Type
Article No
Nominal battery
voltage
12V VRLA
Blocks
With 93PS
30–40 kW
NZM1–A160
281234
(P-122000199)
336–432 V
28–36
NZMN2-A160
259092
444–480 V
37–40
NOTE: Maximum string length for the 93PS C-model is 36 blocks, 216 cells (432 V)
Note: Contact your Eaton sales representative for more information about the
circuit breakers, or if you need help choosing the right model for your UPS
system.
Use the following 24 V shunt release with early-make auxiliary contact together
with the above circuit breakers:
Type
Article No
NZM1-XAHIVL24AC/DC
259792
(P-152001062)
Note: In 93PS UPS C-model, the internal and external circuit breakers
function in cooperation with each other.
Table 10: Rated and maximum currents for rated power and voltage
Rectifier input
UPS output / bypass
Battery
Rated
power
[kW]
Rated
voltage
[V]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
8
380
13
15
12
18
22
26
400
12
14
12
17
22
26
415
12
14
11
16
22
26
10
380
16
19
15
22
27
33
400
15
18
15
21
27
33
415
15
17
14
20
27
33
15
380
24
28
23
34
41
49
400
23
27
22
32
41
49
415
22
26
21
31
41
49
20
380
32
37
31
45
55
66
400
30
36
29
42
55
66
415
29
34
28
41
55
66
Eaton 93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved.
Revision: 003
Document ID: P-164000493