EasyIO FC20 User Reference v1.3

 

Universal Input Connection 

 

EasyIO FC-20 has twelve non-isolated universal inputs. The universal input supports three type of analog 
signal i.e. resistance, voltage and current transmitter via hardware jumper and internal register settings:  

a)  Resistance  –  The  working  range  of  resistance  is  0  –  300K  Ohms.  If  the  input  is  configured  as 

Thermistor  type,  the  system  provides  8  customizable  temperature  lookup  tables  for  resistance  to 
temperature translation. The commonly used Thermistor like 10K, 10K with Shunt, 1K Balco and 1K 
Platinum are all supported 

b)  Voltage  –  Two  selection  of  working  range  0  –  5V  and  0  –  10V.  The  minimum  input  impedance  of 

voltage input is 1 Mega Ohm. 

c)  Current – Two selection of working ranges 0 – 20mA and 4 – 20mA. The current input impedance is 

less than 25 Ohm. 

d)   Pulse Input – Only UI1, UI2, UI3 and UI4 are capable of receiving high speed pulse. Minimum on time 

pulse is 25ms and minimum off time is 25ms. Refer to image below. 

Universal Input Connection 

 

Summary of Contents for FC 20

Page 1: ...EasyIO FC20 User Reference v1 3 EasyIO FC 20 DDC User Reference V1 3...

Page 2: ...erence v1 3 Document Change Log 1st April 2013 Document created 13th July 2013 Software configurations added 27th Sept 2014 FC now support pulse input 6th June 2015 Serial address image Serial Port se...

Page 3: ...EasyIO FC20 User Reference v1 3 Disclaimer EasyIO FC 20 is a product by EasyIO Holdings Pte Ltd Sedona Framework is a trademark of Tridium Inc...

Page 4: ...ns 6 Power supply Connection 6 RS485 Connection 7 Jumpers Setting 9 Digital Output Wiring Connection 11 Universal Input Connection 12 Analog Output Connection 13 Buttons and Indications 14 Software Co...

Page 5: ...as Roof Top Units Fan Coils AHU s package units etc EasyIO FC20 controller comes with built in bootloader program Built in bootloader program will enable user to upgrade firmware without sending back...

Page 6: ...specification for the working range In order to avoid damage on the controller input output devices and RS485 connection use individual power supply for each controller If a single power supply is use...

Page 7: ...he controller should be wired in daisy chain network topology as shown as image below If wire branch can be avoided keep it as short as possible and never connect more than one device to the wire bran...

Page 8: ...ACnet MSTP Modbus Baud Rate 19 2K Parity even Data Bit 8 Not editable Stop Bit 1 BACnet Baud Rate 19 2K Port 1 is used to perform Firmware flashing FwTool exe Virtual Device for program downloads FcVi...

Page 9: ...rotocol toggle the 1 of the dip switch to ON The remaining DIP switch 2 8 are for BACnet MSTP ID or Modbus Serial ID address 0 is not available it will be set to 1 depending on DIP switch 1 selection...

Page 10: ...tch number Functions Remarks 1 Protocol Setting On Bacnet MSTP Off Modus RTU 2 Serial Address Address 64 MSB 3 Serial Address Address 32 4 Serial Address Address 16 5 Serial Address Address 8 6 Serial...

Page 11: ...ing Connection EasyIO FC 20 has four general purpose isolated digital output connections relay output Each relay output able to drive up to 1A 30VDC 48VAC load It does not output voltage or current It...

Page 12: ...s 8 customizable temperature lookup tables for resistance to temperature translation The commonly used Thermistor like 10K 10K with Shunt 1K Balco and 1K Platinum are all supported b Voltage Two selec...

Page 13: ...Output can be configured to drive voltage or current output via hardware jumper setting and internal register settings The working range for voltage is 0 10V and for current either 0 20mA or 4 20mA F...

Page 14: ...ED to indicate its current state Button and LED indications LED Conditions Description 1 PWR PWR is used to indicate the presence of 24VAC power source and internal power 2 ERR ERR is to indicate when...

Page 15: ...les and kits files Step 1 Get the required files from EasyIO technical support at support easyio com The files are the Sedona kits and platform manifest for the EasyIO FC series Step 2 Close the workb...

Page 16: ...EasyIO FC20 User Reference v1 3 Step 5 For Niagara Ax 3 6 xx user Drag and drop it in to the sedona root folder Hit Yes on the pop up to merge the files...

Page 17: ...6 For Niagara Ax 3 7 xx user Drag and drop it in to the sedona root folder Hit Yes on the pop up to merge the files Step 7 Re open workbench and connect to EasyIO FC 20 controller Refer to EasyIO FC 2...

Page 18: ...EasyIO FC20 User Reference v1 3 Technical Support For technical issue please contact Email support easyio com...

Reviews: