Installation Plan and Unpacking
Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2
www.eaton.com/powerquality
3-11
Table 3-5. External Output Power Cable Terminations for the Eaton 93E 30IAC-D and 60IAC-D
Terminal Function
Breaker Rating
Terminal
Function
Number and Size of
Pressure Termination
(AWG or kcmi)
Tightening Torque
Nm (lb in)
Type and Size
Screw
AC Output from Distribution
Panel Breakers to Critical Load
N/A
N
Neutral
64 – #6–#14
#6–#8:
#10–#14:
2.8 (25)
1.7 (15)
Slotted
22 – 1/0
#4–#6:
#8:
#10–#14:
5.0 (45)
4.5 (40)
4.0 (35)
N/A
G
Ground
32 – #6–#14
#6–#8:
#10–#14:
2.8 (25)
1.7 (15)
Slotted
11 – 1/0
#4–#6:
#8:
#10–#14:
5.0 (45)
4.5 (40)
4.0 (35)
AC Output from Subfeed
Breakers to Critical Load
“EG” Frame
A
Phase A
1 – #14–1/0
31
(275)
5/16” Hex
B
Phase B
1 – #14–1/0
31
(275)
5/16” Hex
C
Phase C
1 – #14–1/0
31
(275)
5/16” Hex
N
Neutral
64 – #6–#14
#6–#8:
#10–#14:
2.8 (25)
1.7 (15)
Slotted
22 – 1/0
#4–#6:
#8:
#10–#14:
5.0 (45)
4.5 (40)
4.0 (35)
G
Ground
4 – 1/0–#14
5.6 (50)
Slotted
AC Output from Subfeed
Breakers to Critical Load
“JG” Frame
A
Phase A
1 – #4–350
31
(275)
5/16” Hex
B
Phase B
1 – #4–350
31
(275)
5/16” Hex
C
Phase C
1 – #4–350
31
(275)
5/16” Hex
N
Neutral
64 – #6–#14
#6–#8:
#10–#14:
2.8 (25)
1.7 (15)
Slotted
22 – 1/0
#4–#6:
#8:
#10–#14:
5.0 (45)
4.5 (40)
4.0 (35)
G
Ground
4 – 1/0–#14
5.6 (50)
Slotted
NOTE
Wire branch circuits in accordance with branch circuit breaker manufacturer's ratings and instructions and national and local electrical codes (output is
prewired to the panelboard).