3. Installation
3.5 Connection with a FlexPDU (Power Distribution Unit) module
(optional)
5PX
FlexPDU
43
47
48
49
50
1.
5PX 2200i / 3000i
: connect
the UPS input socket
(10)
to
the AC-power source using
the cable
(31)
supplied.
5PX 1500i / 2000i
: use the power
cable of the protected equipment.
2.
5PX 2200i / 3000i
: connect the
input socket on the
FlexPDU
module
(50)
to the UPS outlet
(7)
using the cable
(43)
supplied.
5PX 1500i / 2000i
: connect the
input socket on the
FlexPDU
module (50)
to one of the
outlets
(9)
.
The cable and the connectors
are marked in red.
3.
Connect the equipment to the
outlets
(47)
,
(48)
and
(49)
on the
FlexPDU module
. These outlets
differ, depending on the version
of the
FlexPDU module
.
4.
Fit the connection securing
system that prevents the plugs
from being pulled out
accidentally.
3.6 Connection with a HotSwap MBP module
(optional)
The
HotSwap
MBP
module makes it possible to service or even replace the UPS without affecting the connected
loads (
HotSwap
function).
5PX
HotSwap MBP
46
51
52
55
54
53
56
57
58
1.
Connect the input socket
(58)
on
the
HotSwap MBP
module to the
AC-power source using the cable
(31)
supplied.
2.
Connect the UPS input socket
(10)
to the “UPS Input”
(57)
on the
HotSwap MBP
module, using the
cable
(46)
supplied. These cables
and the connectors are marked
blue.
3.
Connect the UPS outlet
(7)
to
the “UPS Output”
(56)
on the
HotSwap MBP module, using the
cable
(46)
supplied.
5PX 1500i
: connect one of the UPS
outlets
(9)
to the “UPS Output”
(56)
on the
HotSwap MBP
module.
These cables and the connectors
are marked in red.
4.
Connect the equipment to the out-
lets
(51)
and
(52)
on the
HotSwap
MBP
module. These outlets differ,
depending on the version of the
HotSwap MBP
module.
Caution. Do not use UPS outlets
(8) and (9) to supply equipment
because use of switch (55) on the
HotSwap MBP module would cut
supply to the equipment.