Seismic Data Requirements for Eaton UPS Equipment Installation User’s Guide 164000050—Rev 05
Table 12. 93PM Unit Center of Gravity Specifications (Continued)
Model
Voltage
Type
X (left to right)
Y (front to rear)
Z (bottom to
top)
Both 93PM (480V)
and 93PM-L
(208V)
IBC-L, IBC-LH (480V) with Left-Mounted Sidecar
602 mm
600 mm
1046 mm
IBC-L, IBC-LH (480V) with Right-Mounted Sidecar
421 mm
600 mm
1046 mm
IBC-LW, IBC-LHW (432V)
456 mm
506 mm
1036 mm
IBC-LW, IBC-LHW (480V)
434 mm
507 mm
981 mm
55..33
P
Poow
weerr C
Caabblleess
It is recommended that power cables be lashed together at least every meter within the equipment. Refer to
the appropriate Eaton UPS instruction and operation manual for other requirements related to securing power
cables.
55..44
9933P
PM
M FFlloooorr P
Pllaann S
Seeccuurriinngg D
Diim
meennssiioonnss
through
detail the measurements for attaching the seismic brackets to the floor of the
building. The drawings are for reference only and are not to scale. Dimension are in millimeters (inches).
Eaton 93PM (480V) and 93PM-L (208V) Foundation Plan and Mounting Requirements