8
6 First commissioning and modifying network settings
Installation and Operating Instructions Web-Controller
40071860236 (E) February 2019 www.eaton.com
Resistor must be connected next to the switch.
S1 CGLine
S2 Interface
Option inputs (In1/In2):
Programmable digital inputs. The inputs are activated by
bridging of both contacts of In1 or In2.
The following functions can be freely assigned to the digital
inputs:
n
Rest order
n
Maintained Light ON/OFF per Line
n
Start function test
n
Stop test
n
External failure
Relay outputs:
The Web-Controller also has 2 freely programmable
relay outputs each with a change-over contact.
Programmable functions:
n
At least one luminaire failure
n
Three consecutive luminaire failure
n
Communication failure
n
Battery operation
n
Function test active
n
Duration test active
n
Charging failure
n
Test failure
Assignment:
Relay 1:
Relay 2:
21
22
24
11
12
14
USB connections:
The Web-Controller has 2 USB connections: 1 x USB A
host and 1 x USB B device.
USB1 (Type A host):
A standard USB storage stick can be connected to this USB
port to save the current configuration and the logbook to the
USB stick.
USB2 (Type B device):
This USB connection enables connection of the
Web-Controller to a standard PC. Controller functions can be
programmed via the PC and a configuration software, e.g.
luminaire configurations. The PC configuration software is
available optionally.
6 First commissioning and modifying
network settings
The network settings of the Web-Controller can be modified
by the PC software or via web browser. The following
procedure describes the setup via web browser.
NOTE
For correct perform of the duration test and function test the
date and the time must be adjusted (see chapter 6.5).
6 .1 Factory default nework settings
The Web-Controller is supplied as standard with the
fixed IP address 192.168.1.200. Operation via DHCP (dynamic
IP address assignment) is possible but not factory-activated.
Because typical company networks only permit own-assigned
IP addresses, we recommend configuring network settings via
direct connection to a PC, e.g. a notebook.
6 .2 Preparing the PC for configuration
It is mandatory to observe the following:
n
For direct connection from the Web-Controller to
a PC, a crossover cable is required.
n
The devices must be in the same subnet, meaning the net-
work card of the PC must be set to 192.168.1.xxx (not equal
to 200), e.g. 192.168.1.50 (subnet to 255.255.255.0).
n
Settings for gateway and DNS must not be taken into
account with a direct connection.
Connection example for direct connection:
PC network setting:
To modify the network settings of the PC open the system
control
Network and release centre