Temperature Modes

 

The thermostat controls to the target temperature by switching the relay ON/OFF as required. The

 

control logic has hysteresis i.e. in the heating mode the temperature has to exceed the target setpoint

 

plus the hysteresis to switch the relay OFF to prevent fast on/offs. In cooling mode this operates in

 

reverse. The diagram below illustrates the temperature control operation.

 

The target temperature is typically adjusted by the user by pressing UP & DOWN buttons. The target 

temperature is changed in different operating situations;

 

COMFORT MODE; target temperature as adjusted by the user (or via the networked
system) and displayed on the screen

ECONOMY MODE; target temperature switched to the ECONOMY setpoint

OFF MODE; the thermostat is OFF, but FROST setpoint is active protecting the building

Centigrade to Fahrenheit

 

ECO Mode

 

EIO

-55  Series  has  Fahrenheit  to  Celcius  icons  on  the  top 

of the Home Screen. From this icon it is possible to change 
the units by touching this icon.

 

This option is particularly useful in hospitality applications 
where the client base is expected to be international.

 

NOTE: 

EIO

-55 series has all configuration parameters 

displayed in Fahrenheit only.

  

The thermostat is switched to ECO mode via network

or via digital input. The thermostat operates also in the ECO 
mode when the Holiday mode has been activated.

 

In the ECO mode the thermostat controls to the ECO 
heating/cooling setpoint and the current target setpoint is 
displayed on the screen.

 

When in the ECO mode, the ECO mode can be cancelled by 
pressing the ECO icon on the front screen. Last command 
controls the thermostat state i.e if the thermostat has been 
switched to ECO mode via a digital input or over the network, the 
user can cancel the mode through the touchscreen. 

OFF Mode

 

The thermostats can be switched to OFF mode via

 

the touchscreen, digital volt-free input (e.g. time

 

clock) or via the communication network (system

 

configuration). The thermostat switches also to OFF

 

mode when the cleaning mode has been activated.

 

In the OFF mode the current Frost Setpoint is

 

displayed as the target temperature. 

When in OFF mode if room temperature drops below

 

the Frost Setpoint, the frost protection is activated,

 

the SNOWFLAKE icon is displayed on the screen

 

and the relay output is switched ON. When the  
thermostat has been overridden to OFF mode via the 
network, or a digital input transition, the user can  
cancel the OFF mode by pressing the OFF icon.  
Similarly, a networked thermostat driven to OFF  
mode by the user can be overridden back to  
COMFORT mode using the network master. 

Boost

 

Holiday Mode

 

Cleaning Mode

 

The thermostat relay can be switched ON for a timed period by activating the BOOST function. The

 

BOOST overrides the automatic temperature control and switches the output ON. As default the boost

 

time is set to 0 (deactivated).

 

After entering FURTHER INFORMATION screen, by selecting the HOLIDAY icon, it is possible to set

 

the number of days of holidays. The available range is 0-31 days. After setting the holiday, the

 

thermostat immediately switches to OFF mode (alternatively 

EIO

 can switch to ECO MODE during

 

holidays, see configuration parameters).
By setting holiday to 0 or just by pressing ENTER button the thermostat switches to permanent 

 

HOLIDAY MODE. The HOLIDAY MODE can be cancelled by pressing the HOLIDAY ICON. 

After entering FURTHER INFORMATION screen, by selecting the CLEANING icon, it is possible to

 

Summary of Contents for EIO-55 Series

Page 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Page 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Page 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Page 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Page 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Page 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Page 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Page 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Page 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Page 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Page 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Page 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Page 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Page 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Page 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Page 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Page 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...