background image

27

Instructional Leaflet 

IL70C1037H05

Effective October 2009

Digitrip models 520, 520i; and 520M, 520Mi,

520MC, 520MCi trip units for use only in

Magnum and Magnum DS circuit breakers

eaton corporation

 www.eaton.com

m

 CAUTION

BEFORE PLUGGING A TEST KIT INTO THE TEST PORT, PLACE THE LTM 

JUMPER IN THE INACTIVE POSITION (SEE FIGURE 30). AFTER TESTING, 

RETURN THE LTM JUMPER TO ITS ORIGINAL POSITION.

The test kit authorized by Eaton for use with the Digitrip units plugs 

into the test port of the unit and provides a secondary injection test 

that simulates the current transformer. Existing test kits, styles 

140D481G02R, 140D481G02RR, 140D481G03 or G04, along with 

the Magnum test kit adapter 8779C02G04, can be used to test the 

trip unit and breaker.

Functional test kit (handheld)

Description of handheld test kit

A battery-powered test kit is also available and capable of testing 

trip elements for Digitrip units 520/520M/520MC and Digitrip 220+, 

including power-up, instantaneous trip, short delay trip, and ground 

(earth) fault trip. These test selections are chosen with the switch 

labeled “Select Test” located in the upper right-hand corner of the 

test kit (see 

Figurt 39

). The test currents are not adjustable for this 

test kit.
The style number of this device is #70C1056.

Test procedure

Complete procedural instructions for the Eaton functional test kit can 

be found in I.L. #5721B13, which is packaged with each test kit.

Figurt 39. FuncoiNnal Ttso Kio

Note:

N

After completion of testing, perform a power-up by depressing Reset 

pushbutton, which will clear the trip memory. Disconnect cable from test kit 

to prevent accidental operation and battery drainage. Reset the Instantaneous 

setting to its original condition. Reposition the LTM jumper to the as-found 

condition. Install the small cover on the Digitrip and install the breaker’s 

plexiglass cover.

Currents

Each test selected by the Select Test switch on the test kit supplies 

a fixed milliampere current value. The long delay setting will affect 

the per unit (I

r

) current value and the response of the Digitrip unit.

Batteries

The functional test kit contains a total of seven 9V batteries. 

A lithium ion cell is the preferred battery type for BAT A and is 

attached to the main PC board of the test kit. This battery has a 

much longer lifespan to accurately perform the selected tests. The 

remaining six batteries are located on a separate board in the test kit 

and serve to power up the display on the 520M trip unit.
LEDs A and B function to represent sufficient battery voltage 

from both the single lithium cell and the six alkaline batteries, 

respectively. If either LED does not light or lights only dimly, replace 

the appropriate battery or batteries within the functional test kit 

case. To do this, open the back of the case using a screwdriver and 

remove the battery or batteries from their respective locations. For 

best results, replace lithium battery (Battery A) with ULTRALIFE

T

 

U9VL battery. When replacing battery sixpack (Battery B), replace all 

batteries at the same time using standard 9V alkaline batteries.

PtrfNrmanct otsoing fNr grNund faulo orip unios— 

primary injtcoiNn
Code requirements

The NEC, under Article 230-95-C, requires that any ground fault 

protection system be performance tested when first installed. 

Conduct tests in accordance with the approved instructions provided 

with the equipment. Make a written record of this test and make the 

results available to the authority having inspection jurisdiction.

Standards requirements

As a follow-up to the basic performance requirements stipulated 

by the NEC, UL Standard No. 1053 requires that certain minimum 

instructions must accompany each ground fault protection system. 

These statements (General test instructions), plus a copy of the 

record forms (

Figurt 44

Figurt 45

, and 

Figurt 46

), are included as 

part of this instructional leaflet.

General test instructions

The interconnected system must be evaluated only by qualified 

personnel and in accordance with the equipment assembler’s 

detailed instructions.
To avoid improper operations following apparently correct simulated 

test operations, the polarity of the neutral sensor connections 

(if used) must agree with the equipment assembler’s detailed 

instructions. Where a question exists, consult the specifying 

engineer and/or equipment assembler.

m

 WARNING

PERSONAL INJURY CAN OCCUR WHEN WORKING ON POWER SYSTEMS. 

ALWAYS TURN OFF POWER SUPPLYING BREAKER BEFORE CONDUCTING 

TESTS. TEST OUT OF THE CELL, IF POSSIBLE. THERE IS A HAZARD OF 

ELECTRICAL SHOCK OR BURN WHENEVER WORKING IN OR AROUND 

ELECTRICAL EQUIPMENT.

Verify the grounding points of the system using high voltage testers 

and resistance bridges to ensure that ground paths do not exist that 

could bypass the sensors.
Use a low voltage (0–24V), high-current, AC source to apply a test 

current of 125% of the Digitrip unit pickup setting through one 

phase of the circuit breaker. This should cause the breaker to trip 

in less than 1 second and operate the alarm indicator, if one is 

supplied. Reset the breaker and the alarm indicator. Repeat the  

test on the other two phases (see 

Figurt 40

).

Summary of Contents for 520

Page 1: ...URES EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS m WARNING OBSERVE ALL RECOMMENDATIONS NOTES CAUTIONS AND WARNINGS RELATING TO THE SAFETY OF PERSONNEL AND EQUIPMENT O...

Page 2: ...g 17 Section 4 Protection settings 22 General 22 Long delay current setting 22 Long delay time setting 23 Short delay current setting 23 Short delay time setting 23 Instantaneous current setting 24 Gr...

Page 3: ...LSIG 19 Figure 20 Digitrip 520M MLSI 20 Figure 21 Digitrip 520M MLSIA 20 Figure 22 Digitrip 520M MLSIG 20 Figure 23 Digitrip 520Mi MWLSIG 20 Figure 24 Digitrip 520MC CLSI 21 List of figures Descriptio...

Page 4: ...r use only in Magnum and Magnum DS circuit breakers eaton corporation www eaton com List of tables Description Page Table 1 Protection Types Available for Digitrip Trip Units 6 Table 2 Communication F...

Page 5: ...unit As current begins to flow through the breaker the sensors generate a secondary current that powers the trip unit The Digitrip 520 family of trip units provides five phase and two ground time curr...

Page 6: ...s Yes Yes Ground earth fault protection Ground fault option Yes Yes Yes Ground fault alarm No Yes d Yes d Ground fault pickup 25 100 x In c 25 100 x In c 25 100 x In c Ground fault delay I2 t at 0 625...

Page 7: ...messages alarm Overload long pickup X X X X High load alarm X N A N A N A Ground alarm N A X b X X b Remote messages trip Long delay trip X X X X Short delay trip X X X X Instantaneous trip X X X X G...

Page 8: ...OM ITS CONNECTOR DAMAGE TO INTERNAL CURRENT TRANSFORMERS MAY OCCUR DUE TO AN OPEN CIRCUIT CONDITION m CAUTION IF A RATING PLUG IS NOT INSTALLED IN THE TRIP UNIT THE UNIT WILL INITIATE A TRIP WHEN IT I...

Page 9: ...irements The cover is held in place by two cover screws Security is ensured by the insertion of a standard meter seal through the holes in both of the cover retention screws The plexiglass cover has a...

Page 10: ...etting for a time in excess of a 0 1 second delay The alarm relay will reset automatically if the ground current is less than the ground fault pickup see Figure 5 Note 4 High load alarm 520M 520MC mod...

Page 11: ...the force of the compressed spring by the permanent magnet When a tripping action is initiated the low energy trip actuator coil receives a tripping pulse from the Digitrip unit This pulse overcomes...

Page 12: ...ultiple ground scheme is shown in Figure 14 In this figure a ground fault is shown that has two possible return paths via the neutral back to its source The three neutral sensors are interconnected to...

Page 13: ...summed together at the PC board donut transformer to sense ground fault via element R5 b No jumper on secondary contacts B 6 B 7 c Neutral input if four wire is via contacts B 4 B 5 Neutral current in...

Page 14: ...3000 1 H13 3200 1 H14 630 1 H15 1250 1 H16 3150 1 H17 4000 1 H18 100 1 All secondary currents to be 1 00A nominal at full scale Insulation level 0 6 kV BIL 10 kV full wave Continuous thermal current r...

Page 15: ...ground sensing c This scheme is not applicable to four pole breakers No secondary contacts B 4 and B 5 are available on four pole breakers Do not jumper B 6 B 7 in four pole applications Ground Retur...

Page 16: ...B 7 to program the Digitrip to use element R4 c This scheme is not applicable to four pole breakers R5 R5 R5 T M2 M1 B5 B4 I 2 G I 2 G I 2 G I 2 G IG IG ig ig i 2 g i 2 G i 2 g i 2 g i 2 g N in B5 B5...

Page 17: ...s are digitized by the CHip chip The microcomputer continually digitizes these signals This data is used to calculate true rms current values which are then continually compared with the protection fu...

Page 18: ...e affected parts of the system When zone interlocking is employed a fault within the zone of protection of the breaker will cause the Digitrip 520 family of units to Trip the affected breaker immediat...

Page 19: ...models 520 520i and 520M 520Mi 520MC 520MCi trip units for use only in Magnum and Magnum DS circuit breakers eaton corporation www eaton com Figure 16 Digitrip 520 LI Figure 17 Digitrip 520 LSI Digit...

Page 20: ...rip models 520 520i and 520M 520Mi 520MC 520MCi trip units for use only in Magnum and Magnum DS circuit breakers eaton corporation www eaton com Figure 20 Digitrip 520M MLSI Figure 21 Digitrip 520M ML...

Page 21: ...7 8 9 95 1 0 t Response I2 Dependent on In In Max Amp Rating Current Sensor Rating Battery Check Reset Battery Test Step Unit Status Catalog 2 4 7 10 12 15 20 24 Short Delay Setting Short Delay Time...

Page 22: ...ound current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated time current curves are pictured on the face of the trip unit Each rotary switc...

Page 23: ...g Plug Long delay time setting There are eight available long delay time settings as illustrated in Figure 31 ranging from 2 24 seconds These settings are the total clearing times when the current val...

Page 24: ...nstantaneous Current Settings Ground fault current setting The eight ground fault current settings are labeled with values from 0 25 to 1 0 x In see Figure 36 The domestic U S models have a maximum of...

Page 25: ...ace Module BIM can be used to monitor up to 31 Digitrip 520MC trip units The acceptable addresses are 001 031 Remote master computer When desired Digitrip 520MC trip units can communicate with a BIM o...

Page 26: ...PING OPERATION WILL CAUSE DISRUPTION OF SERVICE AND POSSIBLE PERSONAL INJURY RESULTING IN THE UNNECESSARY SWITCHING OF CONNECTED EQUIPMENT m CAUTION TESTING A CIRCUIT BREAKER WHILE IT IS IN SERVICE AN...

Page 27: ...trip unit LEDs A and B function to represent sufficient battery voltage from both the single lithium cell and the six alkaline batteries respectively If either LED does not light or lights only dimly...

Page 28: ...d from the Cell A B C Suitable Conductors Low Voltage AC Current Source Primary Disconnect Stabs When Drawout Polarity and Identification A B C Suitable Conductors Low Voltage AC Current Source Primar...

Page 29: ...ip and associated Cause of Trip LEDs see Figure 15 Insulating Tab Rating Plug Door Flipped Open Use Type 1 3 N Lithium Battery Only Pull to Remove Battery Pull Out After Installation Battery installat...

Page 30: ...LE SENSOR RATING MATCHES THAT PRINTED ON THE RATING PLUG DOOR INSTALLING A RATING PLUG THAT DOES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MISCOORDINATION AND OR FAILURE OF THE PROTECTION SYSTEM...

Page 31: ...gitrip 220P or 520 LI L curve 70C1296 Digitrip 220P or 520 LI I curve 70C1006 Digitrip 520 LS curve 70C1007 Digitrip 520 I curve 70C1008 Digitrip 520 G curve 70C1446 Digitrip 520MC Maintenance Mode tr...

Page 32: ...d A blue LED confirms that the function is on For the other two methods of arming the Maintenance Mode function this switch must be in the position labeled 0 1 With this setting a remote switch wired...

Page 33: ...A blue LED on the Digitrip verifies that Maintenance Mode is armed b The recommended selector switch for this low voltage application is Eaton part number 10250T1333 2E which includes a contact block...

Page 34: ...e fault and will send an interlocking signal to the main trip unit The main trip unit will begin to time out and in the event that the feeder breaker Z2 does not clear the fault the main breaker will...

Page 35: ...in Magnum and Magnum DS circuit breakers eaton corporation www eaton com Figure 49 Typical Zone Interlocking Connections with Two Main Breakers M1 M2 and a Tie Breaker T F23 C ZO ZI F22 C ZO ZI T C Z...

Page 36: ...er See Section 2 Notes Trip unit is malfunctioning Replace trip unit High inrush phase currents may cause fictitious ground pickup momentarily Connect Zout to Zin jumper to provide some time delay see...

Page 37: ...INPUT 520M ONLY Z_COM BRKCLSD K2 8 K2 9 K2 7 K2 6 K2 5 K2 4 K2 3 K2 2 K2 1 A 30 A 29 A 27 A 28 B 19 B 18 OPTIONAL AUX SWITCH 52b 52a B 17 B 16 A 22 A 21 A 19 A 20 A 26 A 25 OPTIONAL AUX SWITCH 52b 52...

Page 38: ...COM network uses a 3 pin The RS 485 Modbus uses a 4 pin connector that consists of signals A B COMmon and SHielD Three baud rates of 1200 9600 or 19200 are selectable via programming switch for the Mo...

Page 39: ...structional Leaflet IL70C1037H05 Effective October 2009 Digitrip models 520 520i and 520M 520Mi 520MC 520MCi trip units for use only in Magnum and Magnum DS circuit breakers eaton corporation www eato...

Page 40: ...and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INC...

Reviews: