figure 4-11 Interface Terminal detail (without transfer)
figure 4-12 Building alarm Terminal Block Connector assignments(without transfer)
Table 4-1 Building alarm Connections
Building alarm Terminal name
description
1
Building Alarm 1 +
Input: Programmable UPS alarm, activated by a remote dry contact closure.
2
Building Alarm 1 –
3
Building Alarm 2 +
Input: Programmable UPS alarm, activated by a remote dry contact closure.
4
Building Alarm 2 –
5
Building Alarm 3 +
Input: Programmable UPS alarm, activated by a remote dry contact closure.
6
Building Alarm 3 –
Building Alarm 1
Building Alarm 3
Building Alarm 2
Mini-Slot
Communication Bay 1
Mini-Slot
Communication Bay 2
Building Alarm
(See Figure 4-12 for Detail)
REPO Terminals
(See Figure 4-16 for Detail)
Parallel CAN Output (RJ45)
Pull chain Terminals
Parallel CAN Input (RJ45)
Eaton 9EHD UPS (20-40 kVA, 380/400/415V) Installation and Operation Manual