background image

32

Instructional Leaflet 

IL70C1037H05

Effective October 2009

Digitrip models 520, 520i; and 520M, 520Mi,

520MC, 520MCi trip units for use only in

Magnum and Magnum DS circuit breakers

eaton corporation

 www.eaton.com

Section 10: Digitrip 520Mc with  

Maintenance Mode 

WARNING

ONLY CERTIFIED AND COMPETENT PERSONNEL SHOULD ATTEMPT  

TO INSTALL OR MAINTAIN POTENTIALLY HAZARDOUS EQUIPMENT. 

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. 

ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. 

ALWAYS FOLLOW SAFETY PROCEDURES. EATON IS NOT LIABLE FOR THE 

MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.

CAUTION

OBSERVE ALL RECOMMENDATIONS, NOTES, CAUTIONS, AND WARNINGS 

RELATING TO THE SAFETY OF PERSONNEL AND EQUIPMENT. OBSERVE 

AND COMPLY WITH ALL GENERAL AND LOCAL HEALTH AND SAFETY 

LAWS, CODES, AND PROCEDURES.

CAUTION

A FLASH HAZARD ANALYSIS SHOULD BE DONE TO DETERMINE PERSONAL 

PROTECTIVE EQUIPMENT REQUIREMENTS.

Gtntral

Per the above WARNING, it is highly recommended that 

maintenance be conducted on electrical equipment, including  

circuit breakers with the system de-energized. 
For situations that arise where this is not possible, the Maintenance 

Mode function of the Digitrip 520MC family (

Cat. 5ARMLSI, 

5ARMLSIG, 5ARMLSIA

) can reduce arc flash incident energy that 

is generated on a fault condition. This is accomplished by an analog 

trip circuit which, when armed, provides a fast-acting response 

to the fault. The reduced arc condition will occur only in devices 

downstream of the trip unit in Maintenance Mode. This is separate 

from the normal system protection setting of Instantaneous. The 

Maintenance Mode is located in the upper, white portion of the unit. 

Mainotnanct MNdt stooings

The Maintenance Mode settings (labeled R5, R4, R3, R2, R1) 

provide the Arc Flash Reduction setting. R5 is the maximum 

reduction setting, which correlates to the lowest pickup value. 
Nominal trip current of Maintenance Mode settings:
Setting R5 

2.5 x Rating Plug Amperes

Setting R4  

4.0 x Rating Plug Amperes

Setting R3  

6.0 x Rating Plug Amperes

Setting R2  

8.0 x Rating Plug Amperes

Setting R1  

10.0 x Rating Plug Amperes

Arming Mainotnanct MNdt 

There are three ways to arm the Maintenance Mode Arc Flash 

Reduction setting. One method is locally via the two-position switch 

in the Maintenance Mode section of the trip unit. Turning the 

switch to the ON position will arm the setting selected. A blue LED 

confirms that the function is on.
For the other two methods of arming the Maintenance Mode 

function, this switch must be in the position labeled 0/1. With this 

setting, a remote switch wired through the breaker secondary 

contacts can remotely arm the Maintenance Mode setting. A 

high quality, gold-plated or palladium contact is required in this 

application. The blue LED will verify that the function is armed.  

(See wiring diagram 

Figurt 47

.)

A third method to arm the Maintenance Mode setting is via a 

communication device. A Palm Pilot along with an IR MINT device 

can be employed to arm the setting. By initiating the ENABLE 

setting, the Maintenance Mode selection in the control screen of 

the Palm, Maintenance Mode is set. There is a confirmation screen 

that verifies the arming. A BIM (Breaker Interface Module) is another 

communication method to arm the setting. When Maintenance 

Mode setting is enabled via device communications, this setting 

must be disabled by device communications.

RtmNot indicaoNr

The Magnum circuit breaker will be wired with secondary contacts 

A9 and A12. Circuit breakers built after September 2005 have a 

normally open contact available to customer use. This contact can 

be used to indicate remotely that the Maintenance Mode setting 

is armed. Refer to diagram below for a wiring of this remote (blue 

light) indicator.

ChNNsing oht rtducoiNn stooing

The Arcflash Reduction Maintenance System is an eight-position 

rotary switch that has five unique settings. Setting R5 is repeated 

four times. From the factory, the Magnum circuit breaker is shipped 

with the Digital unit set to the R5 setting and with its arming switch 

set to the 0/1 position. The 0/1 position means that it is locally 

OFF, but can be remotely turned ON. The blue LED, if illuminated, 

provides indication that the Maintenance Mode setting is armed 

per one of the three methods described on page 32. In general, the 

selection of one of the Reduction Settings (R5 through R1) should 

be determined and selected by a person who is experienced in 

power system analysis.
This setting choice normally does not change unless there are future 

system modifications that could increase or decrease fault levels at 

the circuit breaker location.

Tripping and otsoing

The Maintenance Mode function will provide fast tripping even when 

the regular Instantaneous is set to OFF. The Instantaneous LED 

position is also used to indicate a trip initiated by the Maintenance 

Mode setting. The LCD display, if powered, will indicate this with 

four dashes. 
The Maintenance Mode setting, external wiring (if any), and tripping 

functionality should be periodically verified by primary or secondary 

injection current testing.

Summary of Contents for 520

Page 1: ...URES EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS m WARNING OBSERVE ALL RECOMMENDATIONS NOTES CAUTIONS AND WARNINGS RELATING TO THE SAFETY OF PERSONNEL AND EQUIPMENT O...

Page 2: ...g 17 Section 4 Protection settings 22 General 22 Long delay current setting 22 Long delay time setting 23 Short delay current setting 23 Short delay time setting 23 Instantaneous current setting 24 Gr...

Page 3: ...LSIG 19 Figure 20 Digitrip 520M MLSI 20 Figure 21 Digitrip 520M MLSIA 20 Figure 22 Digitrip 520M MLSIG 20 Figure 23 Digitrip 520Mi MWLSIG 20 Figure 24 Digitrip 520MC CLSI 21 List of figures Descriptio...

Page 4: ...r use only in Magnum and Magnum DS circuit breakers eaton corporation www eaton com List of tables Description Page Table 1 Protection Types Available for Digitrip Trip Units 6 Table 2 Communication F...

Page 5: ...unit As current begins to flow through the breaker the sensors generate a secondary current that powers the trip unit The Digitrip 520 family of trip units provides five phase and two ground time curr...

Page 6: ...s Yes Yes Ground earth fault protection Ground fault option Yes Yes Yes Ground fault alarm No Yes d Yes d Ground fault pickup 25 100 x In c 25 100 x In c 25 100 x In c Ground fault delay I2 t at 0 625...

Page 7: ...messages alarm Overload long pickup X X X X High load alarm X N A N A N A Ground alarm N A X b X X b Remote messages trip Long delay trip X X X X Short delay trip X X X X Instantaneous trip X X X X G...

Page 8: ...OM ITS CONNECTOR DAMAGE TO INTERNAL CURRENT TRANSFORMERS MAY OCCUR DUE TO AN OPEN CIRCUIT CONDITION m CAUTION IF A RATING PLUG IS NOT INSTALLED IN THE TRIP UNIT THE UNIT WILL INITIATE A TRIP WHEN IT I...

Page 9: ...irements The cover is held in place by two cover screws Security is ensured by the insertion of a standard meter seal through the holes in both of the cover retention screws The plexiglass cover has a...

Page 10: ...etting for a time in excess of a 0 1 second delay The alarm relay will reset automatically if the ground current is less than the ground fault pickup see Figure 5 Note 4 High load alarm 520M 520MC mod...

Page 11: ...the force of the compressed spring by the permanent magnet When a tripping action is initiated the low energy trip actuator coil receives a tripping pulse from the Digitrip unit This pulse overcomes...

Page 12: ...ultiple ground scheme is shown in Figure 14 In this figure a ground fault is shown that has two possible return paths via the neutral back to its source The three neutral sensors are interconnected to...

Page 13: ...summed together at the PC board donut transformer to sense ground fault via element R5 b No jumper on secondary contacts B 6 B 7 c Neutral input if four wire is via contacts B 4 B 5 Neutral current in...

Page 14: ...3000 1 H13 3200 1 H14 630 1 H15 1250 1 H16 3150 1 H17 4000 1 H18 100 1 All secondary currents to be 1 00A nominal at full scale Insulation level 0 6 kV BIL 10 kV full wave Continuous thermal current r...

Page 15: ...ground sensing c This scheme is not applicable to four pole breakers No secondary contacts B 4 and B 5 are available on four pole breakers Do not jumper B 6 B 7 in four pole applications Ground Retur...

Page 16: ...B 7 to program the Digitrip to use element R4 c This scheme is not applicable to four pole breakers R5 R5 R5 T M2 M1 B5 B4 I 2 G I 2 G I 2 G I 2 G IG IG ig ig i 2 g i 2 G i 2 g i 2 g i 2 g N in B5 B5...

Page 17: ...s are digitized by the CHip chip The microcomputer continually digitizes these signals This data is used to calculate true rms current values which are then continually compared with the protection fu...

Page 18: ...e affected parts of the system When zone interlocking is employed a fault within the zone of protection of the breaker will cause the Digitrip 520 family of units to Trip the affected breaker immediat...

Page 19: ...models 520 520i and 520M 520Mi 520MC 520MCi trip units for use only in Magnum and Magnum DS circuit breakers eaton corporation www eaton com Figure 16 Digitrip 520 LI Figure 17 Digitrip 520 LSI Digit...

Page 20: ...rip models 520 520i and 520M 520Mi 520MC 520MCi trip units for use only in Magnum and Magnum DS circuit breakers eaton corporation www eaton com Figure 20 Digitrip 520M MLSI Figure 21 Digitrip 520M ML...

Page 21: ...7 8 9 95 1 0 t Response I2 Dependent on In In Max Amp Rating Current Sensor Rating Battery Check Reset Battery Test Step Unit Status Catalog 2 4 7 10 12 15 20 24 Short Delay Setting Short Delay Time...

Page 22: ...ound current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated time current curves are pictured on the face of the trip unit Each rotary switc...

Page 23: ...g Plug Long delay time setting There are eight available long delay time settings as illustrated in Figure 31 ranging from 2 24 seconds These settings are the total clearing times when the current val...

Page 24: ...nstantaneous Current Settings Ground fault current setting The eight ground fault current settings are labeled with values from 0 25 to 1 0 x In see Figure 36 The domestic U S models have a maximum of...

Page 25: ...ace Module BIM can be used to monitor up to 31 Digitrip 520MC trip units The acceptable addresses are 001 031 Remote master computer When desired Digitrip 520MC trip units can communicate with a BIM o...

Page 26: ...PING OPERATION WILL CAUSE DISRUPTION OF SERVICE AND POSSIBLE PERSONAL INJURY RESULTING IN THE UNNECESSARY SWITCHING OF CONNECTED EQUIPMENT m CAUTION TESTING A CIRCUIT BREAKER WHILE IT IS IN SERVICE AN...

Page 27: ...trip unit LEDs A and B function to represent sufficient battery voltage from both the single lithium cell and the six alkaline batteries respectively If either LED does not light or lights only dimly...

Page 28: ...d from the Cell A B C Suitable Conductors Low Voltage AC Current Source Primary Disconnect Stabs When Drawout Polarity and Identification A B C Suitable Conductors Low Voltage AC Current Source Primar...

Page 29: ...ip and associated Cause of Trip LEDs see Figure 15 Insulating Tab Rating Plug Door Flipped Open Use Type 1 3 N Lithium Battery Only Pull to Remove Battery Pull Out After Installation Battery installat...

Page 30: ...LE SENSOR RATING MATCHES THAT PRINTED ON THE RATING PLUG DOOR INSTALLING A RATING PLUG THAT DOES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MISCOORDINATION AND OR FAILURE OF THE PROTECTION SYSTEM...

Page 31: ...gitrip 220P or 520 LI L curve 70C1296 Digitrip 220P or 520 LI I curve 70C1006 Digitrip 520 LS curve 70C1007 Digitrip 520 I curve 70C1008 Digitrip 520 G curve 70C1446 Digitrip 520MC Maintenance Mode tr...

Page 32: ...d A blue LED confirms that the function is on For the other two methods of arming the Maintenance Mode function this switch must be in the position labeled 0 1 With this setting a remote switch wired...

Page 33: ...A blue LED on the Digitrip verifies that Maintenance Mode is armed b The recommended selector switch for this low voltage application is Eaton part number 10250T1333 2E which includes a contact block...

Page 34: ...e fault and will send an interlocking signal to the main trip unit The main trip unit will begin to time out and in the event that the feeder breaker Z2 does not clear the fault the main breaker will...

Page 35: ...in Magnum and Magnum DS circuit breakers eaton corporation www eaton com Figure 49 Typical Zone Interlocking Connections with Two Main Breakers M1 M2 and a Tie Breaker T F23 C ZO ZI F22 C ZO ZI T C Z...

Page 36: ...er See Section 2 Notes Trip unit is malfunctioning Replace trip unit High inrush phase currents may cause fictitious ground pickup momentarily Connect Zout to Zin jumper to provide some time delay see...

Page 37: ...INPUT 520M ONLY Z_COM BRKCLSD K2 8 K2 9 K2 7 K2 6 K2 5 K2 4 K2 3 K2 2 K2 1 A 30 A 29 A 27 A 28 B 19 B 18 OPTIONAL AUX SWITCH 52b 52a B 17 B 16 A 22 A 21 A 19 A 20 A 26 A 25 OPTIONAL AUX SWITCH 52b 52...

Page 38: ...COM network uses a 3 pin The RS 485 Modbus uses a 4 pin connector that consists of signals A B COMmon and SHielD Three baud rates of 1200 9600 or 19200 are selectable via programming switch for the Mo...

Page 39: ...structional Leaflet IL70C1037H05 Effective October 2009 Digitrip models 520 520i and 520M 520Mi 520MC 520MCi trip units for use only in Magnum and Magnum DS circuit breakers eaton corporation www eato...

Page 40: ...and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INC...

Reviews: