background image

MAIN DEVICE

MOUNTING FEET

MOUNTING RAIL(S)

“X”

“Z”

MOUNTING FEET

Fig. 1 Locations of Mounting Feet, Rails, and Modules

Fig. 2  Ring Type and Ringless Covers

METER COVER

SCREWS

MOVABLE LATCH

RING STYLE

COVER

RINGLESS STYLE

COVER

35SS, 37SS - 2,3 METER

35SS, 37SS - 1 METER

1MM, 3MM - 200 AMP

1MM, 3MM - 125 AMP

TYPE OF METER MODULE

35-3/16 (893.76)

17-1/16 (433.39)

34-7/32 (869.16)

34-7/32 (869.16)

“X” in.(mm)

18-1/2 (469.90)

19-27/32 (504.03)

18-15/32 (469.11)

12-19/32 (319.88)

“Z” in.(mm)

35MM, 37MM - 2 METER

35MM, 37MM - 1,3,4 METER

30-11/16 (779.46)

30-11/16 (779.46)

27 (685.80)

13 (330.20)

Installation Instructions for Type 1MM, 3MM, 35MM, 37MM,

35SS, and 37SS Modular Metering Centers

H A Z A R D O U S   VO LTAG E .   W I L L   C AU S E

SEVERE INJURY OR DEATH.

VOLTAJE  PELIGROSO.  CAUSA  HERIDAS

SEVERAS O MUERTE.

Turn  OFF power  supplying  this  equipment  before  working

inside.

INTERRUMPA  el  suministro  de  energia  que  alimenta  este

e q u i p o   a n t e s   d e   t r a b a j a r   e n   e l   i n t e r i o r   d e l   m i s m o.

PELIGRO

DANGER

MOUNTING FEET:

Swivel the mounting feet at the top and bottom of the en-

closures as shown (meter modules have two mounting feet

and main devices have four mounting feet).  After marking

holes on the wall, the mounting feet may be moved away

for drilling of the holes. (See Fig. 1 below).

Please read these instructions completely before installing

or removing device.  Improper installation could be

hazardous to personnel and/or equipment.
Por favor lea estas instrucciones en su totalidad antes de

instalar o mover el aparato.  Una instalacion inapropiada

puede ser peligrosa para el personal y/o el equipo.
Veuillez lire les présentes directives au complet avant

d’installer ou de retirer le dispositif.  Une mauvaise installation

pourait causer des blessures au personnel et/ou

endommager l’equipement.

INSTALL MOUNTING RAILS ON WALL:

Establish the required height of the centerline  of the bottom

meter socket, per the utility company specifications.

Determine the bottom line of the meter modules and main

devices.  Use a “Z” dimension per the table below.  That

is the distance from the bottom meter socket line to the

bottom of a meter module.

Measure up a distance “X” (see table) inches from the

bottom line of the meter modules to mounting holes for the

mounting rail.  Strike a level line for the fasteners and attach

the mounting rails. (See Fig. 1 below).

METER SOCKET COVERS:

Remove all the meter socket covers which are over the

horizontal main bus.  Ring style covers are attached with

two screws inside the socket rim.  Ringless style covers

are attached with an external movable latch. (See Fig. 2).

Ringless style covers have barrel lock provision K.O.  To

use, remove knockout and apply kit 3MMBLKIT or 37MMBLK.

METER MODULES:

Hang meter modules on the mounting rails, loosen all of

the main bus joint bolts, and slide the meter modules

together.

Fasten the enclosures together, in order to bond devices

together and provide suitable ground path, with the (2) #  -

20 screws supplied with each module.

Torque to 26 lb-in (2.94 N-m).

Torque each main bus joint bolt to 300 lb-in (33.90 N-m).

Secure mounting feet to the wall. (See Fig. 3 on Page 2).

TENSION  DANGEREUSE.  PEUT  CAUSER

DES  BLESSURES  GRAVES  OU  LA  MORT.

Couper  l’alimentation  électrique de  cet  équipement  avant

d’y effectuer des travaux.

)

I.L. 70-8306

1