UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
3-3
The basic environmental requirements for operation of the UPS are:
S
Ambient Temperature Range:
0–40°C (32–104°F)
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
95%, noncondensing
C
A
U
T
I
O
N
If battery systems are located in the same room as the UPS, the battery manufacturer's environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3‐3.
Table 3‐3. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
BTU/hr
1000 (kg-cal/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395-825/450
450 kVA (CSS)
400/400
87 (21886)
Approximately 1510 liter/sec (3200 cfm)
With Field Installed UPM
Approximately 2265 liter/sec (4800 cfm)
480/480
88 (22107)
Eaton 9395-825/500
500 kVA (CSS)
400/400
96 (24318)
480/480
97 (24563)
Eaton 9395-825/550
550 kVA (CSS)
400/400
106 (26749)
480/480
107 (27020)
Eaton 9395-825/650
650 kVA (MSS)
400/400
125 (31613)
Approximately 2265 liter/sec (4800 cfm)
With Field Installed UPM:
Approximately 3020 liter/sec (6400 cfm)
480/480
127 (31933)
Eaton 9395-825/750
750 kVA (MSS)
400/400
145 (36476)
480/480
146 (36845)
Eaton 9395-825/825
825 kVA (MSS)
400/400
159 (40124)
480/480
161 (40530)
Eaton 9395-825/650
650 kVA (CSS)
400/400
125 (31613)
Approximately 2265 liter/sec (4800 cfm)
With Field Installed UPM:
Approximately 3020 liter/sec (6400 cfm)
480/480
127 (31933)
Eaton 9395-825/750
750 kVA (CSS)
400/400
145 (36476)
480/480
146 (36845)
Eaton 9395-825/825
825 kVA (CSS)
400/400
159 (40124)
480/480
161 (40530)
Eaton 9395-825/650
650 kVA (IOM)
400/400
125 (31613)
Approximately 2265 liter/sec (4800 cfm)
With Field Installed UPM:
Approximately 3020 liter/sec (6400 cfm)
480/480
127 (31933)
Eaton 9395-825/750
750 kVA (IOM)
400/400
145 (36476)
480/480
146 (36845)
Eaton 9395-825/825
825 kVA (IOM)
400/400
159 (40124)
480/480
161 (40530)
NOTE
MSS = Momentary Static Switch; CSS = Continuous Static Switch; IOM = Input Output Module