AMH-4.76-VR

+

VR-Series

 Replacement Circuit Breaker

m

 WARNING

KEEP HANDS OFF THE TOP EDGE OF THE FRONT BARRIER WHEN PUSHING 

A CIRCUIT BREAKER INTO A CELL. FAILURE TO DO SO COULD RESULT IN 

BODILY INJURY, IF FINGERS BECOME WEDGED BETWEEN THE CIRCUIT 

BREAKER AND THE CELL. USE THE HANDLES PROVIDED ON THE FRONT OF 

THE CIRCUIT BREAKER FACEPLATE, OR USE BOTH FULLY OPENED HANDS 

FLAT ON THE FRONT OF THE FACEPLATE.

These checks can be performed with the circuit breaker in its 

withdrawn or disconnect position and connecting the circuit breaker 

to a test cabinet or to the switchgear cell’s secondary receptacle 

using the special extension cable designed for this purpose and 

described in Section 3.
Perform electrical operations checks. Close and trip the circuit 

breaker electrically several times to verify that the operation is 

reliable and consistent. Check that the operation of the spring 

charging motor is reasonably prompt and that the motor makes no 

unusual noise.

m

 WARNING

DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE CIRCUIT 

BREAKER IN THE “CONNECT” POSITION BECAUSE OF THE POSSIBILITY OF 

CONNECTING DE-ENERGIZED LOAD CIRCUITS TO THE ELECTRICAL POWER 

SOURCE, RESULTING IN DEATH, PERSONNEL INJURY OR EQUIPMENT

compressed spring length (measured in the open position) is 

recorded if different than the dimension in this instruction book.

Sttp 11e:

  After an adjustment is made, make sure that all nuts are 

secured in place, prior to returning to service.

5.3   MANUAL OPERATION CHECK

Manual operational checks must be performed before the circuit 

breaker  is connected to an energized circuit. Tests must be 

performed with the circuit breaker withdrawn from the cell or in the 

disconnect position. While the circuit breaker is withdrawn or in the 

disconnect position, place the maintenance tool into the manual 

charge socket opening and charge the closing springs with about 

36 up and down strokes of the handle. When charging is complete, 

the closing crank goes over center with an audible “click” and the 

springs Charged / Discharged Indicator shows “Charged”. Remove 

the maintenance tool.

m

 NOTICE

IF THE SPRINGS ARE TO BE CHARGED ON A CLOSED CIRCUIT BREAKER, 

NO CLICK IS HEARD AT THE END OF CHARGING OPERATION. DISCONTINUE 

CHARGING AND REMOVE THE MAINTENANCE TOOL AS SOON AS 

“CHARGED” FLAG IS FULLY VISIBLE. CONTINUE ATTEMPTS TO FURTHER 

CHARGE MAY RESULT IN DAMAGE TO THE MECHANISM.

m

 WARNING

ALWAYS REMOVE THE MAINTENANCE TOOL AFTER CHARGING THE 

SPRING. FAILURE TO REMOVE THE MAINTENANCE TOOL FROM THE 

BREAKER COULD CAUSE INJURY TO PERSONNEL AND/OR EQUIPMENT 

DAMAGE IF THE BREAKER WAS TO CLOSE.

Close and trip the circuit breaker by pushing the close lever then the 

trip lever (Figure 3.3).

5.4   VACUUM INTERRUPTER INTEGRITY

Using a dry lint-free cloth or a paper towel, clean all the insulating 

surfaces of the pole units. Conduct a vacuum interrupter integrity 

check as described in Section 6.

5.5   LOW FREQUENCY WITHSTAND TEST (INSULATION 

CHECK)

Check breaker primary and secondary insulation per Section 6.

5.6   CONTACT EROSION AND WIPE

Manually charge the closing springs and close the circuit breaker. 

Check contact erosion and wipe as described in Section 6.

5.7   PRIMARY CIRCUIT RESISTANCE

Check the primary circuit resistance as described in Section 6. The 

resistance should not exceed the values specified. Record the values 

obtained for future reference.

5.8   ELECTRICAL OPERATIONS CHECK

After going through the above steps, the circuit breaker is now 

ready to be operated electrically. It is preferred that this check be 

made with the circuit breaker in the Test position in the breaker 

compartment.
Since the Type AMH-4.76-VR+ Circuit Breaker is for use in existing 

AMH Metal-Clad Switchgear, installation procedures are similar. If it 

is necessary to reference anything in the breaker compartment, refer 

to the original instruction books supplied with the assembly.

m

 WARNING

EXAMINE THE INSIDE OF THE CELL BEFORE INSERTING THE BREAKER 

FOR EXCESSIVE DIRT OR ANYTHING THAT MIGHT INTERFERE WITH THE 

CIRCUIT BREAKER TRAVEL.

Figurt 5.2. AMH-VR+ in tht Disconntct Position

Summary of Contents for AMH-4.76-VR+

Page 1: ...September 2018 Instruction Book IB182923EN AMH 4 76 VR VR Series Replacement Circuit Breaker Effective AMH 4 76 VR 1200A Shown...

Page 2: ...f further information is required an Eaton sales office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling po...

Page 3: ...NTERLOCKS 14 4 7 1 ANTI CLOSE INTERLOCK 14 4 7 2 RACKING SYSTEM TRIP AND SPRING RELEASE INTERLOCKS 14 4 7 3 ACTIVE INTERLOCK 15 4 7 4 SHUTTER INTERLOCK 15 4 8 MISCELLANEOUS ITEMS 15 4 8 1 OPERATIONS C...

Page 4: ...important that this installation and maintenance instruction booklet be read and followed closely to achieve optimum performance and a long useful circuit breaker life in its application 1 1 VISUAL IN...

Page 5: ...ted Voltage Factor Rated Withstand ANSI Test Voltage Rated Short Circuit Maximum Sym Interrupting Capability Closing and Latching Momentary Capabilities kV MVA Amps K Low Freq kV RMS Impulse kV Peak I...

Page 6: ...R VR Series Replacement Circuit Breaker E H I G F J H D B C C A Table 2 AMH 4 76 VR Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J AMH 4 76 VR 250...

Page 7: ...injury and or property damage Do not work on a breaker with the secondary test coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death personnel inj...

Page 8: ...ker Style 94C9506G01 Racking Handle The racking handle is used to drive the racking mechanism which moves the circuit breaker into and out of the cell The original OEM racking handle will interface wi...

Page 9: ...d indicator Push the manual trip button The breaker will trip as shown by the breaker contacts open green indicator After completing this initial check leave the closing springs discharged and breaker...

Page 10: ...ernal View of AMH 4 76 VR AMH 4 76 VR 250 1200A Shown Front External View 1 Manual Charging Socket 5 Guide Bar 9 Push to Open Button 2 Push To Close Button 6 Breaker Contacts Indicator 10 MOC Actuator...

Page 11: ...ment Circuit Breaker Figure 3 4 Rear External View of AMH 4 76 VR AMH 4 76 VR 250 1200A Shown Rear External View 1 Shutter Actuator 4 SURE CLOSE Spring 7 Secondary Disconnect 2 Primary Disconnect 5 Gu...

Page 12: ...R ASSEMBLY Each vacuum interrupter assembly also referred to as pole unit is assembled at the factory as a unit to assure correct dimensional relationships between working components Three interrupter...

Page 13: ...ND FINGERS AWAY FROM CIRCUIT BREAKER S INTERNAL PARTS WHILE THE CIRCUIT BREAKER CONTACTS ARE CLOSED OR THE CLOSING SPRINGS ARE CHARGED THE CIRCUIT BREAKER CONTACTS MAY OPEN OR THE CLOSING SPRINGS DISC...

Page 14: ...ct opens the SR circuit so that even though the circuit breaker would subsequently open it could not be reclosed before CS C was released and remade This is the anti pump function 4 5 1 TIMING The ope...

Page 15: ...ted by the circuit breaker shutter actuator that opens the shutter as the circuit breaker is racked into the circuit breaker compartment and closes the shutter as the circuit breaker is racked out of...

Page 16: ...pt between Test and Connect positions OPERATION C and NO C and NC C and NO C and NO C and NC C and NO Brown Switch Black Switch Black Switch Brown Switch SWITCH TERMINAL LS1 bb LS2 aa LS2 bb LC PS1 PS...

Page 17: ...ront Faceplate Removed VR Series Circuit Breaker Element Mechanism 1 LH Closing Spring 5 Spring Release Assembly 9 Manual Charge Socket 2 Motor Cutoff Switch 6 Shunt Trip Assembly 10 Ratchet wheel 3 L...

Page 18: ...nkage 1 Spring Release Close Latch 6 Ratchet Wheel 11 Anti Close Interlock 2 Pole Shaft 7 Spring Crank 12 Motor Ratchet Lever 3 Closing Spring Fixed End 8 Cam Shaft 13 Spring Release Close Clapper 4 C...

Page 19: ...Closing Spring Discharged 4 9 c Breaker Closed and Closing Spring Discharged 4 9 b Breaker Open and Closing Spring Charged 4 9 d Breaker Closed and Closing Spring Charged Charging Schematic 1 Main Li...

Page 20: ...does not fully open or close it is time to maintain the MOC in the cell Maintenance usually means cleaning and lubricating the MOC mechanism If the MOC has seen a large number of cycles however worn c...

Page 21: ...of the handle When charging is complete the closing crank goes over center with an audible click and the springs Charged Discharged Indicator shows Charged Remove the maintenance tool m NOTICE IF THE...

Page 22: ...s indicator reads OPEN d Push the circuit breaker into the cell until the mechanical stop is reached this will be indicated by an audible click At this point the side plunger has fallen into the front...

Page 23: ...uit breaker can be operated either electrically or mechanically Remove rotary racking handle before performing any testing b To further remove the circuit breaker to the disconnect position continue t...

Page 24: ...lace Insulation Integrity Main circuit to ground Withstand 15kV 60Hz for 1 Minute 5kV Rating 27kV 60Hz for 1 Minute 8 25kV and 15kV Ratings Hi pot Tester Clean and retest or replace Control circuit to...

Page 25: ...t is recommended that the equipment be capable of delivering 25 milliamperes for one minute The current delivery capability of 25 mA ac applies when all three vacuum interrupters are tested in paralle...

Page 26: ...from Ohm s Law and is expressed in micro ohms Repeat for the remaining two poles The resistance should not exceed the factory test levels more than 200 as stated in IEEE C37 09 Factory test levels ar...

Page 27: ...e Tool Mounting Testing Locations by Circuit Breaker Type CIRCUIT BREAKER DESIGNATION APPROXIMATE MECHANISM CHASSIS WIDTH INCH LOWER MOUNTING HOLE LOWER MOUNTING HOLE MARKER PLACEMENT HOLE AM4 16 VR 1...

Page 28: ...on a sheet of paper that can be kept as a record of the test Record the date of the test person conducting the test circuit breaker serial number and the operations counter on the tape or paper Figur...

Page 29: ...Marker CloSure Tool TM 15O 15O Figure 6 13 Determining the Distance Traveled Figure 6 14 Illustrative Testing Tape Sample Figure 6 12 Evaluate the CloSure Performance Date of Breaker Operations CloSu...

Page 30: ...lement requires maintenance only once every ten years or ten thousand operations which ever comes first After a ten year service interval or when ten thousand operations have been reached contact your...

Page 31: ...or burned Motor Cut Off Contacts open or burned Trip Coil Assembly Clapper fails to reset Closing sound but no close Pole Shaft Not open fully Trip Latch Reset Spring Damaged or missing Trip Bar D Sha...

Page 32: ...SWITCH Breaker Auxiliary Switch 94C9525G13 5 BREAKER POSITION SWITCH Breaker Position Switch PS1 94C9525H06 6 BREAKER POSITION SWITCH Breaker Position Switch PS2 94C9525H07 7 LATCH CHECK SWITCH Latch...

Page 33: ...33 Instruction Book IB182923EN September 2018 www eaton com AMH 4 76 VR VR Series Replacement Circuit Breaker...

Page 34: ...vard Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No IB182923EN September 2018 Eaton is a registered trademark All trademarks are property of th...

Reviews: