background image

Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01

33

77..55

R

Reeccyycclliinngg TThhee U

Usseedd EEqquuiippm

meenntt

Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.

RISK OF ELECTRIC SHOCK

- Observe the warning associated with the risk of electric shock symbol.

This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This
product contains sealed, Lithium-Ion batteries and must be disposed of properly. For more information,
contact your local recycling/reuse or hazardous waste center.

This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.

Recycling The Used Equipment

Summary of Contents for 9PX6KIRTN-L

Page 1: ...p n DPD 9PX2205 Revision 01 9PX6KIRTN L 9PXEBM192RT2U L 9PX 6000 Li ion 9PX 6000 Li ion Advanced Users Guide Eaton 9PX 6KVA Lithium Ion ...

Page 2: ... can require the services of a person or organization skilled with respect to EMC aspects S Sp pe ec ciia all S Sy ym mb bo olls s The following are examples of symbols used on the product to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additiona...

Page 3: ... such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit P Pr ro od du uc ct t S Sa af fe et ty y To connect the UPS instructions and operation described in the manual must be followed in the indicated order CAUTION To reduce the risk of fire the unit connects only to a circui...

Page 4: ...rage temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety If there are any questions don t hesitate to contact your local EATON representative ...

Page 5: ... 4 Tower Installation 13 3 5 Rack Installation 14 3 6 Installation Requirements 16 3 7 Connecting the EBM s 17 3 8 Installation depending on the system earthing arrangement SEA 19 3 9 Power Cables Connection 19 3 10 Detecting Other Accessories 20 4 4 C Co om mm mu un niic ca at tiio on n 2 21 1 4 1 Communication Ports 21 4 2 UPS Remote Control Functions 22 5 5 O Op pe er ra at tiio on n 2 25 5 5 1...

Page 6: ... Equipment Care 29 7 2 Storing the Equipment 29 7 3 Replacing the Batteries 29 7 4 Battery Settings Reset 31 7 5 Recycling The Used Equipment 33 8 8 T Tr ro ou ub blle es sh ho oo ot tiin ng g 3 35 5 8 1 Typical Alarms and Faults 35 8 2 Silencing the Alarm 36 8 3 Service and Support 37 8 4 Compliance Contact 37 9 9 S Sp pe ec ciif fiic ca at tiio on ns s 3 39 9 9 1 Model Specifications EMEA 39 Tab...

Page 7: ... nt ta all P Pr ro ot te ec ct tiio on n EATON has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components The cardboard we use comprises over 50 of recycled cardboard Sacks and bags are...

Page 8: ...er quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Eaton 9PX you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Providing outstanding performance and reliability the Eaton 9PX s unique benefits ...

Page 9: ...ription Weights kg lb Dimensions mm inch D X W X H 9PX6KIRTN L 36 9 81 4 685 x 440 x 130 28 4 x 17 3 x 5 1 9PXEBM192RT2U L 35 8 78 9 645 x 438 x 85 5 25 3 x 17 2 x 3 3 2 2 2 2 A Ac cc ce es ss so or riie es s Table 3 UPS Accessories Part number Description 9PXEBM192RT2U L Extended Battery Module 9RK 4 post Rack Kit 9PX Network M2 Gigabit Network Card Network M3 Gigabit Network Card INDGW M2 Indust...

Page 10: ...n port Connector for ROO Remote On Off control Connector for communicating with an additional battery module Connector for RPO Remote Power Off control Slot for optional communication card Connector for additional battery module Group 1 4 10A programmable outlets for connection of critical equipment Input Output terminal blocks Connector for Hotswap MBP detection Group 2 4 10A programmable outlets...

Page 11: ...le Battery breaker 2 2 4 4 C Co on nt tr ro oll P Pa an ne ell The UPS has a five button graphical LCD It provides useful information about the UPS itself load status events measurements and settings Online mode indicator green Fault indicator red Online mode 100 30min 1EBM 50 2 7kW 3 0kVA Efficiency 95 Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange C...

Page 12: ...ad equipment status Online mode 100 30min 1EBM 50 2 7kW 3 0kVA Efficiency 95 Battery status Efficiency and load group information The following table describes the status information provided by the UPS Note If other indicator appears see the troubleshooting for additional information Table 4 LCD Operating Status Operation status Cause Description Standby mode The UPS is Off waiting for startup co...

Page 13: ...u options use the two middle buttons and to scroll through the menu structure Press the button to select an option Press the ESC button to cancel or return to the previous menu Table 5 Display Functions Main menu Submenu Display information or Menu function Measurements Load Input Bypass Output Efficiency Battery DC Bus Average Power Usage Cumulat Power Usage BMS Information Control Go to Bypass T...

Page 14: ...User Settings Submenu Available Settings Default settings Local Settings Language English Français Deutsch Español Русский Simplified Chinese Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time Date time Format International US International LCD Modify LCD screen brightness and contrast ...

Page 15: ...bled Disabled Authorize the product to restart automatically when mains recovers after a complete battery discharge Enabled Auto start Enabled Disabled The UPS automatically starts up as soon as mains power is available no need to press the button Disabled Energy Saving Disabled 100W 1000W If Enabled UPS will shutdown after 5 min of back up time if load is less than threshold Disabled Sleep mode E...

Page 16: ...10 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 User Settings ...

Page 17: ... Send a copy of the damage claim within 15 days to your service representative IMPORTANT Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representative 3 3 2 2 U Un np pa ac ck kiin ng g t th he e C Ca ab biin ne et t Unpacking the cabinet in a low temperature environment may cause co...

Page 18: ... C Ch he ec ck kiin ng g t th he e A Ac cc ce es ss so or ry y K Kiit t Verify that the following additional items are included with the UPS Figure 5 9PX6KIRTN L 2 Tower stands Rack kit for 19 inch enclosures optional Cable gland for Output connection additional cable gland for Input Network card communication card optional RS232 communication cable USB communication cable Safety instructions Quic...

Page 19: ... guide to install both the UPS and the EBM NOTE 3 If you ordered other UPS accessories refer to specific user manuals to check the packing contents 3 3 4 4 T To ow we er r I In ns st ta alllla at tiio on n Tip If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its final ...

Page 20: ... of the logo Adjustment of the angle of vision of the LCD panel 9PX6000Li ion 3 3 5 5 R Ra ac ck k I In ns st ta alllla at tiio on n NOTE It is recommended that the UPS internal battery pack be removed before attempting to install the UPS in a Rackmount configuration Follow Steps 1 6 on how to remove the battery pack from the UPS Rack Installation ...

Page 21: ...CD control panel to the UPS Do not pull on the cable or disconnect it 4 Remove the two screws that hold the metal protection cover in place 5 Carefully guide the BMS cable through the hole in the metal protection cover and remove 6 Pull out the handle of the battery pack and slide the pack out slowly on to a flat and stable surface Use two hands to support the battery pack I In ns st ta alllliin n...

Page 22: ... and install the screws for the front panel then clip the center cover The rails and necessary hardware are supplied by EATON 3 3 6 6 I In ns st ta alllla at tiio on n R Re eq qu uiir re em me en nt ts s Recommended protective devices and cable cross sections 1 Recommended upstream protection UPS Power Rating Upstream circuit breaker 6000VA D curve 32A Installation Requirements ...

Page 23: ... and firmly 1 Plug the EBM power cable s into the battery connector s Up to 4 EBMs may be connected to the UPS 2 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable 3 Connect the battery detection cable s to the connector of the UPS and of the EBM s NOTE The EBM communication wiring connections are directional and must be connected in the ...

Page 24: ...nection Battery Comm Battery Comm Battery Comm Battery Comm UPS EBM 1 EBM 2 EBM 3 EBM 4 EBM Communication Wiring ON OFF Figure 11 Tower EBM Connection ON OFF Battery Comm Battery Comm Battery Comm Battery Comm UPS EBM 1 EBM 2 EBM 3 EBM 4 EBM Communication Wiring Connecting the EBM s ...

Page 25: ...lle es s C Co on nn ne ec ct tiio on n A Ac cc ce es ss s t to o T Te er rm miin na all B Bllo oc ck ks s 1 Remove the terminal blocks cover one screw 2 Punch the knockouts and insert the cables conduits inside High leakage current Earth connection essential before connecting supply This type of connection must be carried out by qualified electrical personnel Before carrying out any connection che...

Page 26: ...t the Output cable through the cable gland Connect the three cables to the Output terminal blocks Put back and secure the terminal blocks cover with the screw Tighten the cable glands 1 2 3 4 5 6 3 3 1 10 0 D De et te ec ct tiin ng g O Ot th he er r A Ac cc ce es ss so or riie es s Tip If you ordered other UPS accessories refer to specific user manuals to check the connection to the UPS Detecting ...

Page 27: ...t the other end of the communication cable 16 or 17 to the RS232 1 or USB 2 communication port on the UPS The UPS can now communicate with EATON power management software 1 2 1 6 7 8 9 n c n o n c common n o n o n c n o n c 2 3 4 5 Status active information if contact between pin and common is closed Pin 1 not on bypass Pin 2 load not protected Pin 3 not low battery Pin 4 not on battery Pin 5 user...

Page 28: ...tting down the load and the UPS by thermal relay for instance in the event of room over temperature When RPO is activated the UPS shuts down the output and all its power converters immediately The UPS remains on to alarm the fault The RPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation The RPO...

Page 29: ... previously described procedures 6 Activate the external remote shut down contact to test the function Always test the RPO function before applying your critical load to avoid accidental load loss Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices The 9PX models have one available communication bay for the ...

Page 30: ...n card in the slot 3 Secure the card cover with the 2 screws Eaton Intelligent Power Software suite Eaton Intelligent Power Software suite is available from Eaton com Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives you a complete record of critical power events and it notifies you of important UPS or power information If there is a power ...

Page 31: ...the indicator is on do not proceed until all alarms are clear Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 7 Verify that the indicator illuminates solid indicating that the UPS is operating normally and any loads are powered and protected The UPS should be in Online mode NOTE The internal batteries charge to 90 capacity in less tha...

Page 32: ...1 Press the button on the front panel for three seconds A confirmation message will appear When confirmed the UPS starts to beep and shows a status of UPS shutting OFF The UPS then transfers to Standby mode 2 Set the upstream circuit breaker not provided to the O position Off to switch off the utility power UPS Shutdown ...

Page 33: ...of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available and your equipment is not protected however the utility power continues to be passively filtered by the UPS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for at least 5 seconds and will stay in this mode if three transfers to Bypass occur...

Page 34: ... Bypass Transfer out of tolerance 1 Press any button to activate the menu options then select Settings Output settings and Bypass transfer 2 Select Enabled or Disabled for BP AC NOK and Enter to confirm If Enabled the UPS transfers to Bypass even if Bypass AC source is out of tolerance depending on output mode If Disabled the UPS output is shutdown 6 6 8 8 C Co on nf fiig gu ur riin ng g B Ba at t...

Page 35: ...tteries were never recharged do not use them Contact your service representative 7 7 3 3 R Re ep plla ac ciin ng g t th he e B Ba at tt te er riie es s DO NOT DISCONNECT the batteries while the UPS is in Battery mode The internal battery is heavy Use caution when handling the heavy batteries Eaton Lithium ion UPS batteries have an expected life span of 8 years After 8 years of operation the UPS wi...

Page 36: ... eyes and may be extremely toxic Determine if the battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply ...

Page 37: ...the EBM s 1 Unplug the EBM power cable and battery detection cable from the UPS If additional EBM s are installed unplug the EBM power cable and battery detection cable from each EBM 2 Replace the EBM s See 7 5 Recycling The Used Equipment for proper disposal A small amount of arcing may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM cable into th...

Page 38: ...e Press the to advance the menu 2 7kW 3 0kVA 30min 1 EBM Efficiency 95 Reset battery life Yes No Are you sure Reset battery life Done Return the UPS to Normal Operation If the UPS internal batteries and external battery packs were replaced without powering down the UPS 1 Check the UPS front panel display for active alarms or notices Resolve any active alarms before continuing See section 8 1 Typic...

Page 39: ... the risk of electric shock symbol This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed Lithium Ion batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the tras...

Page 40: ...34 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Recycling The Used Equipment ...

Page 41: ...enu options 2 Press the button to select Event log or Fault log 3 Scroll through the listed events or faults The following table describes typical conditions Conditions Possible cause Action Battery mode LED is On 1 beep every 10 seconds A utility failure has occurred and the UPS is in battery mode The UPS is powering the equipment with battery power Prepare your equipment for shutdown Battery mod...

Page 42: ...ers to Bypass mode or shuts down if Bypass is unusable If the UPS transferred to Bypass mode the UPS will return to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflow around the UPS is not restricted Restart the UPS If the condition continues to persist ...

Page 43: ...al Authorization RMA number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units IMPORTANT For criti...

Page 44: ...38 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Compliance Contact ...

Page 45: ...2U L Rack Tower 192Vdc 6000VA Table 9 Weights and Dimensions Description Weights kg lb Dimensions mm inch D X W X H 9PX6KIRTN L 36 9 81 4 685 x 440 x 130 28 4 x 17 3 x 5 1 9PXEBM192RT2U L 35 8 78 9 645 x 438 x 85 5 25 3 x 17 2 x 3 3 Table 10 Electrical Input Model Default Input Voltage Max Current Input Nominal Voltages Input Voltage Window at Rated Load 9PX6KIRTN L 230V 25 2A 200V 208V 220V 230V ...

Page 46: ...102 no alarm 102 110 load transfers to Bypass mode after 2 minutes 110 125 load transfers to Bypass mode after 1 minute 125 150 load transfers to Bypass mode after 10s 150 load transfers to Bypass mode after 500ms Output Overload Bypass Mode 100 125 no alarm 125 150 UPS shuts down after 1 minute 150 UPS shuts down after 1s Voltage Waveform Sinewave Harmonic Distortion 2 THDV on linear load 5 THDV ...

Page 47: ...ratures 0 to 40 C 32 to 104 F in Online mode with linear derating for altitude Note thermal protection switches load to Bypass in case of overheating Storage Temperatures 0 to 40 C 32 to 104 F with batteries 15 to 60 C 5 to 140 F without batteries Transit Temperature 25 to 55 C 13 to 130 F Relative Humidity 0 to 95 no condensing Operating Altitude Up to 3 000 meters 9 843 ft above sea level with 1...

Page 48: ...e cycle monitoring EBM Battery Cable Length 350 mm 13 78 in Table 16 Communications Options Communication Bay 1 available independent communication bay for connectivity cards Communication Ports RS 232 DB9 1200 19200 bps USB 19200 bps Relay Output Contacts 4 relay outputs normally open or normally closed Remote On Off 2 pins jumper normally open Remote Power Off 3 pins jumper normally open or norm...

Page 49: ...Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 43 Model Specifications EMEA ...

Page 50: ...DPD 9PX220501 DPD 9PX2205 01 ...

Reviews: