background image

11

9  Maßbilder/19  Drawings

Manual: ZB-S central battery system in electrical service rooms EBR-S

   40071860238 (C)   November 2017   www.ceag.de

9  Maßbilder/19  Drawings

EBR-S 1800

EBR-S 2050

586

200

0

lichtes Innenmaß

 

|

 clear inside dimension

1945

lichtes Öffnungsmaß

 

| clear opening dimension

180

0

500

ca. 600

Zuluft 

| Supply air

Abluft 

| Exhaust air

Kabeleinführung

Cable entry

Flexschlauch
für Zuluft

Flexible hose for 
supply air

894

234

6

208

4

ca. 40

0

ø135

810

lichtes Innenmaß

clear inside dimension

700

lichtes Öffnungsmaß

clear opening dimension

50

0

lichtes Innensmaß

clear inside dimension

Zuluft 

| Supply air

Abluft 

| Exhaust air

Kabeleinführung

Cable entry

Vorderansicht Sockel/Stand 

optional

Sockel/Stand 

optional

Front View

Innenansicht

Inside view

Seitenansicht

Side view

Seitenansicht

Side view

Draufsicht

Top view

Grundriss

Floor plan

1144

736

Vorderansicht

Front View

Innenansicht

Inside view

Seitenansicht

Seitenansicht

Side view

215

5

lichtes Innenmaß 

|

 clear inside dimension

Kabeleinführung

Cable entry

652

250

1

ca. 2000

223

9

2100

lichtes Öffnungsmaß 

| clear opening dimension

ca. 850

Zuluft 

| Supply air

Abluft 

| Exhaust air

Flexschlauch
für Zuluft

Flexible hose for 
supply air

Side view

Draufsicht

Top view

Zuluft 

| Supply air 

Abluft 

| Exhaust air

Kabeleinführung

Cable entry

Grundriss

Floor plan

65

0

lichtes Innenma

ß

clear inside dimension

ca. 60

0

1060

lichtes Innenmaß

clear inside dimension

950

lichtes Öffnungsmaß

clear opening dimension

Sockel/Stand 

optional

Sockel/Stand 

optional

Summary of Contents for CEAG ZB-S 10C3

Page 1: ...EBR S Zielgruppe Teil 1 Elektrofachkraft gem EN 50110 1 Installation instructions ZB S central battery system in electrical service rooms EBR S Target group part 1 Qualified electrician acc to EN 50110 1 Elektrische Betriebsräume Typ EBR S Electrical service rooms of type EBR S ...

Page 2: ...tungseinführung ZB S mit 600 mm Schranktiefe 6 8 Montage Abfangschiene Leitungseinführung ZB S mit 400 mm Schranktiefe 6 9 Maßbilder 11 10 Übereinstimmungserklärung des Elektrofachbetriebes 12 Content 11 Safety notes 2 12 Installation of ZB S 2C3 CG100 CG 102 and CG 104 in the EBR S 1800 elect service room 7 13 Installation of ZB S 18C3 10C3 and CG200 in the EBR S 1800 electrical service room 7 14...

Page 3: ...ftung montieren siehe Montage und Bedienungsanleitung ELEKTRISCHER BETRIEBSRAUM PRIORACK Elt EBR 4 Leitungen einführen 5 Anlage gemäß CEAG Anleitung ZB S anschließen und in Betrieb nehmen 3 Einbau ZB S 18C3 10C3 und CG200 in elektrischen Betriebsraum EBR S 1800 1 Anlage aufstellen und mit der Rückwand des Raumes verschrauben ACHTUNG Um Schrauben in das Brandschutzmaterial einschrauben zu können mü...

Page 4: ...92 170 692 170 692 170 692 155 Zubehör Maximale Anzahl von zusätzlichen Kabelschotts KRS 125 Pro Kabelschott max 26 Leitungen 3 x 2 5 mm oder 10 Leitungen a 3 x 25 16 mm siehe Abb Seite 5 6 6 6 6 6 Sockel mit Sockelblende 1060 mm breit H 84 mm EBR S 2050 SO EBR S 2050 SO EBR S 2050 SO EBR S 2050 SO EBR S 2050 SO CEAG Sachnummer 40036071115 40036071115 40036071115 40036071115 40036071115 Sockel mit...

Page 5: ...a ja 3 86 3 86 1 01 1 01 0 60 0 51 0 22 400 350 250 200 150 200 80 4 4 2 2 2 2 2 78 78 26 26 26 26 26 10 10 10 10 10 10 10 2417 2501x1144x736 2417 2501x1144x736 2262 2346x894x586 2262 2346x894x586 2262 2346x894x586 2262 2346x894x586 2262 2346x894x586 692 205 692 200 459 120 459 115 459 50 459 110 459 35 6 6 4 4 4 4 4 EBR S 2050 SO EBR S 2050 SO 40036071115 40036071115 EBR S 1800 SO EBR S 1800 SO E...

Page 6: ...8 Zur Befestigung am Schrank unbedingt zusätzlich die zur Befestigung des Dachbleches verwendeten Zahnscheiben mitverwenden x4 752 250 70 8 Zur Befestigung am Schrank unbedingt zusätzlich die zur Befestigung des Dachbleches verwendeten Zahnscheiben mitverwenden x4 7 Montage Abfangschiene Leitungseinführung ZB S mit 600 mm Schranktiefe 8 Montage Abfangschiene Leitungseinführung ZB S mit 400 mm Schr...

Page 7: ... instructions ELECTRICAL SERVICE ROOM PRIORACK Elt EBR 4 Feed in the cables 5 Connect the system in accordance with the CEAG ZB S instructions and carry out commissioning of the system 13 Installation of ZB S 18C3 10C3 and CG200 in the EBR S 1800 electrical service room 1 Align the system and screw fasten to the rear wall of the room CAUTION Holes must be pre drilled for fastening screws into the ...

Page 8: ...170 692 170 692 155 Accessories Maximum number of supplementary KRS 125 cable sealings Max 26 cables per cable sealing 3 x 2 5 mm or 10 cables at 3 x 25 16 mm see figure on page 5 6 6 6 6 6 Plinth with plinth panel width 1060 mm H 84 mm EBR S 2050 SO EBR S 2050 SO EBR S 2050 SO EBR S 2050 SO EBR S 2050 SO CEAG part number 40036071115 40036071115 40036071115 40036071115 40036071115 Plinth with plin...

Page 9: ...86 1 01 1 01 0 60 0 51 0 22 400 350 250 200 150 200 80 4 4 2 2 2 2 2 78 78 26 26 26 26 26 10 10 10 10 10 10 10 2417 2501x1144x736 2417 2501x1144x736 2262 2346x894x586 2262 2346x894x586 2262 2346x894x586 2262 2346x894x586 2262 2346x894x586 692 205 692 200 459 120 459 115 459 50 459 110 459 35 6 6 4 4 4 4 4 EBR S 2050 SO EBR S 2050 SO 40036071115 40036071115 EBR S 1800 SO EBR S 1800 SO EBR S 1800 SO...

Page 10: ...e 760 535 70 8 When mounting to the cabinet ensure you also use the serrated washers used for fixing the roof plate x4 752 250 70 8 When mounting to the cabinet ensure you also use the serrated washers used for fixing the roof plate x4 17 Assembling the stop rail for ZB S cable infeed with 600 mm cabinet depth 18 Assembling the stop rail for ZB S cable infeed with 400 mm cabinet depth ...

Page 11: ...ble entry Vorderansicht Sockel Stand optional Sockel Stand optional Front View Innenansicht Inside view Seitenansicht Side view Seitenansicht Side view Draufsicht Top view Grundriss Floor plan 1144 736 Vorderansicht Front View Innenansicht Inside view Seitenansicht Seitenansicht Side view 2155 lichtes Innenmaß clear inside dimension Kabeleinführung Cable entry 652 2501 ca 2000 2239 2100 lichtes Öf...

Page 12: ...trofachbetriebes Elektrofachbetrieb Straße PLZ Ort Name des Verantwortlichen Wir bestätigen durch unsere Unterschrift dass wir die Anforderungen der Montage und Bedienungsanleitung Elektrischer Betriebsraum Priopack ELT EBR der Firma Priorit und der EATON Einbauanleitung Zentralbatteriesysteme ZB S in elektrische Betriebsäume Typ EBR S ohne Abweichungen eingehalten haben Ort Datum Stempel Untersch...

Page 13: ... service provider Electrical service provider Street Postal code Location Name responsible person With this declaration of conformity we confirm that we fulfil the requirements of the Priorit Mounting and Service Instruction Electrical Service Room Priopack ELT EBR and the EATON Installation instruction ZB S central battery sys tem in electrical service rooms EBR S without any deviations Location ...

Page 14: ...ση English General safety instructions The devices are not suitable for private use An installation must be performed by qualified electricians taking into account the national safety and accident prevention regulations The devices must be used in accordance with their intended use in a proper and undamaged condition Remove all foreign objects from the devices before their first use When working w...

Page 15: ...i întâi alimentarea cu curent asigurați le împotriva repornirii și verificați ca să nu fie sub tensiune Cele de mai sus se referă la alimentarea de la rețea alimentarea de rezervă tensiunea de reglare și curenții de scurgere Nu întrerupeți circuitele sub sarcină Fiți atenți la obiecte care pot cădea în timpul transportului Utilizați numai piese de schimb originale Pусский Общие инструкции по безоп...

Page 16: ...υθερώνεται διαβρωτικός ηλεκτρολύτης Όταν εργάζεστε με τις μπαταρίες κλείνετε τον διακόπτη λειτουργίας βεβαιώνεστε ότι δεν μπορεί να ανοίξει ξανά και ελέγχετε εάν υπάρχει τάση σε αυτές Μην αποσυνδέετε την μπαταρία υπό φορτίο Κατά την αποσύνδεση υπό φορτίο ή σε περίπτωση βραχυκυκλώματος το τόξο που σχηματίζεται μπορεί να προκαλέσει εγκαύματα Μην τοποθετείτε ξένα αντικείμενα ή εργαλεία πάνω στην μπατ...

Page 17: ...ierzonym przeznaczeniem gdy są one w dobrym i nieuszkodzonym stanie Należy unikać gromadzenia się ładunku elektrosta tycznego oraz wyładowań iskier Ryzyko wybuchu Jeżeli obudowa akumulatora jest uszkodzona wycieka z niej korozyjny elektrolit Podczas pracy przy akumulatorach należy naj pierw całkowicie wyłączyć zasilanie upewnić się że nie można go włączyć ponownie oraz spraw dzić czy nie ma napięc...

Page 18: ...er verktyg på batteriet Var uppmärksam på fallande delar under transport Hissa eller lyft aldrig blockbatterier blockceller genom dess poler Använd endast originalreservdelar vid utbyte Türkçe Genel güvenlik talimatları Bataryalar özel kullanım için uygun değildir Bir kurulum ulusal güvenlik ve kaza önleme yönetmelikleri dikkate alınarak vasıflı elekt rikçiler tarafından yapılmalıdır Bataryalarla ...

Page 19: ...19 Notes Manual ZB S central battery system in electrical service rooms EBR S 40071860238 C November 2017 www ceag de Notes ...

Page 20: ...n besuchen Sie www eaton eu Ihre Ansprechpartner finden Sie unter www ceag de Eaton Industries Manufacturing GmbH Electrical Sector EMEA Route de la Longeraie 7 1110 Morges Switzerland Eaton eu CEAG Notlichtsysteme GmbH Senator Schwartz Ring 26 59494 Soest Germany Tel 49 0 2921 69 870 Fax 49 0 2921 69 617 E Mail info n ceag de Web www ceag de 2017 Eaton Alle Rechte vorbehalten Printed in Germany B...

Reviews: