GT200 series general purpose inverter instruction manual
Table 6-2 Changing time of inverter parts
Part name
Standard changing time
Fan
2
~
3 years
Electrolytic capacitor
4
~
5 years
PCB
5
~
8 years
Fuse
10 years
Applicable condition for changing time of aforementioned inverter parts
(1) Environment temperature
:
Annual average is 30
℃
.
(2) Load factor: Less than 80%
(3) Running time: Less than 12 hours every day
86