
20 kW
frame
20 kW C-model
frame
40 kW
frame
Floor loading
1,007 kg/m
2
310 kg/m
2
1,478 kg/m
2
Note: Maximum number of internal batteries are included with all the models (except the
C-model, which has no internal batteries).
The UPS cabinets use forced air cooling to regulate internal component
temperature. By default, air inlets are in the front of the cabinet and outlets are
in the back. Allow clearance in front of and behind each cabinet for proper air
circulation.
The clearance required around the UPS cabinet is shown in Table
6
.
Note: This equipment is not intended for building-in, rack-mounting or for
incorporation in larger equipment.
Table 6: UPS cabinet minimum clearances
20 kW frame*
40 kW frame
From the top of the cabinet
500 mm
500 mm
From the front of the cabinet
500 mm
650 mm
From the back of the cabinet
150 mm
250 mm
From the side of the cabinet
0 mm
0 mm
* Applies to the 93PS 20 kW C-model frame as well.
Eaton 93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved.
Revision: 003
Document ID: P-164000493
36 (104)