Automatic Standby Generator Owner’s Manual
29
Section 6
Quick Reference Guide
Problem
LED
Things to
Check
Active Alarm
Solution
Unit running in AUTO but no power
in house.
GREEN
Check MLCB.
NONE
Check MLCB. Contact servicing dealer if
MLCB is in the ON position.
Unit shuts down during operation.
RED
Check the
LEDs/Screen
for alarms.
HIGH
TEMPERATURE
Check ventilation around the intake,
exhaust and rear of generator. Contact
serving dealer if no obstruction is found.
Unit shuts down during operation.
RED
Check the
LEDs/Screen
for alarms.
OVERLOAD
REMOVE LOAD
Clear alarm and remove household
loads from the generator. Put back in
AUTO and restart.
Unit was running and shuts down,
attempts to restart.
RED
Check the
LEDs/Screen
for alarms.
RPM SENSE
LOSS
Clear alarm and remove household
loads from the generator. Put back in
AUTO and restart. If problem returns,
contact servicing dealer to investigate
possible fuel issue.
Unit will not start in AUTO with utility
loss.
NONE
See if screen
says unit not
activated.
NOT
ACTIVATED
Refer to activation section in Owner’s
Manual.
Unit will not start in AUTO with utility
loss.
GREEN
Check screen
for start delay
countdown.
None
If the start up delay is greater than
expected, contact servicing dealer to
adjust from 2 to 1500 seconds.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
LOW OIL
PRESSURE
Check oil level. Add oil per Owner’s
Manual. Contact servicing dealer if oil
level is correct.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
RPM SENSE
LOSS
Clear alarm. From the MAIN menu on
the control panel, navigate to the BAT-
TERY MENU. Contact servicing dealer if
battery is GOOD. Replace battery If
CHECK BATTERY is displayed.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
OVERCRANK
Check fuel line shutoff valve is in the ON
position. Clear alarm. Attempt to start
the unit in MANUAL. If it does not start
or starts and runs rough, contact servic-
ing dealer.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
LOW VOLTS
REMOVE LOAD
Clear alarm and remove household
loads from the generator. Put back in
AUTO and restart.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
FUSE PROBLEM
Check ATO 7.5 amp fuse. Replace with
same type fuse if bad. Contact servicing
dealer if fuse is good.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
OVERSPEED
Contact servicing dealer.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
UNDER
VOLTAGE
Contact servicing dealer.
Unit will not start in AUTO with utility
loss.
RED
Check the
LEDs/Screen
for alarms.
UNDERSPEED
Contact servicing dealer.
Summary of Contents for 8 kW Air-cooled
Page 4: ...iii This page intentionally left blank...
Page 14: ...10 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 22: ...18 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 32: ...28 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 35: ......