![EasyIO EIO-55 Series Product Manual Download Page 17](http://html1.mh-extra.com/html/easyio/eio-55-series/eio-55-series_product-manual_3618763017.webp)
EIO
-55
16
40123
Humidity Sensor Calibration
REAL
-10.0..+10.0 °F
40124
Humidity Display
Unsigned
0
= Disabled
1
= Enabled (default)
40125
Cleaning Mode Time
Unsigned
0..480 minutes (Default 0)
40126
Boost Mode Time
Unsigned
0..480 minutes (Default 0)
40127
Backlight
Unsigned
0..20 (default 5)
40128
Relay Control Mode
Unsigned
0
= Normally Open (Default)
1
= Normally Closed
40129
Lock Mode Password
Unsigned
0000...9999 (Default 0000)
40130
Maintenance Mode Password
Unsigned
0000...9999 (Default 6666)
40134
Enable Holiday Symbol
Unsigned
0
= Disabled
1
= Enabled (Default)
40135
Holiday Mode Target
Unsigned
0
= OFF/Frost Mode (Default)
1
= ECO Mode
40137
Staff Access Code
Unsigned
0000...9999
40138
Language
Unsigned
0
= English
1
= Finnish
2
= Swedish
40139
Zone 1 Text (Room Sensor
Unsigned
1
= Room (Default)
Description)
2
= Floor
3
= Outside
4
= Zone 1
5
= Zone 2
6
= Zone 3
7
= Bathroom
8
= Sauna
9
= Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
40140
Zone 2 Text (Floor Sensor
Unsigned
0
= Disabled
Description)
1
= Room
Default: 2 = Floor
2
= Floor
Note: Disabled removes the text
3
= Outside
and the Floor measurement from
4
= Zone 1
the display.
5
= Zone 2
40141
Zone 3 Text (Outside / Network
Unsigned
6
= Zone 3
7
= Bathroom
Sensor Description)
8
= Sauna
Default: 3 = Outside
9
= Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
40142
Outside Temperature Source
Unsigned
0
= Internal Sensor (Default)
1
= Network Temperature
40300
MAC Address
Unsigned
0..127 (Default 1)
40301
BACnet Baud Rate
Unsigned
0
= 9600 (Default)
1
= 19200
2
= 38400
3
= 57600
4
= 76800
40400
Force Reset
Unsigned
0
= Normal (Default)
1
= Force Reset
40401
Non Volatile Memory Update
Unsigned
0
= Normal
1
= Update
40403
Force Factory Defaults
Unsigned
0
= Normal (Default)
1