In the configuration menu
of the two digital inputs
1
,
2
the inputs can be
assigned specific commands
and the two relays can be
assigned conditions when
the relay’s state changes.
Configuration of the two digital inputs
3
:
n
Not configured: no function
n
Rest order: During a mains failure (luminaires are in emergency mode), the rest mode will
switch OFF the luminaires. If mains return, the luminaires will go back in normal mode. To the
next mains failure, the luminaires switch again to emergency mode.
n
Activate IA mode: Activate the Increase Affordance mode in line 1, 2, 3 and/or 4.
n
Maintained mode OFF per line: Switches off the maintained mode luminaires of the line as
long as the input is active
n
Start function test: With positive pulse, starts the function test with all luminaires
n
Stop FT/DT: Interrupts a duration test or function test with all luminaires
n
External failure
Configuration of the two relay outputs
4
:
n
Not configured: no function
n
One luminaire fault: Common fault for at least one luminaire
n
Three consecutive luminaires failure: At least 3 consecutive luminaires in a zone are faulty
n
Communication fault: At least 1 luminaire has a communication fault
n
Battery operation: At least 1 luminaire is in battery mode, e.g. with mains failure
n
Function test: At least 1 luminaire is in a function test
n
Duration test: At least 1 luminaire is in a duration test
n
Charging failure: At least 1 luminaire has a battery or charge fault
n
Test failure: At least 1 luminaire has an FT or DT fault, e.g. nominal operating time not reached
7 .11 „Digital input/output“ configuration screen
2
3
4