UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
3-14
Table 3‐4. Input/Output Ratings and External Wiring Requirements for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825
– Common Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
592
650
592
750
683
750
683
825
751
825
751
Input and Output Voltage
Volts
400/400
480/480
400/400
480/480
400/400
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1079
891
1245
1028
1369
1130
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(3)
500
(4)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(5)
500
(4)
500
(5)
500
(5)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
C
Total Amps
1280
1280
1502
1502
1600
1600
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
350
(6)
350
(6)
500
(6)
500
(6)
500
(6)
500
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(5)
500
(4)
500
(5)
500
(5)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
–
AWG or kcmil
(each)
4/0
(1
4/0
(1)
4/0
(1
4/0
(1)
4/0
(1
4/0
(1)
NOTE
Callout letters
A
,
B
,
C
, and
D
map to Figure 6‐5 , Figure 6‐7, Figure 6‐9, Figure 6‐11, or Figure 6‐15. Callout letters
A
,
C
, and
D
map to
Figure 6‐17 or Figure 6‐19.
NOTE
Bypass wiring data is not applicable to IOM configurations.