![background image](http://html1.mh-extra.com/html/eaton/ab-de-ion/ab-de-ion_instruction-leaflet_3927463005.webp)
5
Instruction Leaflet
IL15560C
Effective August 2011
AB De-ion® Circuit Breaker
Type PB-DC (Mag. Only)
EATON CORPORATION
www.eaton.com
Before replacing cover make sure that 2 barriers G are in the line end
and one in the load end of each pole of the breaker. Replace cover and
fasten down with 8 cover screws H and I.
Install rear connectors J with 4 hex head screws in each connector as
shown. Tighten screws with a torque of 15 ft. Ibs. max.
To change trip units, throw breaker to the open position and remove
breaker cover by loosening the 8 cover screws H and I. Remove load
end rear studs J. Then loosen trip unit screws C and D. Lift trip unit out
of the breaker frame.
3
Poles In Series
+
LOAD
Use rated cable per N.E.C.,
connect to terminals, as per
breaker nameplate.