28
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
33..66
B
Byyppaassss O
Ovveerrvviieew
w
The BPM has three operating positions (see
). Consider both the operating state of the UPS and the
BPM when protecting your critical loads.
Failure to understand the correct bypass sequence and position may cause the critical load to be dropped.
Damage to the power modules or the Bypass switch can occur.
•
If the UPS remains in Bypass Mode and incoming AC power is lost, the load is automatically dropped. The
UPS must be in Normal Mode to provide battery backup power.
•
In the UPS or LINE position, AC input power is still connected to the input terminals inside the UPS.
•
If the UPS is in the standby mode and the bypass switch is in the LINE or UPS positions pressing
the red bypass switch interlock button will energize the UPS output.
•
Do not attempt to push the red interlock button or attempt to move the bypass switch handle if the
UPS is operating on battery power.
•
If you have any questions or problems with the bypass operation, call the Help Desk (see , “
” ).
The BPM consists of a load position handle and a red button (see
).
Figure 26. Bypass Switch Positions
LOTO Bar (red)
Interlock Button (red)
Bypass switch
handle
The red button:
•
Sends an electrical signal to the UPS to switch to the Bypass Mode (if it is not already operating in that
mode ).
•
Operates a mechanical interlock, to prevent the switch from being turned without first signaling the UPS.
You must press the red button before you can turn the load position handle.
When the red button is pressed, the UPS front panel displays “Bypass Mode.” To move the MBP switch
handle from one position to another, the red button must be pressed WHILE the handle is being rotated.
Otherwise, the switch will be damaged.
The bypass switch has three positions as described in
.
Summary of Contents for 9PXM8S4K
Page 1: ...p n P 164000669 Revision 10 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Table of Contents...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 List of Tables...
Page 20: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Physical Features...
Page 98: ...86 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Display Menu Screens...
Page 104: ...92 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Communication Slots...
Page 120: ...P 16400066910 P 164000669 10...