50
Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
44..33..22
EElleeccttrriiccaallllyy C
Coonnnneeccttiinngg tthhee U
UP
PS
S S
Seeccttiioonnss
1.
Remove the I/O bottom entry conduit plate and retain the hardware for later use (see
Figure 22. Section Bottom Entry Landing Conduit Plate
Bottom Entry Conduit
Landing Plate
I/O Section
Ground
NOTE
AC and DC input inter-cabinet power wiring harnesses are secured in the ISBM/PM to
brackets for shipping in the left side of the ISBM section. The shipping brackets can be
removed and discarded after releasing the power wiring.
2.
Disconnect the power wiring harnesses from the ISBM shipping brackets (see
Summary of Contents for 9395XC
Page 8: ......
Page 160: ...16400107901 164001079 01 ...