background image

12

Instruction Book    

IB182023EN   March 2016   www.eaton.com

AMH-4.76-VR

Replacement Circuit Breaker

breaker. If the mark on the interrupter stem is visible, the interrupter 

is satisfactory. If the mark is no longer visible, the interrupter 

assembly must be replaced.
The erosion indicator is easily viewed from the rear on the 5kV, 7.5kV 

or 15kV designs. 

 WARNING

FAILURE TO REPLACE THE INTERRUPTER ASSEMBLY WHEN INDICATED BY 

THE CONTACT EROSION INDICATOR COULD CAUSE THE BREAKER TO FAIL, 

LEADING TO DEATH, PERSONAL INJURY OR PROPERTY DAMAGE.

4.1.3   CONTACT WIPE AND STROKE

Contact wipe is the indication of the force holding the vacuum 

interrupter contacts closed and the energy available to hammer the 

contacts open with sufficient speed for interruption.
Stroke is the gap between fixed and moving contacts of a vacuum 

interrupter with the breaker open. 
The circuit breaker mechanism provides a fixed amount of motion 

to the operating rods. The first portion of the motion is used to 

close the contacts (i.e. stroke) and the remainder is used to further 

compress the preloaded wipe spring. This additional compression 

is called wipe. Wipe and stroke are thus related to each other. 

As the stroke increases due to the erosion of contacts, the wipe 

decreases. A great deal of effort and ingenuity has been spent in the 

design of VR-Series breakers, in order to eliminate any need for field 

adjustment of wipe or stroke. 

 WARNING

THERE IS NO PROVISION FOR IN-SERVICE ADJUSTMENTS OF CONTACT 

WIPE AND STROKE. ALL SUCH ADJUSTMENTS ARE FACTORY SET AND 

SHOULD NOT BE ATTEMPTED IN THE FIELD.

4.2   PHASE BARRIERS

Phase barriers are sheets of insulation located between the 

interrupter pole assemblies and on the sides of the breaker frame. 

The phase barriers are designed to isolate energized conductor 

components in each phase from the adjacent phase and ground.

 WARNING

ALL PHASE BARRIERS MUST BE IN PLACE BEFORE PLACING THE 

CIRCUIT BREAKER INTO SERVICE. FAILURE TO HAVE THEM IN POSITION 

CAN CAUSE DEATH, SERIOUS PERSONNEL INJURY AND/OR PROPERTY 

DAMAGE.

4.3   BUSHINGS AND DISCONNECTING CONTACT 

ASSEMBLIES

The line and load bushing assemblies, which are the primary 

circuit terminals of the circuit breaker, consist of six silver plated 

conductors. Solid stab type primary disconnecting contacts at 

the ends of the conductors provide means for connecting and 

disconnecting the breaker to the bus terminals in the switchgear 

compartment.

4.4   STORED ENERGY MECHANISM

The spring-type stored energy operating mechanism is mounted on 

the breaker frame and in the front of the breaker. Manual closing 

and opening controls are at the front panel (Figure 3.3). They are 

accessible while the breaker is in any of its four basic positions. (See 

Section 5 in this manual)
The mechanism stores the closing energy by charging the closing 

springs. When released, the stored energy closes the breaker, 

charges the wipe and resets the opening springs. The mechanism 

may rest in any one of the four positions shown in Figure 4.6 as 

follows:

a. Breaker open, closing springs discharged.
b. Breaker open, closing springs charged.
c. Breaker closed, closing springs discharged.
d. Breaker closed, closing springs charged.
The mechanism is a mechanically “trip-free” design. Trip-free is 

defined later in this section.
In normal operation the closing spring is charged by the spring 

charging motor, and the breaker is closed electrically by the 

switchgear control circuit signal to energize the spring release coil. 

Tripping is caused by energizing the trip coil through the control 

circuit.
For maintenance inspection purposes the closing springs can be 

charged manually by using the maintenance tool and the breaker can 

be closed and tripped by pushing the “Push to Close” and “Push to 

Open” buttons on the front panel.

 WARNING

KEEP HANDS AND FINGERS AWAY FROM BREAKER’S INTERNAL PARTS 

WHILE THE BREAKER CONTACTS ARE CLOSED OR THE CLOSING SPRINGS 

ARE CHARGED. THE BREAKER CONTACTS MAY OPEN OR THE CLOSING 

SPRINGS DISCHARGE CAUSING CRUSHING INJURY. DISCHARGE 

THE SPRINGS AND OPEN THE BREAKER BEFORE PERFORMING ANY 

MAINTENANCE, INSPECTION OR REPAIR ON THE BREAKER.

THE DESIGN OF THIS CIRCUIT BREAKER ALLOWS MECHANICAL CLOSING 

AND TRIPPING OF THE BREAKER WHILE IT IS IN THE “CONNECT” 

POSITION. HOWEVER, THE BREAKER SHOULD BE CLOSED MECHANICALLY 

ONLY IF THERE IS POSITIVE VERIFICATION THAT LOAD SIDE CONDITIONS 

PERMIT. IT IS RECOMMENDED THAT CLOSING THE BREAKER IN THE 

“CONNECT” POSITION ALWAYS BE DONE WITH THE CUBICLE DOOR 

CLOSED. FAILURE TO FOLLOW THESE DIRECTIONS MAY CAUSE DEATH, 

PERSONAL INJURY, OR PROPERTY DAMAGE.

ELECTRICAL TRIPPING CAN BE VERIFIED WHEN THE BREAKER IS IN THE 

“TEST” POSITION.

4.4.1   CLOSING SPRING CHARGING

Figure 4.5 shows schematic section views of the spring charging 

parts of the stored energy mechanism.
The major component of the mechanism is a cam shaft assembly 

which consists of a shaft to which are attached two closing spring 

cranks (one on each end), the closing cam, drive plate, and a free-

wheeling ratchet wheel.
The ratchet wheel (6) is actuated by an oscillating ratchet lever 

(12) and drive pawl (10) driven by the motor eccentric cam. As the 

ratchet wheel rotates, it pushes the drive plates which in turn rotate 

the closing spring cranks and the closing cam on the cam shaft. 

The motor will continue to run until the limit switch “LS” contact 

disconnects the motor.
The closing spring cranks have spring ends connected to them, 

which are in turn coupled to the closing springs. As the cranks 

rotate, the closing springs get charged.
The closing springs are completely charged, when the spring cranks 

go over dead center and the closing stop roller (9) comes against the 

spring release latch (1). The closing springs are now held in the fully 

charged position.
The closing springs may also be charged manually as follows: Insert 

the maintenance tool in the manual charging socket. Move it up and 

down several times (about 36) until a clicking sound is heard and 

closing spring status indicator shows “charged” (Figure 3.3). Any 

further motion of the maintenance tool will result in free wheeling of 

the ratchet wheel and will not result into advance of charging.

Summary of Contents for AMH-4.76-VR

Page 1: ...March 2016 Instruction Book IB182023EN AMH 4 76 VR Replacement Circuit Breaker Supercedes October 2013 Effective AMH 4 76 VR 4 76 1200A Shown...

Page 2: ...office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Ea...

Page 3: ...BLOCK 13 4 7 INTERLOCKS 13 4 7 1 ANTI CLOSE INTERLOCK 13 4 7 2 RACKING SYSTEM TRIP AND SPRING RELEASE INTERLOCKS 13 4 8 MISCELLANEOUS ITEMS 15 4 8 1 MOC OPERATOR 15 4 8 2 OPERATIONS COUNTER 15 SECTION...

Page 4: ...K RESPONSE CODE VR Series circuit breakers have a quick response code QR Code on the escutcheon of the circuit breaker cover This QR Code is a matrix barcode that provides direct access to download VR...

Page 5: ...VR Replacement Circuit Breaker E H I G F J H D B C C A Table 2 AMH 4 76 VR Dimensions Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H I J AMH 4 76 VR 250 250U 120...

Page 6: ...nd or property damage Do not work on a breaker with the secondary test coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death personnel injury and...

Page 7: ...eaker Style 94C9506G01 Racking Handle The racking handle is used to drive the racking mechanism which moves the circuit breaker into and out of the cell The original OEM racking handle will interface...

Page 8: ...nual trip button The breaker will trip as shown by the breaker contacts open green indicator After completing this initial check leave the closing springs discharged and breaker contacts open Outdoor...

Page 9: ...ont External View of AMH 4 76 VR Front External View 1 Manual Charging Socket 5 Guide Bar 9 MOC Actuator 2 Push To Close Button 6 Breaker Contacts Indicator 10 Push To Open Button 3 Racking Access Doo...

Page 10: ...Replacement Circuit Breaker Figure 3 4 Rear External View of AMH 4 76 VR Rear External View 1 Shutter Actuator 4 SURE CLOSE Spring 7 Secondary Disconnect 2 Primary Disconnect 5 Guide Rail 8 Ground Con...

Page 11: ...he vacuum to be quickly restored and prevents the transient recovery voltage from causing a restrike across the gap of the open contacts 4 1 1 THE INTERRUPTER ASSEMBLY Each interrupter is assembled at...

Page 12: ...r positions shown in Figure 4 6 as follows a Breaker open closing springs discharged b Breaker open closing springs charged c Breaker closed closing springs discharged d Breaker closed closing springs...

Page 13: ...ely retrofitted breakers Consequently it prevents the breaker from closing automatically even though the control close contact may have been made while the breaker is racked to the CONNECTED position...

Page 14: ...een Test and Connect positions OPERATION C and NO C and NC C and NO C and NO C and NC C and NO Brown Switch Black Switch Black Switch Brown Switch SWITCH TERMINAL LS1 bb LS2 aa LS2 bb LC PS1 PS2 Break...

Page 15: ...e breaker s MOC operator interfaces with the cell MOC switch in the same manner as the original breaker being replaced All VR Series breakers which are supplied with MOC operators are engineered with...

Page 16: ...t Front Faceplate Removed 18WR Vacuum Element 1 LH Closing Spring 5 Spring Release Assembly 9 Manual Charge Socket 2 Motor Cutoff Switch 6 Shunt Trip Assembly 10 Ratchet wheel 3 Latch Check Switch Rea...

Page 17: ...Spring Release Close Latch 6 Ratchet Wheel 11 Anti Close Interlock 2 Pole Shaft 7 Spring Crank 12 Motor Ratchet Lever 3 Closing Spring Fixed End 8 Cam Shaft 13 Spring Release Close Clapper 4 Closing...

Page 18: ...g Spring Discharged 4 9 c Breaker Closed and Closing Spring Discharged 4 9 b Breaker Open and Closing Spring Charged 4 9 d Breaker Closed and Closing Spring Charged Charging Schematic 1 Main Link Roll...

Page 19: ...he cell Maintenance usually means cleaning and lubricating the MOC mechanism If the MOC has seen a large number of cycles however worn components may have to be replaced To insure the proper operation...

Page 20: ...an audible click and the springs Charged Discharged Indicator shows Charged Remove the maintenance tool NOTICE IF THE SPRINGS ARE TO BE CHARGED ON A CLOSED BREAKER NO CLICK IS HEARD AT THE END OF CHAR...

Page 21: ...ndicator reads OPEN d Push the circuit breaker into the cell until the mechanical stop is reached this will be indicated by an audible click At this point the side plunger has fallen into the front sl...

Page 22: ...the breaker can be operated either electrically or mechanically Remove rotary racking handle before performing any testing b To further remove the breaker to the disconnect position continue turning...

Page 23: ...ted Withstand 1125V 60Hz For 1 Minute Hipot Tester Clean And Retest Or Replace 2 Power Element Vacuum Interrupters Contact Erosion Visibility Of Mark Visual Close The Breaker And Look For Green Mark O...

Page 24: ...ential test is recommended a DC test may be performed if only a DC test unit is available but is not recommended In this case the equipment must be capable of delivering 5 milliamperes for one minute...

Page 25: ...the primary circuit Open the breaker Connect the high potential lead of the test machine to one of the poles of the breaker Connect the remaining poles and breaker frame to ground Start the machine w...

Page 26: ...nergy available in terms of over travel in inches to close the breaker contacts to their full extent It may be used periodically to monitor the health of the mechanism General Information The CloSure...

Page 27: ...uit breaker then close it then reopen it Verify that the mark made in Step 7 is aligned with the pen opening If it is not aligned this indicates a problem with the circuit breaker stop the test and co...

Page 28: ...Sharpie 15o Left and Right Figure 6 13 Top view of Cam and Marker Interface Cam Marker CloSure Tool TM 15O 15O Figure 6 10 With Marker in Hole C While Closing Breaker Figure 6 8 Manually Charging Clo...

Page 29: ...cam shaft the main link and the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be dis...

Page 30: ...Cut Off Contacts Open Or Burned Trip Coil Assembly Clapper Fails To Reset Closing Sound But No Close Pole Shaft Not Open Fully Trip Latch Reset Spring Damaged Or Missing Trip Bar D Shaft Fail To Rema...

Page 31: ...Breaker Auxiliary Switch 94C9525G13 5 BREAKER POSITION SWITCH Breaker Position Switch PS1 94C9525H06 6 BREAKER POSITION SWITCH Breaker Position Switch PS2 94C9525H07 7 LATCH CHECK SWITCH Latch Check...

Page 32: ...levard Cleveland OH 44122 United States Eaton com 2013 Eaton All Rights Reserved Printed in USA Publication No IB182023EN March 2016 Eaton is a registered trademark All trademarks are property of thei...

Reviews: