EasyIO EIO-55 Series Product Manual Download Page 13

EIO

-55 

  12 

applied (default)

 

1

 

= Thermostat Off when power

 

applied

 

118

 

Lock Mode

 

Unsigned 16

 

0..3

 

0

 

= Lock mode disabled (default)

 

1

 

= On/Off/Boost workable only

 

2

 

= Temp settings only available

 

3

 

= All buttons disabled

 

119

 

Enable Temperature Units Swap

 

Unsigned 16

 

0..1

 

0

 

= Disabled

 

1

 

= Enabled (Default)

 

120

 

Sensor Calibration

 

Signed 16

 

-100..+100

-10.0..+10.0 °F

121

 

RI1 Sensor Calibration

 

Signed 16

 

-100..+100

-10.0..+10.0 °F

122

 

RI2 Sensor Calibration

 

Signed 16

 

-100..+100

-10.0..+10.0 °F

123

 

Humidity Sensor Calibration

 

Signed 16

 

-100..+100

-10.0..+10.0 %rH

124

 

Humidity Display

 

Unsigned 16

 

0..1

 

0

 

= Disabled

 

1

 

= Enabled (default)

 

125

 

Cleaning Mode Time

 

Unsigned 16

 

0...480

 

0..480 minutes (Default 0)

 

126

 

Boost Mode Time

 

Unsigned 16

 

0...480

 

0..480 minutes (Default 0)

 

0

 

= Disabled

 

127

 

Backlight

 

Unsigned 16

 

1..20

 

0..20 (default 5)

 

128

 

Relay Control Mode

 

Unsigned 16

 

0..1

 

0

 

= Normally Open (Default)

 

1

 

= Normally Closed

 

129

 

Lock Mode Password

 

Unsigned 16

 

0..9999

 

0000...9999

 

130

 

Maintenance Mode Password

 

Unsigned 16

 

0..9999

 

0000...9999

 

131

 

Override A/C

 

Unsigned 16

 

0..2

 

0

 

= None (default)

 

1

 

= Override On

 

2

 

= Override Off

 

132

 

Override Lights

 

Unsigned 16

 

0..2

 

0

 

= None (default)

 

1

 

= Override On

 

2

 

= Override Off

 

133

 

Override Lock Mode

 

Unsigned 16

 

0..2

 

0

 

= None (default)

 

1

 

= Lock Screen

 

2

 

= Cancel Lock Mode

 

Register

 

Parameter Description

 

Data Type

 

Raw Data

 

Range

 

134

 

Enable Holiday Symbol

 

Unsigned 16

 

0..1

 

0

 

= Disabled

 

1

 

= Enabled (default)

 

135

 

Holiday Mode Target

 

Unsigned 16

 

0..1

 

0

 

= OFF/Frost Mode (default)

 

1

 

= ECO Mode

 

136

 

Relay Network Override (Overrides the relay

 

Unsigned 16

 

0..2

 

0

 

= No Override (Default)

 

drive directly)

 

1

 

= Override Relay On

 

2

 

= Override Relay Off

 

137

 

Staff Code

 

Unsigned 16

 

0..9999

 

0000...9999

 

138

 

Language

 

Unsigned 16

 

0..2

 

0 = English (Default)

 

1

 

= Finnish

 

2

 

= Swedish

 

139

 

Zone 1Text (Room Sensor Description)

 

Unsigned 16

 

1..15

 

1 = Room (Default)

 

2

 

= Floor

 

3

 

= Outside

 

4

 

= Zone 1

 

5

 

= Zone 2

 

6

 

= Zone 3

 

7

 

= Bathroom

 

8

 

= Sauna

 

9

 

= Bedroom

 

10 = Kitchen

 

11 = Cooler

 

12 = Flow

 

13 = Hot Water

 

14 = Tank

 

15 = Pool

 

140

 

Zone 2 Text (Floor Sensor Description)

 

Unsigned 16

 

0..15

 

0 = Disabled

 

Default: 2 = Floor

 

1

 

= Room

 

Note: Disabled removes the text and the

 

2

 

= Floor

 

Floor measurement from the display.

 

3

 

= Outside

 

141

 

Zone 3 Text (Outside / Network Sensor

 

Unsigned 16

 

0..15

 

4

 

= Zone 1

 

5

 

= Zone 2

 

Description)

 

6

 

= Zone 3

 

Default: 3 = Outside

 

7

 

= Bathroom

 

Note: Disabled removes the text and the

 

8

 

= Sauna

 

Floor measurement from the display.

 

9

 

= Bedroom

 

10 = Kitchen

 

Summary of Contents for EIO-55 Series

Page 1: ...EIO 55 PRODUCT MANUAL BACnet or Modbus Touchscreen Thermostat EIO 55 MOD EIO 55 BAC EIO 55 MOD HUM EIO 55 BAC HUM...

Page 2: ...Model Type Model Description Modbus 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL BACnet MSTP 3 5 Touchscreen Thermostat Non Programmable 24Vac dc Power Supply Non UL EIO 55...

Page 3: ...000 6 1 2001 Generic Immunity EN60730 1 2016 Low Voltage EN6100 4 2 4 5 11 ESD Transient Surges Interruptions Degree of Protection IP20 Housing Housing Material Polycarbonate Plastics Self Extinguishi...

Page 4: ...FUNCTION BASED ICON in holiday mode shows the holiday icon from where the holiday mode can be cancelled in cleaning mode shows the cleaning icon from where the mode can be can celled in BOOST mode sho...

Page 5: ...fault the built in temperature sensor but can be configured to use an external sensor connected to RI1 The description for the room temperature can be changed via Room Text parameter in the configurat...

Page 6: ...s the thermostat state i e if the thermostat has been switched to ECO mode via a digital input or over the network the user can cancel the mode through the touchscreen OFF Mode The thermostats can be...

Page 7: ...ivated The lock mode can be configured to work in different ways DISABLED Lock Mode Icon Not Available ON OFF BOOST ONLY Allows On Off Boost Buttons Only ADJUST ONLY Allows Temperature Adjustment Or O...

Page 8: ...ct closes the DI Contact Alarm alarm message is displayed on the screen Network option is selected when the digital input is used for monitoring purposes only Humidity Measurement and Display RH optio...

Page 9: ...ol 2 Heating Cooling Change Over Min Limit Underfloor Heating Minimum Limit Setpoint 0 0 95 0 F Default 64 0 F Max Limit Underfloor Heating Maximum Limit Setpoint 0 0 122 0 F Default 86 0 F Limit Hyst...

Page 10: ...C Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable Holiday Enable Holiday Icon 0 Disabled 1 Enabled default Humidity Display Enable Disable Humidity Display if option fitted 0 Disab...

Page 11: ...nges are carried out over the network Modbus or BACnet then NonVol Update register object is required to be forced on to save the changes The register will automatically return to normal state when us...

Page 12: ...Default 64 0 F Register Parameter Description Data Type Raw Data Range 104 Minimum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 57 0 F 105 Maximum Setpoint Unsigned 16 0 950 0 0 95 0 F Default 86 0...

Page 13: ...2 Override Lights Unsigned 16 0 2 0 None default 1 Override On 2 Override Off 133 Override Lock Mode Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode Register Parameter Description Data...

Page 14: ...trol 0 1 Off On Relay Output Override Relay Mode Network FUNCTION CODE 04 READ INPUT REGISTERS 0 Built In Temperature Measurement Signed 16 400 3020 40 0 150 0 C 40 0 302 0 F 1 Underfloor Temperature...

Page 15: ...AV 9 LCD Brightness AV 10 Control Hysteresis AV 11 Network Temp AV 12 Nominal Setpoint Binary Input 3 BI 0 Digital Input DI1 BI 1 Cleaning Mode Status BI 2 Boost Mode Status Binary Output 9 BO 0 Relay...

Page 16: ...ture Sensor Unsigned 0 Disabled Default Mode 1 Main Control 2 Outdoor Temperature Display 3 System Networked Solutions 40108 Rin2 Underfloor Temperature Unsigned 0 Disabled default Sensor Mode 1 Min M...

Page 17: ...d 1 Room Default Description 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 Pool 40140 Zone 2 Text Floor Sensor Unsigned...

Reviews: