12
Note:
1. The conductor cross sections above apply for theoretical maximum currents in consideration of protective
devices.
2. *n represents the number of the wire, which indicates that n same AWG wires are needed. For example,
“2AWG*3”indicates that three 2 AWG wires are needed.
3. The diameter of the earth wire needs to be the same as the N wire.
5.2 Requirements of protective devices
The 3A3 Pro UPS supplies no breakers or protective components with its cabinet for input (including battery
input). For output, only breakers are connected in the cabinet and no protective components are supplied.
When installing the 3A3 Pro UPS, the user needs to connect the external breakers and protective components
in the input and output terminals. It is recommended to select the NFB instead of the traditional combination
kit including breaker and fuse.
The voltage and current should be taken into consideration when selecting NFB. And it is recommended to
select it according to the real capacity of the UPS (the modules installed) to ensure effective protection. Please
refer to the table below for UPS module and corresponding NFB requirements.
Note: it is recommended to choose three-pole NFBs (linked breaker) for the input and output of the UPS and
a three-pole NFB (linked breaker) for the battery. Refer to the Section 5.3 and Section 5.4 in this manual for
detailed information.
UPS
Module
UPS Input NFB
UPS Output NFB
Battery NFB
Voltage/Current
Voltage/Current
Voltage/Current
1
3φ 40A/ 250VAC
3φ 40A/ 250VAC
3φ 40A/ 500VDC
2
3φ 80A/ 250VAC
3φ 80A/ 250VAC
3φ 80A/ 500VDC
3
3φ 120A/ 250VAC
3φ 120A/ 250VAC
3φ 120A/ 500VDC
4
3φ 160A/ 250VAC
3φ 160A/ 250VAC
3φ 160A/ 500VDC
5
3φ 200A/ 250VAC
3φ 200A/ 250VAC
3φ 200A/ 500VDC
6
3φ 240A/ 250VAC
3φ 240A/ 250VAC
3φ 240A/ 500VDC
7
3φ 280A/ 250VAC
3φ 280A/ 250VAC
3φ 280A/ 500VDC
8
3φ 320A/ 250VAC
3φ 320A/ 250VAC
3φ 320A/ 500VDC
9
3φ 360A/ 250VAC
3φ 360A/ 250VAC
3φ 360A/ 500VDC
10
3φ 400A/ 250VAC
3φ 400A/ 250VAC
3φ 400A/ 500VDC
Summary of Contents for ARRAY 3A3 Pro
Page 1: ...ARRAY 3A3 Pro UPS...
Page 2: ......
Page 3: ...UPS...
Page 5: ...1 2 3 4 5 UPS 6 7 8 9 UPS UPS 1 2 UPS UPS 3 Eaton 1 UPS 2 3 4 A B C D E 5 6 7...
Page 6: ...1 a 0 40 20 90 b c 2 UPS 25 55 UPS 0...
Page 7: ...UPS UPS UPS UPS 01 03 05 08 11 16 18 21 31 33 35 37 39 40 41...
Page 10: ...3 2 1 1 2 1 2 2 2 3 2 3 4 2 4 5 2 5 2 2 2 1 2 3 2 4 2 5...
Page 11: ...4 2 8 2 2 2 6 2 7 UPS 1 2 6 2 UPS 2 7 3 UPS 2 8...
Page 12: ...5 3 1 UPS 120kVA 3 1 LCD UPS UPS 3 2 150kVA...
Page 13: ...6 3 4 120K 3 6 150K 3 3 120K 3 5 150K...
Page 14: ...7 3 2 UPS 3 7 3 10 3 8 3 9...
Page 16: ...9 1 2 3 M8 4 2 4 2 4 1 4 3 4 3 4 UPS 4 3 D1 D2 D3...
Page 17: ...10 5 UPS 6 4 4 7 4 6 UPS UPS 4 5 8 M6 4 5 9 UPS 4 4 4 5 3U 2 2U...
Page 20: ...13 UPS 1 1 UPS N 2 3A3 Pro UPS 32 40 40 3 UPS UPS 5 4 5 2 5 3 N...
Page 21: ...14 2 1 5 6 2 UPS 5 7 3 4 5 6 5 7 UPS 5 4 5 5 UPS...
Page 22: ...15 1 5 8 2 UPS 5 9 3 5 8 5 9 150kVA 1 2 5 10 3 UPS 5 11 4 5 10 UPS 5 11 UPS...
Page 26: ...19 7 2 UPS 1 1 ON 6 2 2 UPS 7 3 6 3 4 5 7 4 1 ENTER 1111 1234 7 3 7 4...
Page 27: ...20 1 UPS UPS 2 EPO 3 4 7 3 10 UPS UPS ENTER 1 2 1111 1234...
Page 28: ...21 8 1 UPS UPS UPS UPS ID ID English 14 UPS LCD LCD LCD 13 10 10 5 11 3V...
Page 30: ...23 UPS 1 2 3 1 2 3 1 2 UPS 3 UPS 4 UPS 10 UPS...
Page 31: ...24 UPS UPS 8 3 a b 45 0 45 0...
Page 32: ...25 7 2 7 3 1111 1234 8 4 35 35 a b 35 35 45 0...
Page 33: ...26 UPS 8 5 ID ID 0 65535...
Page 34: ...27 8 6 YYYY MM DD hh mm ss xxx xxx ID ID 0 65535 CSB UPM1 UPM10 0 65535 14 8 6 1...
Page 35: ...28 10 60min 0 9000s 10s LCD 1 100 13 400 830 3938 800 830 3938 13666666666 13888888888...
Page 36: ...29 8 6 2 45 18 18 Panasonic_100AH 15 15 5 5 10 10 242V 198V...
Page 37: ...30 XCP USB BUS 8 7...
Page 38: ...31 UPS 400 889 3938 UPS 1 1 UPS UPS 2 9 1 1 UPS 2 3 UPS 9 1 UPS 9 2 9 3 9 1...
Page 43: ...36 2 1 LCD 6 LCD 11 3...
Page 46: ...39 24 400 889 3938 www eaton com powerquality upsservice eaton com...
Page 47: ...40 _ _ 1 4 2 1 2 3 4 5 Fault...
Page 103: ...614 00789 03...