45
III.
Bridge the ‘AC input terminal mL1/mL2/mL3’ with ‘busbar #13’, then connect the
main source cable (L) to it
IV.
Bridge the ‘AC input terminal bL1/bL2/bL3’ with ‘busbar #12’, then connect the
bypass source cable (L) to it
2.
Output:
I. Connect the ground cable (PE) to the chassis
II. Bridge the
‘AC segment terminal N/N/N’ with ‘busbar #3’, then connect the AC
cable (N) to it
III. Bridge the
‘AC segment terminal L1/L2/L3’ with ‘busbar #3’, then connect the
AC cable (L) to it
3.
Connecting to UPS 1 and UPS 2:
I. Remove all busbars of the UPS
II.
Connect UPS 1 and UPS 2 to the MBP with ‘Cable to UPS 1’ and Cable to UPS
2’ included in the MBP’s accessory