Wiring Diagrams: Lighting Electrically Held
ote:
N
source drawing reference wiring diagram 286979 .
ote:
N
For kits with a green OFF light, an additional top added
NC auxiliary is needed to be supplied by the customer .
NC1 NC2
STOP/OFF
NO4
NO3
START/ON
2/13
3/14
R1
M
A2
A1
M
X2
X1
RUN
R
1 2
96
95
OL
X2
X1
OFF
G
1 2
T1
62
61
M
T1
54
53
M
98
97
OL
1
2
4
3
1 2
1 2
WIRING FOR DC STARTERS ONLY
STOP/START OR OFF/ON OVAL. OPTIONS SHOWN: RUN LIGHT AND OFF LIGHT
BLK/RED
BLK/RED
RED
RED
RED
RED
BLK/WHT
BLK/WHT
RED
RED
YEL
BLK
RED
(BLU IF DC)
RED
(BLU/WHT IF DC)
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR CONTROL POWER WIRING OPTIONS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
A1
M HOLD
A2
M PICKUP
X2
X1
RUN
R
R1
M LATE OPENING
96
95
OL
98
97
OL
BLU
RED
BLK/RED
BLK/RED
BLU
BLU
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX)
4
Instructions and Operation
P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON
www.eaton.com
C600M Wiring Kit Diagrams