Seismic Data Requirements for Eaton UPS Equipment Installation User’s Guide 164000050—Rev 05
29
Table 10. 93PM Unit and Fastener Requirements from Unit to Floor (Continued)
Model
Voltage
Type
Bolt Type and Size
Torque
Quantity
Both
93PM
(480V)
and
93PM-L
(208V)
IAC-D (208V and 480V)
Class 8.8, M12 or
Grade 5, 1/2”
87 Nm
64 lb-ft.
8
IAC-PD (208V and 480V)
8
IBC-S
8
IBC-L, IBC-LH
8
IBC-L, IBC-LH with Left or Right-Mounted Sidecar
12
IBC-LW, IBC-LHW
12
NOTE
The torque value for each bracket-to-cabinet connecting bolt is listed below:
Class 8.8,
M8
Bolt = 27 Nm [20 lb-ft.]
Class 8.8,
M10
Bolt = 42 Nm [31 lb-ft.]
Class 8.8,
M12
Bolt = 87 Nm [64 lb-ft.]
55..11
D
Diissppllaacceem
meenntt
The horizontal displacement of the top of the equipment is listed in
. The horizontal displacements
given in the table are plus/minus values. The equipment must be at the minimum distance listed in the table to
avoid contact with other stationary objects during a seismic event.
Table 11. 93PM Unit Seismic Displacement Requirements
Model
Voltage
Type
Front to Back
Side to Side
93PM
480 Vac
UPS 50 kW, 100 kW, and 150 kW Frames
130 mm
180 mm
UPS 50 kW, 100 kW, and 150 kW Frames with
Small Left or Right-Mounted Sidecar
120 mm
140 mm
UPS 100 kW and 150 kW Frames with
Large Left or Right-Mounted Sidecar
120 mm
140 mm
UPS 200 kW Frame
130 mm
180 mm
UPS 200 kW Frame with
Left or Right-Mounted Sidecar
130 mm
180 mm
UPS 400 kW Frame
94 mm
112 mm
IAC-B (400 kW)
130 mm
180 mm
IAC-BD
100 mm
100 mm
IAC-T (480V)
100 mm
100 mm
93PM-L
208 Vac
UPS 60 kW and 120 kW
130 mm
180 mm
UPS 60 kW with Left or Right-Mounted Top Entry Sidecar
120 mm
140 mm
UPS 60 kW with
MBS Left or Right-Mounted Sidecar or
UPS 120 kW with
Top Entry/MBS Left or Right-Mounted Sidecar
120 mm
140 mm
Eaton 93PM (480V) and 93PM-L (208V) Foundation Plan and Mounting Requirements
Summary of Contents for 9 55 Series
Page 62: ...16400005005 164000050 05...