Automatic Standby Generator Owner’s Manual

1.1 — General Safety

Study these safety rules carefully before operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The 
generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing 
to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and 
decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not 
specifically recommend, ensure that it is safe for personnel. Also make sure the procedure, work method or operating technique utilized does not 
render the generator unsafe.

Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or 
being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate 
and maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure steps are taken to make the machine safe 
before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near a running generator.

The installation of this generator must always comply with applicable codes, standards, laws and regulations.

A running generator gives off DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing carbon 
monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness, 
sleepiness, inability to think clearly, fainting, unconsciousness or even death.

The control panel for this unit is intended to be operated by qualified service personnel only.

1.2 — General Safety Hazards

• For safety reasons, this equipment should only

 

be installed, serviced and repaired by a Service Dealer or other competent, qualified electri-

cian or installation technician who is familiar with applicable codes, standards, regulations and product Installation Manual guidelines. The 
operator also must comply with all such codes, standards, regulations and product Installation Manual guidelines.

• The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can 

cause unconsciousness or even death. DO NOT alter or add to the exhaust system or do anything that might render the system unsafe or in 
noncompliance with applicable codes and standards.

• Install a carbon monoxide alarm indoors, according to manufacturer’s instructions/recommendations.
• Adequate, unobstructed flow of cooling and ventilating air is critical for correct generator operation. Do not alter the installation or permit even 

partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be installed and 
operated outdoors only.

• Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the 

unit is operating.

• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.
• Before performing any maintenance on the generator, remove the control panel fuse and disconnect the Negative (—) battery cable to pre-

vent accidental startup. When disconnecting battery cables always remove the NEGATIVE (NEG or “—”) cable first, then remove the 
POSITVE (POS, or “+”) cable. When reconnecting the cables, connect the POSITIVE cable first, and the NEGATIVE cable last.

• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating 

conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.

*
+

*

*

*

*

Summary of Contents for 8 kW Air-cooled

Page 1: ...the unit Eaton Generator Support 1 800 975 8331 n NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS n ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION n DEADLY EXHAUST F...

Page 2: ...re that all maintenance for safe operation is performed promptly and to have the equipment checked periodically by an Authorized Service Dealer Normal maintenance service and replace ment of parts are...

Page 3: ...ransfer Operation 14 3 5 Turning the Generator Off When Operating Under Load 15 3 6 Manual Transfer Operation 15 3 7 Side Compartment 16 3 8 Alarm Response Procedures 17 3 9 Battery Charger 17 3 10 Se...

Page 4: ...iii This page intentionally left blank...

Page 5: ...t Authorized Service Dealer for starting operating and servicing procedures SAVE THESE INSTRUCTIONS The manufacturer suggests that this manual and the rules for safe operation be copied and posted nea...

Page 6: ...ards For safety reasons this equipment should only be installed serviced and repaired by a Service Dealer or other competent qualified electri cian or installation technician who is familiar with appl...

Page 7: ...tor AVOID DIRECT CONTACT WITH THE VICTIM Use a nonconducting implement such as a dry rope or board to free the victim from the live conductor If the victim is unconscious apply first aid and get immed...

Page 8: ...e to install a transfer switch The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is operating NEC 702 Failure to isolate an ele...

Page 9: ...UIT BREAKERS FUEL INLET BACK CONTROL PANEL OIL DIPSTICK AIR FILTER DATA LABEL SEE SAMPLE EXHAUST ENCLOSURE COMPOSITE BASE OIL FILTER OIL FILL CAP BATTERY COMPARTMENT FUEL REGULATOR CIRCUIT BREAKERS FU...

Page 10: ...s follows The control panel contains a display which alerts the operator when a fault condition occurs The above list is not all inclusive For more informa tion about alarms and control panel operatio...

Page 11: ...able emission standards for the duration of the engine s life it is important to follow the maintenance specifications in the Section 4 Maintenance This generator is certified to operate on Liquid Pro...

Page 12: ...lies and CSA C22 2 No 100 04 Standard for Motors and Generators Natural Gas ratings will depend on specific fuel Btu joules content Typical derates are between 10 20 off the LP gas rating Circuits to...

Page 13: ...ted into the control panel module in all models It operates as a Smart Charger which ensures output charging lev els are safe and continuously optimized to promote maximum battery life 2 4 6 Engine Oi...

Page 14: ...10 Automatic Standby Generator Owner s Manual This page intentionally left blank...

Page 15: ...ks are securely locked See Figure 3 1 The enclosed keys provided with this unit are for service personnel usage only Figure 3 1 Generator With Lid Open Side Lock Location Set to AUTO the engine may cr...

Page 16: ...crank and start the generator Transfer to standby power will not occur unless there is a utility failure Feature Description HOME page The default page which will be displayed if no buttons are presse...

Page 17: ...ut of updating During update process the Blue Manual light flashes then the Green Auto light flashes Sequence does this twice When update is complete the unit returns to Install Wizard menu When the c...

Page 18: ...e utility source 3 4 1 2 Cranking The system will control the cyclic cranking as follows 8kW unit 5 cranking cycles as follows 15 second crank seven 7 second rest followed by four 4 additional cycles...

Page 19: ...have been completely turned off Failure to turn off all power voltage supplies may result in extremely hazardous and possi bly fatal electrical shock Prior to automatic operation manually exercise the...

Page 20: ...to the transfer switch using the means provided 7 Press the Control Panel AUTO button 3 7 Side Compartment Local codes may require this compartment to be locked A hasp is provided so the owner operato...

Page 21: ...r and correct Warning and Alarm conditions contact the nearest Authorized dealer or Trained Technician 3 9 Battery Charger NOTE The battery charger is integrated into the control module in all models...

Page 22: ...18 Automatic Standby Generator Owner s Manual This page intentionally left blank...

Page 23: ...hedule A maintenance consists of the oil oil filter and tune up Schedule B maintenance includes the oil oil filter tune up air cleaner spark plug s and valve clearance 4 2 Service Schedule ATTENTION A...

Page 24: ...unning in the residence using the electrical panel s main disconnect Then turn the generator s Main Circuit Breaker to the OFF position 2 Press the Control Panel OFF button Wait 5 minutes 3 Remove the...

Page 25: ...r 1 Start the engine by pressing the MANUAL button on the control panel and allow the engine to run until it is thoroughly warmed up Then press the Control Panel OFF button to shut down the engine 2 A...

Page 26: ...e the wire clip 8kW 4 5 Spark Plugs Reset the spark plug s gap or replace the spark plug s as necessary 1 With the generator shut down lift the lid and remove the front panel 2 Clean the area around t...

Page 27: ...4 4 Make sure the engine is at 60 to 80 F 16 to 27 C Make sure that the spark plug wire is removed from the spark plug and out of the way Remove the four screws attaching the valve cover Loosen the r...

Page 28: ...the Dealer or a qualified Service Technician check the state of charge and condition Do not dispose of the battery by incineration The battery is capable of exploding A battery presents a risk of ele...

Page 29: ...tention After Submersion If the generator has been submerged in water it MUST NOT be started and operated Following any submersion in water have a Dealer thor oughly clean dry and inspect the generato...

Page 30: ...replace the battery 4 Clean and wipe down the entire generator 5 Make sure the 7 5 Amp fuse is removed from the generator Control Panel 6 Reconnect the battery Observe battery polarity Damage may occ...

Page 31: ...l pressure incorrect 4 Confirm fuel pressure to regulator is 10 12 water column 19 22mm mercury for LP and 5 7 water column 9 13mm mercury for natural gas 5 Fuel selector in wrong position 5 Move sele...

Page 32: ...28 Automatic Standby Generator Owner s Manual This page intentionally left blank...

Page 33: ...ill not start in AUTO with utility loss RED Check the LEDs Screen for alarms LOW OIL PRESSURE Check oil level Add oil per Owner s Manual Contact servicing dealer if oil level is correct Unit will not...

Page 34: ...icing dealer if battery is GOOD Replace battery If CHECK BATTERY is displayed Yellow LED illuminated in any state YELLOW Check screen for additional information BATTERY PROBLEM Contact servicing deale...

Page 35: ......

Page 36: ...c All rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45...