background image

Instructional Booklet

Page

26

Effective:  March 2012

Instructions for Installation, Operation and Maintenance of the

Eaton ATC-800 Closed/Open Transition Transfer Switch Controller

For more information visit: www.eaton.com

IB ATS-C103

Step 6:  

Is the NORMAL switching device charged?

If YES:Proceed to Step 7.

If NO: Go through paragraph 6.3.4 first before 

continuing.

Step 7:  

Is the NORMAL power source available?

If YES:Proceed to Step 8.

If NO: Apply the correct system voltage to NORMAL 

connections.

Step 8:  

Is the EMERGENCY switch OPEN?

If YES:Proceed to Step 10.

If NO: Proceed to Step 9.

Step 9:  

Measure the voltage between terminals B10 and B11 on 

the EMERGENCY switching device (shunt trip). Is the 

voltage measured 120 Vac (+/- 10 volts)?  Record the 

reading.

If YES: Refer to the magnum breaker maintenance 

manual IB#2C12060 and check the shunt trip 

EMERGENCY switch.

If NO: Check the wiring to B10 and B11.

Step 10: 

Measure the voltage between terminals B12 and B13 on 

the NORMAL switching device (spring release coil). Is 

the voltage measured 120 Vac (+/- 10 volts)?  Record 

the reading.

If YES: Refer to the magnum breaker maintenance 

manual IB#2C12060 and check the spring

release coil NORMAL switching device.

If NO: Check the wiring to B12 and B13.

Step 11: 

If a problem persists, contact Eaton.

6.3.3  Transfer Switch Will Not Automatically Transfer To 

Emergency
Step 1:  

If the alternate source is a generator, is it running?

If YES: Proceed to Step 2.

If NO: Check the generator.  Check the engine start 

contacts.

Step 2:  

Are the correct line voltage and frequency available at ter-

minals E1, E2 and E3?  Record the readings.

If YES: Proceed to Step 3.

If NO: Verify that there is output voltage from the 

generator.

Step 3:  

Is the voltage selector plug in the correct position?

If YES:  Proceed to Step 4.

If NO:   Position plug correctly.

Step 4:  

Is the NORMAL source available?

If YES: Proceed to Step 5.

If NO:  Proceed to Step 6.

Step 5:  

Is a test (Manual or Exercise) being run?

If YES: STOP!  The transfer switch should not transfer

to EMERGENCY.  The NORMAL source is 

preferred.

If NO:  Proceed to Step 6.

Step 6:  

Check the voltage on transformer ET1 by measuring volt-

age between voting relay KV-8 and GND.  Is the voltage 

measured 120 Vac (+/- 10 volts)?  Record the reading.

If YES: Proceed to Step 7.

If NO:  Check voltage transformer ET1.

Step 7:  

Is the EMERGENCY switching device charged?

If YES: Proceed to Step 8.

If NO:  Go through paragraph 6.3.4 first before 

 continuing.

Step 8:  

Is the NORMAL switching device OPEN?

If YES: Proceed to Step 10.

If NO:  Proceed to Step 9.

Step 9:  

Measure the voltage between terminals B10 and B11 on 

the NORMAL switching device (shunt trip). Is the volt-

age measured 120 Vac (+/- 10 volts)?  Record the read-

ing.

If YES: Refer to the magnum breaker maintenance 

manual IB#2C12060 and check the shunt trip

NORMAL switch.

If NO:

Check the wiring to B10 and B11.

Step 10: 

Measure the voltage between terminals B12 and B13 on 

the EMERGENCY switching device (spring release coil). 

Is the voltage measured 120 Vac (+/- 10 volts)?  

Record the reading.

If YES: Refer to the magnum breaker maintenance 

manual IB#2C12060 and check the spring

release coil EMERGENCY switching device.

If NO: Check the wiring to B12 and B13.

Step 11: 

If a problem persists, contact Eaton.

Summary of Contents for ATC-800

Page 1: ...roller Instructional Booklet Description Page 1 Introduction 2 2 Hardware Description 7 3 Operator Panel 11 4 Operation 14 5 Programming 20 6 Troubleshooting and Maintenance 23 Appendix A Status Displ...

Page 2: ...al or conse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system cost of capital loss of power additional expenses in the use of exi...

Page 3: ...from most system voltages available worldwide at 50 or 60 Hertz In addition a period of no control power operation is provided ATC 800 moni tors the condition of the 3 phase line to line voltage and...

Page 4: ...ce is already available the TDES timer is bypassed Standard Feature 3 Time Delay Emergency to Normal TDEN TDEN delays the transfer to the Normal Source to permit stabiliza tion of the Normal power sou...

Page 5: ...ual to or above the pickup setting to become available again Underfrequency Monitoring for Source 1 1UFD 1UFP This feature constantly monitors Source 1 for an underfrequency condition When the Source...

Page 6: ...time delay in the transfer switch Neutral position when both breakers are open This delay takes place when the load is transferred in either direction to prevent excessive in rush currents due to out...

Page 7: ...Modbus compatible devices A separately mounted communications mod ule will enable the automatic transfer controller to be remotely monitored controlled and programmed via the network Optional Feature...

Page 8: ...ssages 5 Display LEDs seven LEDs to identify the Display Win dow Information 6 Help Pushbutton provides English language help information in any operational mode 7 Increase Decrease Pushbuttons used i...

Page 9: ...e communication module PONI to the back of the ATC 800 Figure 3 or in a remote location Since the ATC 800 is always supplied with a communications port a PONI can be easily retrofitted to the ATC 800...

Page 10: ...kup Range Volts Breaker Switch Style ATS Contactor Style ATS Dropout 2 to 99 of Nominal System Voltage Dropout 2 to 99 of Nominal System Voltage Overvoltage Dropout Range Volts Breaker Switch Style AT...

Page 11: ...Source 1 is the preferred source choice Source 1 Connected Status LED This LED is lit green if Source 1 is connected This is accom plished by sensing the Source 1 breaker via the S1 closed auxil iary...

Page 12: ...sfer will occur and the engine will run for the programmed run time 3 3 4 Display Select Pushbutton As the Display Select Pushbutton is pressed and released ATC 800 steps through the following display...

Page 13: ...le conditions will be shown OVER V The source has risen above the dropout setting and not dropped below the pickup setting UNDER V The source has dropped below the dropout setting and not risen above...

Page 14: ...ated by the features supplied and their programmed setpoint values It provides a sum mary of ATC 800 s intelligence and supervisory circuits which constantly monitor the condition of both normal and e...

Page 15: ...g this contact will activate the Emergency Inhibit input If the Emergency Inhibit contact is opened when the load is con nected to the Normal Source no action will be taken if the Normal Source is ava...

Page 16: ...able up to 10 separate loads The Addressable Relay II must be set for 1200 BAUD rate WATCHDOG feature disabled RELAY PULSE feature disabled Address range from 002 to 00B Under normal condition with so...

Page 17: ...itions include improper circuit breaker operation motor operator failure and unsuccessful closed or in phase transition An alarm may be reset by simultane ously pressing the Increase and Decrease Push...

Page 18: ...the TDNE countdown the Emergency Source goes unavailable more than three times Each time TDNE will restart 4 If the Emergency Source is powering the load and it goes unavailable for more than the TDEF...

Page 19: ...ransition require that both sources be available and synchronized in voltage frequency and phase The frequency difference must be less than the closed transition fre quency difference set point 0 0 to...

Page 20: ...The Setpoints LED will be lit red and the first programming possibility will appear in the display Use the Step Pushbutton to move from one feature setpoint to another stopping at those in need of rep...

Page 21: ...ltage1 115 110 Volts 1OVP Source 1 Overvoltage Pickup Volts Breaker Switch Style ATS Contactor Style ATS 103 to Dropout 2 of Nominal System Voltage1 103 to Dropout 2 of Nominal System Voltage1 110 105...

Page 22: ...ser Minute 0 to 59 Minutes 0 Minutes MANTR Re Transfer Mode 0 Automatic 1 PB Return 0 CTDNE Commitment to Transfer in TDNE 0 Not Committed 1 Committed 0 TMODE Engine Test With Without Load Transfer 0...

Page 23: ...nutes of inactivity with pushbuttons when changing set points Voltage dropout and pickup setpoints are different than what was programmed Adjusted nominal voltage setpoint Re adjust all dropout and pi...

Page 24: ...open when Source 1 contactor opened S1 Aux Close contacts did not close when Source 1 Contactor closed Check Source 1 contactor trip wiring Press Increase and Decrease push buttons simultaneously to c...

Page 25: ...ts Determine the cause and rectify if possible Replace defective com ponents after the cause is determined Step 5 Press the push to close button on the normal switching device Verify whether or not th...

Page 26: ...the correct line voltage and frequency available at ter minals E1 E2 and E3 Record the readings If YES Proceed to Step 3 If NO Verify that there is output voltage from the generator Step 3 Is the volt...

Page 27: ...e ATC 800 are de energized These may also be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to assure that reconn...

Page 28: ...Waiting for load voltage to decay before completing the transfer TDP Countdown timing while waiting for a pre transfer acknowledge input TSEQ Countdown timing between sequenced loads NO R xx No commun...

Page 29: ...Source 2 Connected Time This counter logs time in hours whenever Source 2 is connected to the load Time will start being logged at the time the S2 AUX control input is closed This counter will count u...

Page 30: ...erator 7 Engine test 8 Manual re transfer 9 Engine Test via communications 10 Go to neutral 11 Program mode 12 Options or setpoints error 13 Emergency Inhibit 14 Go to Emergency 15 Lock out 16 Failed...

Page 31: ...sly roll over between AM and PM values Minutes By using the Increase or Decrease Pushbuttons the minutes of the day can be adjusted to the present value The number will continuously roll over between...

Page 32: ...For 1 Phase Sensing with Open Transition FREQ Condition VOLT FREQ Condition VAB VBC VCA FREQ Condition VOLT FREQ Condition Display is blank or a status message appears Note All menu items are not nece...

Page 33: ...D 2UFD 1UFP 2UFP 1OFD 2OFD 1OFP 2OFP TDN TDNLD LDCY PRF SRC EXER EXLD PEDAY PEH PEMIN MANTR CTDNE TMODE TER TPRE GENNO PHASE TSEQ STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP...

Page 34: ...breaker Momentarily energize K3 Source 1 becomes unavailable or Engine Test Plant Exerciser Go To Emergency TDES timer times out Send Engine Start signal Energize Gen Start relay TDNE timer times out...

Page 35: ...eaker Momentarily energize K3 Source 1 becomes unavailable or Go To Emergency TDNE timer times out Open Source 1 breaker Energize K2 Y Source 2 is powering the load Close Source 1 breaker Momentarily...

Page 36: ...signal Energize Gen Start relay TDNE timer times out Y Source 2 is powering the load Energize Alarm relay Open Source 1 Energize K2 Close Source 2 out of Sync Momentarily energize K4 Source 1 is powe...

Page 37: ...tion visit www eaton com Instructional Booklet Effective March 2012 Page 37 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switch Controll...

Page 38: ...let Page 38 Effective March 2012 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switch Controller For more information visit www eaton com...

Page 39: ...re information visit www eaton com Instructional Booklet Effective March 2012 Page 39 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switc...

Page 40: ...DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort inclu...

Reviews: