the motors.

2 .  SCADA switch must be set to LOCAL .

To operate the motors from the control panel, the 

SCADA switch must be set to LOCAL.

3 .  Set MOTOR SELECT switch to desired motor .

To read contact status or to select a motor to operate, 

set the MOTOR SELECT switch to the desired position.

4 .  Confirm correct status indicators are lit .

After selecting a motor, confirm that the status lights 

indicate the actual position of the mechanism.

5 .  Push OPEN or CLOSE pushbuttons to operate 

motor . Yellow light indicates motor operation 

in progress . Push STOP to halt motor operation 

immediately; then push OPEN or CLOSE to 

complete a full open or full close operation . 

(See Note below) .

Push the appropriate pushbutton to perform the OPEN 

or CLOSE operation. If necessary, push the STOP 

pushbutton to halt the motor immediately. Do not leave 

the motor in this condition. Complete a full OPEN or 

CLOSE operation to prevent an inadvertent mechanism 

operation.

6 .  When complete, return MOTOR SELECT switch to 

OFF . Set SCADA switch as desired . Leave POWER 

switch ON to permit SCADA operation .

The status lights will remain lit as long as a motor 

is selected. If AC power is lost, the batteries will 

eventually be drained. Be sure to return the MOTOR 

SELECT switch to the OFF position. Leave the POWER 

switch on if SCADA operation is desired.

otee:

N

The POWER SWITCH does not disable 120 AC or the 

battery charger. To disconnect 120 Vac, remove the 

fuses or disconnect 120 Vac from Terminal P2.

SCADA Operation

Remote monitoring and control operation are provided 

through the SCADA terminals. The control is activated in 

the REMOTE mode when the SCADA toggle switch is set 

to REMOTE.

Features available through SCADA terminals:

Select one of several motors.

Read status of selected motor.

Operate the selected motor.

Monitor opening or closing action.

REMOTE Mode Features

All remote features are accessed through a terminal strip 

mounted on the relay circuit board. (See Figures 6 and 8). 

Remote operation is permitted only when the SCADA 

switch is in the REMOTE position.
The operation of each feature is described as follows:

MOTOR SELECT CONTACTSe: 

Dry contacts for SCADA 

selection of a switch or interrupter mechanism for status 

indication or operation. These contacts require a maintained 

contact closure for as long as the status is being read or the 

motor actuator is active.
If this contact is opened during an operation, the motor 

actuator will stop immediately. If more than one motor is 

selected simultaneously, the lowest numbered motor will 

be selected by default.

STATUS CONTACTSe: 

Dry contacts which indicate open 

or closed status of the switch or interrupter mechanism 

selected via the SCADA Motor Select Contacts.

CLOSE CONTACTe: 

Dry contact which initiates closing the 

switch or interrupter mechanism selected via the Motor 

Select contacts. A momentary contact closure between 

terminal 21 and terminal 22 on the SCADA terminal strip 

is required.

OPEN CONTACTe:

 Initiates opening the switch or 

interrupter mechanism, selected via the Motor Select 

contact. A momentary contact closure between terminal 

19 and terminal 20 on the SCADA terminal strip is required.

CLOSING CONTACTe: 

Dry contact which indicates that 

the motor actuator is closing the switch or interrupter 

mechanism selected via the Motor Select contacts. The 

motor is closing when the contact is closed (terminals 1  

and 2).

OPENING CONTACTe:

 Dry contact which indicates that 

the motor actuator is opening the switch or interrupter 

mechanism selected via the Motor Select contacts. The 

motor is opening when the contact is closed (terminals 3  

and 4).

SCADA SWITCH POSITION CONTACTe: 

A dry contact 

which indicates the position of the SCADA switch. When 

the SCADA switch is in the REMOTE position, this contact 

will be closed. When the SCADA switch is in the LOCAL 

position, this contact will be open (terminals 5 and 6).

6

OPERATION INSTRUCTIONS

   MN285018EN   May 2017

DC motor operator control installation and operation instructions

Summary of Contents for COOPER POWER SERIES

Page 1: ...DC motor operator control installation and operation instructions COOPER POWER SERIES Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 S285 80 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...iliary contacts 2 Simultaneous indication for SCADA 2 Electrical interlocks 2 Control operation LOCAL Mode 3 LOCAL Mode operation 3 LOCAL Mode features 3 Battery charger board 3 Wiring schematic 4 Ins...

Page 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Page 5: ...that the battery is disconnected during storage Quality standards ISO 9001 Certified Quality Management System Control battery storage and charging The 24 Vdc control battery is fully charged prior t...

Page 6: ...panel With the SCADA switch on REMOTE STATUS and control functions are accessed via the SCADA interface See Figures 4 and 6 Auxiliary contacts One a and one b auxiliary switch contact from the B phas...

Page 7: ...rupter mechanism via the motor operator STOP YELLOW PUSH BUTTON Stops the motor operated opening or closing action of the selected switch or interrupter mechanism Note N Mechanisms should not be left...

Page 8: ...Figure 4 Wiring schematic of DC motor operator control 4 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 9: ...agrams supplied with your control for specific information on accessories or special modifications that were supplied at the time of manufacture Dashed wires indicate customer made connections 5 OPERA...

Page 10: ...h SCADA terminals Select one of several motors Read status of selected motor Operate the selected motor Monitor opening or closing action REMOTE Mode Features All remote features are accessed through...

Page 11: ...set to the LOCAL position for extended local control operation CLOSE RED PUSH BUTTON Closes the selected switch or interrupter mechanism via the motor operator OPEN GREEN PUSH BUTTON Opens the select...

Page 12: ...Figure 7 Outline diagram of DC motor operator control 8 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 13: ...onnects the motor to the yellow handle See Figure 11 Translator Tube Figure 10 DC Motor actuator disconnected Note N The actuator and limit switches are adjusted for proper operation prior to shipment...

Page 14: ...ical operating characteristics of the DC Motor Operator Control Table 1 DC motor operator ratings Close max amps Open max amps Running load amperage RLA 12 12 Lock rotor amperage LRA 24 23 In rush 20...

Page 15: ...This page intentionally left blank 11 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN285018EN May 2017 KA2048 0406 REV01 Eaton is a registered trademark All trademarks are property of their...

Reviews: