Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
Table 4. Eaton 9355 10–15 kVA Parallel UPS: Recommended Terminal Block Wiring
Model
Voltage
Wire
Function
Feeder
Circuit
Breaker
Rating
L1, L2, L3,
N Wire
Size
1
Ground
Wire
Size
1
Tighten-
ing
Torque
Conduit Size
2, 3
(Number of
Conduits)
Eaton 9355 10
kVA
UPS System
208
Input
UPS
Module,
TB1
WYE / 4-
Wire
45A
6 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
220
45A
8 AWG
208
Output
UPS
Module,
TB1
WYE / 4-
Wire
6 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
220
Eaton 9355 15
kVA
UPS System
208
Input
UPS
Module,
TB1
WYE / 4-
Wire
60A
4 AWG
10 AWG
120 lb in
(13.5 Nm)
1.25" conduit
(1)
220
208
Output
UPS
Module,
TB1
WYE / 4-
Wire
6 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
220
1
Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to National Electrical Code
(NEC) Table 310-104(A). Code may require a larger AWG size than shown in this table because of temperature, number of
conductors in the conduit, or long service runs. Follow local requirements.
2
Per NEC article 300 20(a) for Ferrous Metal Raceways, all three-phase conductors must be run in the same conduit. Neutral and
ground must be run in the same conduit as the phase conductors.
3
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG ground conductor.
If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the conduit needed to
accommodate the extra wire or size and use that conduit size in place of the conduit size listed. Conduit sizes were chosen from
NEC Table C1, type letters RHH, RHW, RHW 2, TW, THW, THHW, THW 2.
33..44
IInnssppeeccttiinngg tthhee EEqquuiippm
meenntt
If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier or
place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for
concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the
equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
NOTE
Check the battery recharge date on the packaging label. If the date has expired and the
batteries were never recharged, do not use the UPS. Contact your service
representative.
Summary of Contents for 9355 Series
Page 1: ...p n 164201601 Revision E0 10 15 kVA User s Guide Eaton 9355 Parallel UPS ...
Page 4: ......
Page 10: ...x Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 List of Tables ...
Page 18: ...8 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Safety Warnings ...
Page 54: ...44 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 UPS System Installation ...
Page 68: ...58 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Operation ...
Page 72: ...164201601E0 164201601 E0 ...