7.9 Device information screen
The device information
screen in the configuration
menu
1
displays informa-
tion about the
Web-Controller,such as
device name (freely con-
figurable), software ver-
sion etc.
It is also possible with
several Web-
Controllers in the network
to assign a logical address
to each from 1 to 32
2
.
1
7.10 Configuration screen test times
On the “Test” tab
2
in
the configuration menu
1
, it is possible to deter-
mine start times for a
function test and duration
test for up to 8 groups.
It is also possible to set
a test interval via which
tests are cyclically repeat-
ed. Possible test frequen-
cies:
O
O
Function test: 1-30 days
O
O
Duration test: 30 -365
days
The self-con-
tained luminaires of the
corresponding test groups
then carry out an auto-
matic function test of the
lamps or a duration test of
the batteries according to
these set times.
2
1
2
NOTE
If the period of mains failure is greater than 21 days, the
complete system should be re-commissioned. Especially
the date and time must be reconfigured to assure proper
sequencing of the test.