Seismic Data Requirements for Eaton UPS Equipment Installation User’s Guide 164000050—Rev 05
Table 11. 93PM Unit Seismic Displacement Requirements (Continued)
Model
Voltage
Type
Front to Back
Side to Side
93PM-L
208 Vac
UPS 160 kW
120 mm
140 mm
UPS 200 kW
100 mm
100 mm
IAC-B
100 mm
100 mm
Both 93PM
(480V)
and 93PM-L
(208V)
IAC-D (208V and 480V)
100 mm
100 mm
IAC-PD (208V and 480V)
100 mm
100 mm
IBC-S
100 mm
160 mm
IBC-L, IBC-LH
100 mm
160 mm
IBC-L, IBC-LH with Left or Right-Mounted Sidecar
90 mm
100 mm
IBC-LW, IBC-LHW
94 mm
122 mm
Consideration must be given to attachments (conduits, bus duct, etc.) made to the top of the equipment.
Attachments must have provisions to accommodate the displacement of the equipment indicated in
Entry from the bottom of the equipment eliminates the need for accommodating this motion for attachments.
55..22
C
Ceenntteerr ooff G
Grraavviittyy
For seismic calculations, the center of gravity can be approximated using the dimensions in
with
respect to the left side bracket's front mounting hole (x,y,z origin). Battery cabinet center of gravity dimensions
are with batteries installed.
Table 12. 93PM Unit Center of Gravity Specifications
Model
Voltage
Type
X (left to right)
Y (front to rear)
Z (bottom to
top)
93PM
480 Vac
UPS 50 kW Frame (480V)
538 mm
278 mm
887 mm
UPS 50 kW Frame with Left or Right-Mounted
Sidecar
Top Entry Wiring / MBS Sidecar
452 mm
540 mm
884 mm
UPS 100 kW Frame
537 mm
276 mm
921 mm
UPS 100 kW Frame with Left-Mounted Sidecar
Top Entry Wiring Sidecar
427 mm
541 mm
917 mm
UPS 100 kW Frame with Right-Mounted Sidecar
Top Entry Wiring Sidecar
564 mm
356 mm
917 mm
UPS 100 kW Frame with Large Left-Mounted
Sidecar
552 mm
543 mm
922 mm
UPS 100 kW Frame with Large Right-Mounted
Sidecar
552 mm
386 mm
922 mm
UPS 150 kW Frame
530 mm
282 mm
1014 mm
UPS 150 kW Frame with Top Entry Left-Mounted
Sidecar
534 mm
434 mm
979 mm
Eaton 93PM (480V) and 93PM-L (208V) Foundation Plan and Mounting Requirements