Hook on hot lead to the 1L1Lug, Hook the other hot lead to 3L2 lug and then hook your ground wire to our
ground lug.
Hook one hot lead to the 1L1 lug, hook another to the 3L2 lug and then hook the third leg to the 5L3 lug.
Run ground wire to our ground lug. Start Compressor and check rotation. If rotation is reversed, shut off
power and switch two of your hot leads.
**Be sure that your power supply and internal wiring are adequate and that the available frequency and
voltage correspond to that on the motor nameplate. A 230-volt motor will rarely work satisfactorily on a
nominal 208-volt system. Even if the actual voltage is up to 208 volts, the 10 to 12 volt drop during the
starting (this is an average, but not a high figure for commercial buildings), may cause the motor to labor
and blow fuses or heater elements. Do not accept the nominal figure for line voltage, but rather measure it
with a voltmeter during a period of maximum powerdemand.
The compressors are equipped with intake filters requiring no piping. If it is necessary to pipe intake to the
outdoors, see Paragraph 3, “Location”.
A flexible connector should be used between compressor tank and building piping or connection to
aftercooler or other similar equipment in order to minimize noise, vibration, vibration damage, and wear
and tear.
Tank feet should be placed on vibration isolator pads available through your dealer. Anchor bolts should
be gently snugged,
but not tight
, to allow for vibration. Remember, the bolt is only a guide to hold the
compressor in place. Do not over tighten the legs of the tank against the pads…it will damage your tank.
CAUTION
: Do not set tank on dirt. Over time, the tank will tilt causing pump failure from no lubrication.
A. Never install a shut-off valve, such as a glove or gate valve, between the compressor discharge
opening and the receiver unless a safety valve is installed in the line between this valve and the
compressor.
B. Never operate pump at pressures or speeds in excess of those recommended by factory.
Caution
Tank
Pipe Connection
Air intake
3
Single Phase Motors:
Three Phase Motors: