GT200 series general purpose inverter instruction manual
0x331A
AI2
0x331B
Set length
0x331C
Set accelerating time 1
0x331D
Set decelerating time 1
0x331E
Running command given channels:
0: Panel control
1: Terminal control
2: Serial port control
0x331F
Inverter state character 2
0x3320
Frequency given channels:
0: Digit given 1, keyboard
▲ ▼ adjustment
1: Digit given 2: Terminal UP/DN adjustment
2: Digit given 3: Serial Port
3: AI1 Analog Given
4: AI2 Analog Given
5: Terminal PULSE given
6: Panel analog given
0x3321
Accumulated length
Inverter’s control bits are defined as follows:
Control
Words (Bits)
Value
Significance
Function Description
BIT2, 1, 0
111B
Running
command
Start the inverter
110B
Method 0 parking
Park according to the set
decelerating time
101B
Method 1 parking
Park freely
011B
Method 2 parking
The fastest decelerating time
parking.
100B
External fault
parking
Park freely, and the inverter
displays an external fault.
Others
No command
BIT3
1
Reversal
Rotational direction when the
running command is set valid
(invalid for Jog commands)
0
Forward rotating
BIT4
1
Jog forward
rotating
0
Jog forward
rotating invalid