IB140036EN

Instruction Booklet

Page

 

4

Effective: October 2014

O&M Manual for 40-1200A (480/600 Vac) ATC-900 3-Position, 

Open/Closed Transition Contactor Based Transfer Switch

Figure 4A. Open Transition Contactor Based ATS (1200A).

Each panel is independently mounted with interconnecting wiring 

terminated at the connector receptacles on the ATC-900 Control-

ler.

For open transition contactor based transfer switch, enclosure 

mounting is simplified by utilizing mounting flanges with elon-

gated (teardrop) mounting holes on top and floor mount (wall 

supported) flanges with two standard mounting holes on the bot-

tom. 

For close transition contactor based transfer switch, enclosure is 

free standing and is seismic approved. Refer to Section 4 for spe-

cific mounting and modification details.

Table 1. Withstand Ratings.

LOGIC

PANEL

POWER
PANEL

VOLTAGE SELECTION

& TRANSFORMER PANEL

Figure 4B. Closed Transition Contactor Based ATS (1200A)

1.3 ATS Catalog Number Identification

Transfer switch equipment catalog numbers provide a significant 

amount of relevant information that pertains to a particular piece 

of equipment.  The Catalog Number Identification Table (Table 2) 

provides the required interpretation information.  An example is 

offered here to initially simplify the process.

Example:

Catalog Number (circled numbers correspond to position 

headings in Table 2). 

AT

C

9

C3

X

3

1200

X

R U

1 to 2

3

4

5

6

7

8

9

to

12

13

14

15

to

The catalog number ATC9C3X31200XRU describes an ATS with 

a 3 pole, 3 position Power Contactor mounted on a baseplate 

within the enclosure.  The intelligence represented by the logic 

panel is ATC-900 controller.  The continuous current rating of 

this equipment is 1200A and applicable at 480 Vac, 60 Hz.  The 

transfer switch equipment is enclosed in a NEMA 3R enclosure 

and is listed for UL applications.

UL 1008 WITHSTAND AND CLOSE-ON RATINGS (kA)

480 Vac

600 Vac

Switch

 

Rating

 

(Amps)

Any

Breaker

(Amps)

Specific

Breaker

Amps)

Any

Breaker

Amps)

Specific

Breaker

Amps)

100A

50,000

65,000

50,000

65,000

200A

50,000

65,000

50,000

65,000

260A

50,000

65,000

50,000

65,000

320A

50,000

65,000

50,000

65,000

400A

50,000

65,000

50,000

65,000

600A

50,000

65,000

50,000

65,000

800A

50,000

65,000

50,000

65,000

1000A

50,000

65,000

50,000

65,000

1200A

50,000

65,000

50,000

65,000

Summary of Contents for ATC-900

Page 1: ...sition Contactor Based Transfer Switch Instruction Booklet Description Page Introduction 2 Receiving Handling and Storage 6 Equipment Description 7 Installation and Wiring 14 Operation 20 Testing and...

Page 2: ...A It is provided as a guide for authorized and qualified person nel only Please refer to the specific WARNING and CAUTION in Section 1 1 2 before proceeding If further information is required by the p...

Page 3: ...stored the ATS automatically transfers back and initiates generator shutdown In the event the Source 1 power source fails and the Source 2 power source does not appear the ATS remains connected to the...

Page 4: ...ent catalog numbers provide a significant amount of relevant information that pertains to a particular piece of equipment The Catalog Number Identification Table Table 2 provides the required interpre...

Page 5: ...applica ble setpoint ranges for the nominal voltage and frequency setting Source 2 Failed or Fails Source 2 is defined as failed when it is outside of its under voltage overvoltage underfrequency over...

Page 6: ...o sure Care should be exercised however to protect the equip ment from impact at all times Do not remove the protective packaging until the equipment is ready for installation When the ATS equipment r...

Page 7: ...POWER PANEL VOLTAGE SELECTION TRANSFORMER PANEL Figure 5A Three Basic Panels of an Open Transition ATS 1200A LOGIC PANEL POWER PANEL VOLTAGE SELECTION TRANSFORMER PANEL Figure 5B Three Basic Panels of...

Page 8: ...North American market voltage selection panel consists of multi tap transformers contained in a steel case mounted in the transfer switch enclosure Figure 7 The cover has two connec tors on it with th...

Page 9: ...oller has an operating temperature of 20 to 70 C 4 to 158 F The controller circuit board is protected by an insulating confor mal coating The specifications under normal operating conditions are as fo...

Page 10: ...hieves a transfer between sources with no power interruption Both sources must be synchronized in fre quency phase and voltage before the transfer is initiated In phase transition is a feature that wi...

Page 11: ...ad condition after a transfer from the generator source has been made Count down timing begins when the transfer is completed In applica tions where two generators are selected the same cool off timer...

Page 12: ...Control This feature displays status information of a remotely located ATC 900 controller The HMI type Remote Annunciator will seri ally communicate with the ATC 900 over the Modbus 485 or Ethernet u...

Page 13: ...ton ATS equipment enclosed in any of the enclosures listed in Table 3 is listed for application by UL and ULC In addition Eaton ATSs are listed in File E38116 by Underwriters Laborato ries Inc under S...

Page 14: ...supporting the weight of the enclosed ATS equipment For standard ATSs avoid locations that are moist hot or dusty However Eaton offers optional enclosure designs that can be used in special environmen...

Page 15: ...1A Typical Mounting of the ATS to a Mounting Surface Open Transition ATS for Wall Mounting Step 5 Double check to ensure that all packing and shipping materials have been removed Step 6 If Seismic Uni...

Page 16: ...tion Verify that the lugs supplied will accommodate the power cables being used Also verify that the cables comply with local electrical codes Standard ATS equipment as supplied from the factory will...

Page 17: ...ment is installed and operating properly 4 6 Engine Start Connection The engine control contact connections are located on the logic panel of the ATS Connect the engine start wires to the red ter mina...

Page 18: ...232 J14 CT Earth Controller Ground J8 USB Front Panel Memory Stick Interface J11 I O Module s SW1 Modbus Terminator Module J13 RS 422 Interface Source Load Interface Switch Position Contacts For more...

Page 19: ...he cover has two connec tors on it with the one on the right being selectable depending on the voltage applied to S1 and S2 The transformer unit is eas ily removed by removing the two front screws and...

Page 20: ...OURCE 2 IF A GENERATOR CONTROL SELECTOR SWITCH TO THE OFF POSITION BEFORE ATTEMPTING A MANUAL TRANS FER To manually operate 1 Disconnect all sources of power 2 Disconnect the J7 connector from the ATC...

Page 21: ...s on Source 1 4 Simultaneously the engine cool down timer initiates the shut down of the engine driven generator 5 Transfer of the load back to the Source 1 power source is now complete Section 6 Test...

Page 22: ...ded for a preset time after transfer to the Source 1 power source is com pleted 6 1 5 Alternate Tests 1 Alternate operational tests may be possible depending upon the options provided with any given A...

Page 23: ...to go to Source 1 Step 4 Depress the TRIP button located on the operating mechanism of the contactor to bring the contactor to neutral trip position Step 5 Depress the SELECT button located on the ope...

Page 24: ...the structure area for safety hazards or potential maintenance problems Inspect the area especially where switching device is installed for any safety hazards including personnel safety and fire hazar...

Page 25: ...at 68C8282H02 40 1200A Domestic Switch 480VAC 600VAC 4 Pole Cat 68C8282H02 Power Panel Close Transition Does not include Contactor 40 1200A Domestic Switch 480AC 600VAC 2 Pole Cat 69D8080H01 40 1200A...

Page 26: ...LY SUGGESTED THAT THE FULL INSTRUCTIONS BE FOLLOWED FOR ALL INSTALLATIONS SET UP AND TESTING Step 1 Mount the ATS on a flat rigid surface Figure 18A 18B Shim if necessary Figure 18A Mounting Details O...

Page 27: ...TAGE SELECTION PANEL LOGIC PANEL GROUND CONNECTION IB140036EN For more information visit www eaton com Instruction Booklet Effective October 2014 Page 27 O M Manual for 40 1200A 480 600 Vac ATC 900 3...

Page 28: ...TION PANEL LOGIC PANEL GROUND CONNECTION For more information visit www eaton com IB140036EN Instruction Booklet Page 28 Effective October 2014 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position O...

Page 29: ...e proper wire size as listed by the generator set Genset manufacturer For the I O connections there are some switches that the Inputs are wired to a terminal block while others are not When they are n...

Page 30: ...ource 1 contactor Momentarily energize K3 N Is Source 1 available yet Y Source 1 is powering the load TDN timer times out if Option 32A is enabled TDN timer times out if Option 32A is enabled Source 1...

Page 31: ...ad TDN timer times out if Option 32A is enabled TDN timer times out if Option 32A is enabled Source 1 is powering the load N Is Source 1 available yet TDEN timer times out Y Open Source 2 contactor En...

Page 32: ...ww eaton com IB140036EN Instruction Booklet Page 32 Effective October 2014 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Switch Figure 22 Close...

Page 33: ...N For more information visit www eaton com Instruction Booklet Effective October 2014 Page 33 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Swi...

Page 34: ...information visit www eaton com IB140036EN Instruction Booklet Page 34 Effective October 2014 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Swi...

Page 35: ...N For more information visit www eaton com Instruction Booklet Effective October 2014 Page 35 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Swi...

Page 36: ...OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence st...

Reviews: