Page 10
2. Presentation
2.5 Display Functions
Press the Enter (
) button to activate the menu options. Use the two middle buttons ( and ) to scroll
through the menu structure. Press the Enter (
) button to select an option. Press the
button to cancel
or return to the previous menu.
Menu map for Display Functions.
Main Menu
Submenu
Display Information or Menu Function
/
z
H
V
t
u
p
n
I
/
z
H
V
t
u
p
t
u
O
/
f
p
A
d
a
o
L
/
A
V
W
d
a
o
L
s
t
n
e
m
e
r
u
s
a
e
M
Battery V min / Efficiency / Power usage
Control
Load Segments
Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test
Starts a manual battery test
Reset fault state
Clears active faults (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage
Clears power usage measurements
Settings
Local settings
Sets product general parameters
Input / output settings
Sets Input and output parameters
ON / OFF settings
Sets ON / OFF conditions
Battery settings
Sets battery configuration
s
m
r
a
l
a
r
o
g
o
l
t
n
e
v
e
s
y
a
l
p
s
i
D
g
o
l
t
l
u
a
F
/
e
s
a
e
l
e
r
e
r
a
w
m
r
i
F
/
r
e
b
m
u
N
l
a
i
r
e
S
/
r
e
b
m
u
N
t
r
a
P
/
e
p
y
T
S
P
U
n
o
i
t
a
c
i
f
i
t
n
e
d
I
Com card address
2.6 User Settings
The following table displays the options that can be changed by the user.
s
g
n
it
t
e
S
t
l
u
a
f
e
D
s
g
n
it
t
e
S
e
l
b
a
li
a
v
A
n
o
it
p
i
r
c
s
e
D
Local Settings
Language
[English] [Français] [Deutsch]
[Italiano] [Português] [Español]
[
Русский
]
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
languages.
English
User selectable when UPS is
powered for the first time.
LCD settings
Modify LCD screen brightness and
contrast to adapt to room light
conditions.
Audible alarm
[Enabled] [Disabled on battery]
[Always disabled]
Enable or disable the buzzer if an
alarm occurs.
Enabled
In/Out Settings
Output voltage
[100 V] [120 V] [125V]
User selectable when UPS is
powered for the first time.
Input thresholds
[Normal mode] [Extended mode]
Extended mode reduces lower input
voltage to 70V before UPS transfers
to battery.
This can be used if the load can
withstand low input voltage.
Normal mode
Sensitivity
[High] [Low]
High
Load segments -
Auto start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected load is powered after
the specified delay.
Group 1: 3 s
Group 2: 6 s
High: for sensitive equipment, UPS
will transfer to battery when utility
input conditions are varying signifi-
cantly.
Low: for equipment that can
withstand some variation in utility
conditions, the UPS will transfer to
battery when utility input becomes
poor.